21
Wiring
Section 3-2
Wiring a Screwless Clamp Terminal Block (CJ1W-AD04U-SL)
Terminal Block Arrangement
• Strip about 10 mm of the insulation from the end of the wire and insert the
bare wire or attach a pin terminal.
• If bare stranded wire is used without a pin terminal, be sure that there are
no loose wire strands that may contact another circuit.
Connecting the Wires
1,2,3...
1.
Use stranded or solid wire. Pin terminals can also be used.
Insert a precision screwdriver in the release button hole.
2.
When the screwdriver is pushed firmly to the bottom, the lock will be re-
leased and it will be possible to insert the wire into the wire hole.
3.
Insert the wire fully into the wire hole (but without any of the wire insulation
in the wire hole) and pull out the screwdriver to lock the wire in place.
B
Terminal block lock lever
B1
A1
B9
A9
Release button hole
N.C.
B1
N.C.
B2
N.C.
B3
Input 2 V+
B4
Input 2
−
B5
Input 2 I+
B6
Input 4 V+
B7
Input 4
−
B8
Input 4 I+
B9
A1
N.C.
A2
N.C.
A3
N.C.
A4
Input 1 V+
A5
Input 1
−
A6
Input 1 I+
A7
Input 3 V+
A8
Input 3
−
A9
Input 3 I+
A
Wire hole
1.
2.
3.
Wire gauge: 0.15 to 1.5 mm
2
(26 to 16 AWG)
10
+1
−
0
Pin terminal
Содержание SYSMAC CJ1W-AD04U
Страница 1: ...Universal Input Units Cat No W466 E1 02 SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL OPERATION MANUAL...
Страница 2: ...SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL Universal Input Units Operation Manual Revised December 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 61: ...42 Expansion Setting Area Section 4 3...
Страница 69: ...50 Dimensions Appendix A...