11
C200H-TC10
j
ON
OFF
Setting
Sensor type
OFF
JPt
ON
Pt
The switch is factory-set to OFF.
See
Appendix B Sensor T
emperature Measurement Range for the measurable
temperature range.
Operation and Function Setting
SW203
Operation and Function Setting
13
4
5
6
2
OFF
ON
NO
Pin
Function
OFF
ON
6
Not used
---
---
5
Operation in C200H
program mode
Continue control
Interrupt control
4
Loop 2
Enabled
Disabled (not used)
3
Display units
°
C
°
F
2
Control action
Reverse (heating
control)
Normal (cooling
control)
1
Control method
Feed-forward PID
ON/OFF control
The switch is factory-set to OFF.
Selects if the temperature control is continued or interrupted when the CPU Unit
is set to PROGRAM mode.
Note Units with a lot number of 01Z40 or later are provided with Stop Bits for loops 1
and 2 in bits 06 and 04 of word (n+2). For further information, refer to page 5.
Loop 2
Selects if input Loop 2 is used or not.
Note
1. Always set this switch to the ON (disabled) position when input Loop 2 is not
used. A sensor error occurs if this switch is set to the OFF (enabled) position
when no temperature sensor is connected to Loop 2.
2. Use input Loop 1 when only one loop is used.
It is not possible to use Loop 2 if Loop 1 is not used.
Display Units
Selects whether setting and SVs displayed on the Data Setting Console are in
Celsius or Fahrenheit.
Operation in CPU Unit
Program Mode
Switch Settings
Section 2-2