11
Specifications
Section 2-1
• Data Exchange with the CPU Unit (For details, refer to
SECTION 4 In-
put Functions and Operating Procedures
.)
Input Specifications
Special I/O Unit Area in CIO
Area (CIO 2000 to CIO 2959,
CIO 2000.00 to CIO 2959.15)
Regularly exchanges 10 words per Unit.
(CPU Unit
↔
Universal Input Unit)
Special I/O Unit words in DM
Area (D20000 to D29599)
Transfers 100 words of data per Unit. The
following data is transferred at the indi-
cated time.
• Initial settings data: Transferred when
power is turned ON or the Unit is
restarted.
• Continuously refreshed data (e.g., alarm
settings): Transferred during I/O refresh
period.
• Expansion Setting Area: Transferred
during the I/O refresh period.
(CPU Unit
↔
Universal Input Unit)
Items
Specifications
Number of analog inputs
4
Input type
(See note 1.)
• Platinum resistance thermometer:
Pt100 (JIS, IEC), PT1000, or JPt100
• Thermocouple: K, J, T, L, R, S, or B
• Current: 4 to 20 mA, or 0 to 20 mA
• Voltage: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Each input can be set independently.
Maximum rated input
(See note 2.)
Voltage Input: ±15 V
Current Input: ±30 mA
Input impedance
Temperature: 10 k
Ω
min.
Voltage Input: 1 M
Ω
min.
Current Input: 250
Ω
(rated value)
Resolution
12,000 (for voltage or current input)
Converted output data
16-bit binary data
Accuracy (25
°
C)
(These values do not
include the sensor error.)
Typical thermocouple inputs:
(
±
0.3% of PV or
±
1.5
°
C, whichever is greater)
±
1 digit
max.
Special cases:
• The accuracy of L is
±
2
°
C
±
1 digit max.
• The accuracy of K and T at
−
100
°
C or less is
±
2
°
C
±
1
digit max.
• The accuracy of R and S at 200
°
C or less is
±
3
°
CV1
digit max.
• The accuracy of B at 400
°
C or less is not specified.
Platinum resistance thermometers:
(
±
0.3% of PV or
±
0.8
°
C, whichever is greater)
±
1 digit
max.
Voltage inputs and current inputs:
(
±
0.3% FS)
±
1 digit max.
Temperature coefficient
+/
−
100 ppm FS/
°
C max.
Warm-up time
30 min
A/D conversion time
(See note 3.)
250 ms/4 inputs
Содержание SYSMAC CJ1W-AD04U
Страница 1: ...Universal Input Units Cat No W466 E1 02 SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL OPERATION MANUAL...
Страница 2: ...SYSMAC CJ Series CJ1W AD04U CJ1W AD04U SL Universal Input Units Operation Manual Revised December 2007...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 9: ...x...
Страница 13: ...xiv...
Страница 61: ...42 Expansion Setting Area Section 4 3...
Страница 69: ...50 Dimensions Appendix A...