1

 

TECHNICAL SUMMARY 

 

1.1

 

PRODUCT DESCRIPTION 

 
The OSD159 is an add-on 8-channel alarm/contact interface that is either configured as a fiber or a 
copper transmission system. The system consists of a pair of OSD159s which are designed to provide 
duplex transmission of 8 contact closure channels. 
 
The OSD159 can be used as a standalone pair (fiber version) or as an add-on to an existing OSD 
system utilising one available RS232 data channel (copper version). 
 
The OSD159 is available in two physical configurations: card or module. The card versions are 
designed to fit the 3RU-high 19” OSD370 or OSD350 chassis, which allows multiple OSD card 
products to be conveniently powered from and located in the one chassis. The module versions are 
intended for isolated use and require an external power source.  
 
The OSD159 system can be used with any standard multimode optical fiber, and is available optionally 
for singlemode fiber use, over a single fiber for transmission and reception.  
 
 

 

1.1.1

 

APPLICATIONS

 

 

 

Security monitoring or access control 
systems 

 

 

Simple remote control systems 

 

Transmission of open/closed contacts 

 

 
 
1.1.2

 

FEATURES AND BENEFITS 

 
 

 

Enables up to 8 duplex alarm 
conditions to be transferred via one 
RS232/TTL data channel 

 

 

Both card or standalone module 
versions are available 

 

 

Available as either a fiber optic 
modem or as an RS232 based copper 
modem 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

 

RS232 version can work with any 
OSD fiber optic modem which has at 
least one spare data transmission 
channel 

 

Complete end-to-end isolation either 

as a fiber optic unit or as an RS232 
link working in conjunction with 
other OSD fiber modems 

Содержание OSD159

Страница 1: ...OPERATOR MANUAL OSD159 DUPLEX 8 CHANNEL ALARM CONTACT TRANSCEIVER...

Страница 2: ...OPTICAL SYSTEMS DESIGN DOC ID 10108502 OSD159 OPERATOR MANUAL PAGE 2 OSD159 DUPLEX 8 CHANNEL ALARM CONTACT TRANSCEIVER Document No 101085 Revision 02...

Страница 3: ...12 2 3 1 OSD159 INDICATORS 12 3 MAINTENANCE 13 3 1 INTRODUCTION 13 3 2 EXTERNAL INSPECTION 13 3 3 ROUTINE MAINTENANCE 13 4 WARRANTY 14 4 1 WARRANTY PERIOD 14 4 2 REPAIRS 14 4 2 1 WARRANTY REPAIRS 14 4...

Страница 4: ...y powered from and located in the one chassis The module versions are intended for isolated use and require an external power source The OSD159 system can be used with any standard multimode optical f...

Страница 5: ...ND OPTIONS There are various options available for the OSD159 as identified in Table 1 below OSD159 example only TABLE 1 PRODUCTS AND OPTIONS ITEM DESCRIPTION Card Version C Standalone Module Version...

Страница 6: ...ctor Optical Wavelength 850 40nm for OSD159FM 1310nm 40nm for OSD159FL Transmitter Optical Power 15dBm Receiver Sensitivity 40dBm for 1x10 9 BER Receiver Saturation 7dBm Optical Link Budget 25dB at 85...

Страница 7: ...ber Function 1 GND 14 Input 1 2 Input 2 15 Input 3 3 Input 4 16 Input 5 4 Input 6 17 Input 7 5 Input 8 18 Normally Open 1 6 Common 1 19 Normally Open 2 7 Common 2 20 Normally Open 3 8 Common 3 21 Norm...

Страница 8: ...e adequate measures OPTICAL OUTPUT OPERATION Class 1 Class 3A The multimode version of the OSD159 is a Class 1 LED product Wavelength of 850nm and 8dBm power output The singlemode versions of the OSD1...

Страница 9: ...mounted on an even surface and to be secured by means of M4 or smaller screws The OSD159 card version is designed to be inserted into a chassis and secured by means of captivated screws a Module Vers...

Страница 10: ...ernal DC power The voltage range of the OSD159 is 8 to 40VDC or 15 to 26VAC at 3VA maximum Power should be connected to the power socket located at the back of the case as indicated in Table 4 TABLE 4...

Страница 11: ...and lint free tissue to remove contamination Receive Alarm is an alarm signal that can be connected to control external sources eg LED indicator to indicate if there is a loss of received signal when...

Страница 12: ...tor illuminates accordingly on power up see Table 5 Plug in the optical connectors of the optical cable If the set up is connected correctly the OSD159 Link OK LED will change from Red to Green Plug t...

Страница 13: ...heir support circuitry Some components within the unit are Electrostatic ES sensitive and Electrostatic Discharge ESD precautions should be taken when performing maintenance upon the unit 3 2 EXTERNAL...

Страница 14: ...e for all repairs 4 2 1 WARRANTY REPAIRS Return shipments to OSD shall be at customer s expense and freight back to the customer will be at OSD expense 4 2 2 OUT OF WARRANTY REPAIRS OSD reserves the r...

Страница 15: ...uko Pl Warriewood 2102 P O Box 891 Mona Vale N S W Australia 2103 Telephone 61 2 9913 8540 Facsimile 61 2 9913 8735 Email sales osd com au Web Site www osd com au OPTIC L SYSTEMS DESIGN PTY LTD A B N...

Отзывы: