The following supplements the explanation given in
1-1 Features and Functions
.
Changing Set Values during Output of Process Value Alarm
H (High Limit) Alarms
When the alarm set value is raised while the alarm output is ON, the alarm output will be turned OFF when the
following condition is satisfied.
Input value < (alarm set value after change
−
hysteresis)
The alarm output will first turn OFF when the input value falls below the set value (with the hysteresis included).
L (Low Limit) Alarms
When the alarm set value is lowered while the alarm output is ON, the alarm output will be turned OFF when
the following condition is satisfied.
Input value > (alarm set value after hysteresis)
When the hysteresis part alone of the input value is greater than the set value, the alarm output will turn OFF
for the first time.
Example: H Limit Alarms
ON
OFF
Hysteresis
ON
OFF
Hysteresis
ON
OFF
Hysteresis
Input value (Process value,
rate-of-change value,
instantaneous value)
H alarm set value
With present value at this point, alarm output turns ON.
Alarm set value further raised.
Alarm set value further raised.
H alarm set value
H alarm set value
Input value (Process value,
rate-of-change value,
instantaneous value)
Input value (Process value,
rate-of-change value,
instantaneous value)
With present value at this point, alarm output remains ON.
With present value at this point, alarm output turns OFF.
Содержание SYSMAC CJ1W-AD04U
Страница 1: ...Universal Input Units Cat No W466 E1 02 SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL OPERATION MANUAL...
Страница 2: ...SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL Universal Input Units Operation Manual Revised December 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 61: ...42 Expansion Setting Area Section 4 3...
Страница 69: ...50 Dimensions Appendix A...