FT-3100 TRANSMITTER PROGRAMMING GUIDE
ONICON Incorporated 727.447.6140
Page 9
onicon.com
The menu can be accessed by briefly pressing the
ESC
ENTER
key and entering the
access code 4*******.
SECTION 3.0: MAIN MENU
3.1 MENU 1 - SENSOR
1. From Quick Start menu, push
repeatedly
until Main Menu is highlighted.
2. Enter into the main menu.
Sensor Body Model
[S Model = XXX]
Liner Material
[Lining = XXXXXX]
Unit Type
[U type = XXXXXX]
Diameter
[Diam. = in XXX]
KA
[KA = ± XX.XXX]
KZ
[KZ = ± XXXX]
Empty Pipe Detector
[E.P.Detect = ON]
Empty Pipe Threshold
[R max = kohm XXXX]
Elecrode Cleaning
[El. Cleaning = MIN]
Sensor Cable Length
[S.Cable = ft XXX]
Alarm Delay Interval
[S.err.delay = XXX]
Enter the numeric code for the type of sensor body connected to the transmitter.
Body Type
Sensor Code
Threaded Steel
011
Threaded Polypropylene
013
Wafer
002
Flanged
004
To change the setting, press enter to access the function. Use the right arrow key
to move the cursor and the up arrow key to change the code as per the table
above. Press enter to accept the change and exit the function. Press escape to
Sensor Body Model
[S.Model = XXX]
QUICK START
E. P. Detect=
R max=kohm
Pls2=Gal
Tpls2=ms
A1S=Gal/m
ON
0220
1000.0
0500.0
004500
Main Menu
MAIN MENU
1-Sensor
2-Units
3-Scales
4-Measure
5-Alarms
6-Inputs