SYSTEM SETUP
Pamux User’s Guide
2-7
The watchdog timeout interval is set within the hardware and cannot be changed by the user. Refer to
Table 2-3 for minimum, typical, and maximum watchdog timeout values.
Table 2-3: Watchdog Timeout Values
M
Miinniim
muum
m
TTyyppiiccaall
M
Maaxxiim
muum
m
1.0 sec
1.6 sec
2.25 sec
Jumpers 7 and 8 (Reset)
One of the control lines on the Pamux bus is the reset line. This line is used for turning off the relays on
all Pamux stations on the bus. Note that the reset is not intended to be used to shut off outputs upon a
system communication error.
Two jumpers control how the reset line affects the B4. Jumper 7 determines the polarity of the reset
line, either active high or active low, as shown in Table 2-4. In general, it does not matter which polarity
you select as long as you are consistent throughout your Pamux system.
Table 2-4: B4 Reset Jumper
RReesseet t LLeevveell
JJuum
mppeer r 77
Active High
In
Active Low
Out
Jumper 8 determines how the reset line affects the watchdog timer function of channel 0.
If jumper 8 is not installed, the reset line will not affect the watchdog timer function. Hence, if channel 0
activates due to a watchdog condition, an active reset line will have no effect on channel 0 (although it
will deactivate any other channels that are on).
If jumper 8 is installed and the watchdog jumpers are configured to activate channel 0 upon a timeout,
the state of channel 0 depends on whether or not the reset activates before the timeout occurs:
•
If the reset line activates first, all outputs will deactivate. If a subsequent timeout occurs, no
effect will take place until the reset line deactivates, at which time the watchdog function will
take place and channel 0 will activate.
•
If the timeout occurs first, the watchdog function takes place and channel 0 activates. If a
subsequent reset occurs, channel 0 will not be affected and will remain active.
TERMINATING A B4 STATION
For stations on a Pamux bus to operate correctly,
both ends of the bus must be terminated.
The host
computer and the last Pamux station on the bus are the only devices that should be terminated. Note
that if you are using an Opto 22 Pamux adapter card, the host computer is automatically terminated,
since termination resistors are built into the card.
Содержание PAMUX
Страница 10: ...TABLE OF CONTENTS x Pamux User s Guide...
Страница 14: ...TABLE OF CONTENTS xiv Pamux User s Guide...
Страница 103: ...PROGRAMING WITH THE PAMUX DRIVER 3 42 Pamux User s Guide...
Страница 121: ...PROGRAMING WITHOUT THE PAMUX DRIVER 4 18 Pamux User s Guide...
Страница 125: ...TROUBLESHOOTING AND TIPS A 4 A 4 A 4 A 4 A 4 Pamux User s Guide...
Страница 135: ...SPECIFICATIONS B 10 Pamux User s Guide...
Страница 141: ...TEMPERATURE CONVERSIONS ROUTINES C 6 Pamux User s Guide...
Страница 143: ...PRODUCT SUPPORT D 2 Pamux User s Guide...
Страница 149: ...GLOSSARY E 6 Pamux User s Guide...