Through-beam Sensor Heads: FUN Mode Functions
Section 3-8
92
Sample Hold
In Sample Hold Mode, the measured result when the timing input is turned
ON will be the output value.
Hold Mode starts when the power is turned ON, immediately after chang-
ing to RUN or T Mode, or immediately after the reset input is turned OFF.
The output is held at the maximum output (current: approximately 23 mA,
voltage: approximately 5.5 V) until the first time the timing input turns ON.
The first measured result (A in the figure below) is output from the begin-
ning of the first sampling period to the second sampling period. After the
beginning of the second sampling period, the second measured result (B
in the figure below) is output and the sequence is repeated.
Example: Sample Hold
Display value = Output value
Measured value
Current (mA)
23
A
B
Time
Time
Timing input
Timing input
Hold Mode
Start
4
The output is clamped on
the maximum value until
the first time the timing
input turns ON.
Outputs A from the first time
the timing input turns ON.
Outputs B from the second
time the timing input turns ON.
Z157-E1-01C.book Page 92 Thursday, August 31, 2006 5:13 PM
Содержание ZX-CAL
Страница 1: ...Smart Sensors ZX Series Operation Manual Cat No Z157 E1 02 OMRON Corporation ...
Страница 20: ...xvi Z157 E1 01C book Page xvi Thursday August 31 2006 5 13 PM ...
Страница 48: ...Outline of Functions Section 2 5 28 Memo Z157 E1 01C book Page 28 Thursday August 31 2006 5 13 PM ...
Страница 160: ...FUN Function Mode Section 4 5 140 Memo Z157 E1 01C book Page 140 Thursday August 31 2006 5 13 PM ...
Страница 166: ...Setting Problems Section 5 2 146 Memo Z157 E1 01C book Page 146 Thursday August 31 2006 5 13 PM ...