Two-circuit Limit Switch
WL
F-71
Lim
it
Switch
es
Sensor I/O Connector Models
Note: 1.
The above figures are for standard currents.
2.
Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
3.
Lamp load has an inrush current of 10 times the steady-state current.
4.
Motor load has an inrush current of 6 times the steady-state current.
Spatter-prevention Models
Note: 1.
The above figures are for standard currents.
2.
Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
3.
Lamp load has an inrush current of 10 times the steady-state current.
4.
Motor load has an inrush current of 6 times the steady-state current.
Type
Rated
voltage
Non-inductive load
Inductive load
Resistive load
Lamp load
Inductive load
Motor load
NC
NO
NC
NO
NC
NO
NC
NO
For DC
12 VDC
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
24 VDC
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
48 VDC
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
115 VDC
0.8 A
0.8 A
0.2 A
0.2 A
0.8 A
0.8 A
0.2 A
0.2 A
For AC
115 VAC
1 A
1 A
1 A
1 A
1 A
1 A
1 A
1 A
Model
Rated
current
Non-inductive load
Inductive load
Resistive load
Lamp load
Inductive load
Motor load
NC
NO
NC
NO
NC
NO
NC
NO
WL
@
-LES
125 VAC
10 A
3 A
1.5 A
10 A
5 A
2.5 A
250 VAC
10 A
2 A
1 A
10 A
3 A
1.5 A
125 VDC
0.8 A
0.2 A
0.2 A
0.8 A
0.2 A
0.2 A
250 VDC
0.4 A
0.1 A
0.1 A
0.4 A
0.1 A
0.1 A
WL
@
-LDS
115 VAC
10 A
3 A
1.5 A
10 A
5 A
2.5 A
12 VDC
10 A
6 A
3 A
10 A
6 A
24 VDC
6 A
4 A
3 A
6 A
4 A
48 VDC
3 A
2 A
1.5 A
3 A
2 A
Inrush current
NC
30 A max.
NO
20 A max.
Operating temperature
–10
°
C to 80
°
C (with no icing)
Operating humidity
95% max.