Performance Specs
Flow Accuracy:
Natural Gas and Propane: 1% R 500 - 7000 SFPM
Natural Gas and Propane: 2% R 100 - 500 SFPM
Air: ±1% of reading ±0.5% of full scale
Accuracy specification applies to customer's selected flow range
Maximum range: 15 to 35,000 SFPM (0.07 to 71 NMPS)
Minimum range: 15 to 1,000 SFPM (0.07 to 4.7 NMPS)
Flow Response Time: 1 second (one time constant)
Temperature Accuracy: ±1° F (±0.6° C)
Calibration:
Factory Calibration to NIST traceable standards
Zero CAL-CHECK®: In situ, operator-initiated calibration validation
Operating Specs
Units of Measurement (field selectable):
SCFM, SCFH, NM3/H, NM3/M, KG/H, KG/M, KG/S, LB/H, LB/M, LB/S, NLPH,
NLPM, MMSCFD, LB/D, SLPM, NLPS, MSCFD, SM3/H, MT/H, NM3/D, MMSCFM,
SCFD, MCFD, SM3/M, SM3/D
Flow Velocity Range:
15 to 35,000 SFPM (0.07 to 71 NMPS)
Turndown: up to 1000:1; 100:1 typical
Flow Ranges
Pipe Diameter
SCFM
NM3/hr
1.5" (40mm)
0-210
0-330
2" (50mm)
0-350
0-550
3" (80mm)
0-770
0-1,210
4" (100mm)
0-1,330
0-2,100
6" (150mm)
0-3,000
0-4,730
8" (200mm)
0-5,210
0-8,220
12" (300mm)
0-11,700
0-18,450
NOTE: To determine if the F-5500 will operate accurately in other pipe sizes,
divide the maximum flow rate by the pipe area. The application is acceptable if the
resulting velocity is within the velocity range above.