Install the Storage Server Into the Slide-Rail Assemblies
■
“Mark the Rackmount Location” on page 31
■
“Install the Storage Server Into the Slide-Rail Assemblies” on page 38
Install the Storage Server Into the Slide-Rail Assemblies
Use this procedure to install the storage server chassis, with mounting brackets, into the slide-
rail assemblies that are mounted to the rack.
Caution -
Personal Injury or Equipment Damage
: This procedure requires a minimum of
two people because of the weight of the storage server.
Caution -
Always load equipment into a rack from the bottom up so that the rack will not
become top-heavy and tip over. To prevent the rack from tipping during equipment installation,
extend your rack's anti-tilt bar.
1.
Push the slide-rails into the slide-rail assemblies in the rack as far as possible.
2.
Position the storage server so that the rear ends of the mounting brackets are
aligned with the slide-rail assemblies that are mounted in the rack.
38
Oracle Exadata Storage Server X6-2 High Capacity Installation Guide • July 2018
Содержание Exadata Storage Server X6-2 High Capacity
Страница 1: ...Oracle Exadata Storage Server X6 2 High Capacity Installation Guide Part No E63691 03 July 2018 ...
Страница 2: ......
Страница 8: ...8 Oracle Exadata Storage Server X6 2 High Capacity Installation Guide July 2018 ...
Страница 24: ...24 Oracle Exadata Storage Server X6 2 High Capacity Installation Guide July 2018 ...
Страница 64: ...64 Oracle Exadata Storage Server X6 2 High Capacity Installation Guide July 2018 ...
Страница 68: ...68 Oracle Exadata Storage Server X6 2 High Capacity Installation Guide July 2018 ...