![Onicon F-5500 Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/onicon/f-5500/f-5500_installation-and-operation-manual_1636043053.webp)
i
This is the lower flow limit alarm value that can be associated with the alarm output.
An alarm code is generated when the flow value is below this limit. If no checking is
needed, this value should be set to zero.
Press
OK (F4)
to accept the value.
To set the parameters for a
High Temperature Alarm
:
F1 F2 F3 F4
This is the upper temperature limit alarm value that can be associated with the alarm
output. An alarm code is generated when the temperature value exceeds this limit. If
no checking is needed, this value should be set to zero.
Press
OK (F4)
to accept the value.
To set the parameters for a
Low Temperature Alarm
:
F1 F2 F3 F4
This is the lower temperature limit alarm value that can be associated with the alarm
output. An alarm code is generated when the temperature value is below this limit. If
no checking is needed, this value should be set to zero.
Press
OK (F4)
to accept the value.
NOTE: If the programming menu was entered with a
Level 2
password, then more
menus will be shown concerning factory-set parameters that should not be changed.
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
F-5500 Thermal Mass Flow Meter Manual 06/17 - 2030 / 107023
Page 53
Model F-5500
OPERA
TION
Operation: Programming
Programming
by Display
High Temp Alarm
HiTmpAlm = 200 F
CHG OK
Low Temp Alarm
LoTmpAlm = 20 F
CHG OK