Range: 0-100, default: 20.
EMG_LFT_T
:
Emerge lift time.
This parameter defines the time of torch emerge lifting
once a torch tip collision detected.
Unit: 10ms (millisecond)
Range: 5-50, default: 20.
EMR_LFT_P
:
Emerge lift PWM value.
This parameter defines the speed of torch emerge lifting
once a torch tip collision detected.
Range: MIN_PWM-MAX_PWM, default: 100.
ADJ_RANG
:
Arc voltage intelligent adjustment range.
The AVC118 controller has an intelligent arc voltage
adjustment function.
Supposing the initial arc voltage is set too low, the
cutting torch will be also too close to the workpiece, and
the torch tip will be very easy to collide with the
workpiece, if a certain number of continue collisions
have been detected, the AVC118 controller will increase
the given arc voltage automatically to avoid subsequent
collision.
A similar situation will occur due to the wear out of the