FT-3100 TRANSMITTER PROGRAMMING GUIDE
ONICON Incorporated 727.447.6140
Page 25
onicon.com
This function establishes the frequency output level for output 1 or output 2
when the meter is in an alarm condition caused by an empty pipe, ADC error or
an open coil indication.
This function is only available when either output pulse 1or output pulse 2 in
OUTPUTS menu (menu 7) [Out1 = XXXXX] [Out2 = XXXXX] is set to Freq+, Freq-
or Freq±.
The alarm value is set as a percentage of the full scale frequency. The valid range
is 0 – 125%. The default setting is 0%. One or more alarm icons will also be
displayed in the upper left hand side of the display when this alarm is active.
The default setting will cause the frequency output to indicate 0 Hz when in the
alarm state.
To enter a new value, press enter to access the function. Use the right arrow key
to move the cursor and the up arrow key to change the value. Press enter to
accept changes and exit the function. Press escape to exit the program mode.
Frequency Output Value When
in Alarm State
[Hz v.alarm = % XXX]