28
Exchanging Data with the CPU Unit
Section 4-1
Data Allocation in the User Settings Area
DM Area
The Unit’s various user settings are made in the Special I/O Unit words in the
DM Area. Settings such as the alarm settings and span/zero adjustment val-
ues can be changed while the CPU Unit is operating.
Note
The unit number switch setting on the front panel of the Unit determines which
words in the Special I/O Unit Area and DM Area words are allocated to each
Universal Input Unit.
DM Allocation Contents
The following table shows the allocation of DM words and bits.
Refer to
4-2 Detailed Description of User Settings Area Data
for details.
Allocated DM Area words
D20000 to D20099
D20100 to D20199
D20200 to D20299
D20300 to D20399
D20400 to D20499
D20500 to D20599
D20600 to D20699
D20700 to D20799
D20800 to D20899
D20900 to D20999
D21000 to D21099
N
×
100 to
N
×
100 + 99
D29500 to D29599
Special I/O Unit words
in DM Area
CJ-series CPU Unit
CJ1W-AD04U/AD04U-SL
Universal Input Unit
User Settings data
D (m)
Unit values read command
D (m + 1)
Address of data range error
D (m + 2, 6, 10, 14)
Process value H (high limit) alarm setting
D (m + 3, 7, 11, 15)
Process value L (low limit) alarm setting
D (m + 4, 8, 12, 16)
Span adjustment value
D (m + 5, 9, 13, 17)
Zero adjustment value
D (m + 18)
Data direction at sensor error
Temperature unit setting
D (m + 19, 24, 29, 34)
Input type
D (m + 20, 25, 30, 35)
Alarm hysteresis
D (m + 21, 26, 31, 36)
Alarm ON-delay time
D (m + 22, 27, 32, 37)
Process value scaling (upper limit)
D (m + 23, 28, 33, 38)
Process value scaling (lower limit)
D (m + 39)
Expansion Setting Area Enable
D (m + 40)
Expansion Setting Area address
Unit #0
Unit #1
Unit #2
Unit #3
Unit #4
Unit #5
Unit #6
Unit #7
Unit #8
Unit #9
Unit #10
to
Unit #n
Unit #95
(m = 20000 + N
×
100)
Power ON
Unit Restart Bit ON
Power ON
Unit Restart Bit ON
I/O refresh
N: Unit No.
Power ON
Unit Restart Bit ON
to
to
to
DM word
(See note 1.)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
m
Unit default values read command
m + 1
Address of data range error
m + 2
Input 1 Process value H (high limit) alarm setting
m + 3
Input 1 Process value L (low limit) alarm setting
m + 4
Input 1 Span adjustment value
m + 5
Input 1 Zero adjustment value
m + 6
Input 2 Process value H (high limit) alarm setting
m + 7
Input 2 Process value L (low limit) alarm setting
m + 8
Input 2 Span adjustment value
m + 9
Input 2 Zero adjustment value
Содержание SYSMAC CJ1W-AD04U
Страница 1: ...Universal Input Units Cat No W466 E1 02 SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL OPERATION MANUAL...