X. V - Systems Electrical Data
I
O
Customer supplied
receptacle fed from
2 pole dedicated
circuit breaker.
6 - 20R
6 - 20P
Magnetic Starter -
Mount close to
collector
6’ long type SJT 14 AWG
power cord
Motor
Note: This dust collector is pre-
wired at the factory and need only
be plugged into a dedicated NEMA
6-20R electrical receptacle. 2 & 3hp
single phase V-Systems only.
Always Use A Licensed, Professional Electrician.
What size circuit breaker for the V-2000?
The circuit breaker OAS recommends is a 2 pole ‘HACR’ style (or equivalent) 15 amp rated for
250 volts AC.
What size circuit breaker for the V-3000?
The circuit breaker OAS recommends is a 2 pole ‘HACR’ style (or equivalent) 20 amp rated for
250 volts AC.
“HACR’ style breakers are required because they are designed to accommodate high amperage
inrush (prevents nuisance tripping of the circuit breaker when the dust collector motor starts).
Make sure that the conductor(s) used to ‘feed’ the NEMA 6-20R dedicated receptacle are sized
per NEC (NEC = National Electircal Code) Article 310 entitled ‘Conductors for General Wiring’.
Always use a licensed professional electrician to install the electrical circuit between the circuit
breaker panel, and the NEMA 6-20R dedicated receptacle that is used to power up the factory
installed magnetic starter that comes on the V-2000 or the V-3000.
11
V - Systems Owner’s Manual O.A.S. 2008