10
The switch is factory-set to OFF: Parameters can be set from the Data Setting
Console only.
The new setting is valid immediately after the switch setting is changed.
Removing and Attaching the Cover
Removing the Cover
Attaching the Cover
Insert a small flat-blade screw-
driver between the case and
the cover at the top of the Unit
and lever off the cover.
Place the right edge of the
cover against the case and
press into position.
Switching Memory Contents
The contents of the allocated memory differ according to the Unit number set-
ting.
Normal
Data can be set as required using commands (Refer to
4-1 Memory Allocation).
Fixed
Fixed data is allocated to memory. Direct reading and
writing of data is possible.
Refer to
4-1 Memory Allocation for details of the memory contents.
Setting Direction
Selects whether the data settings are made from the Data Setting Console or
from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The reading and setting of the executed bank number are possible from a user
program or from a device, such as the Programming Console, regardless of the
ON/OFF setting of switch SW2-2.
Sensor Type
SW202
Sensor type setting
C200H-TC00
j
8
9
0
1
2
4
3
5
6
7
Setting
0
1
2
3
4
5
6
7
8
9
Sensor type
R
S
K
J
T
E
B
N
L
U
The switch is factory-set to 2.
The selected position is shown by the arrow. Turn the switch with a small flat-
blade screwdriver.
Selected position
Switch Settings
Section 2-2
electronic components distributor