65
Initial I/O Table Registration
Register I/O table
Memory cleared completely
00000
00000
FUN (??)
00000I/OTBL?
?Ć?U=
00000I/OTBL WRIT
????
00000I/OTBL WRIT
9713
00000I/OTBL WRIT
OK
When Remote I/O Master Units in the system are connected to I/O Link
Units, Optical I/O Units, Remote Terminals, or I/O Terminals a word multiplier
between 0 and 3 must be assigned to each one of the Masters after register-
ing the I/O table. The same word multiplier can be assigned to more than one
Master in the same system as long as the same word is not allocated to
more than one unit. Word allocations to I/O Link Units, Optical I/O Units, and
Remote terminals, and I/O Terminals are computed from the words set on the
Units as follows:
(32 x word multiplier) + word setting on the Unit
Make sure that the lowest words allocated to I/O Link Units, Optical I/O Units,
Remote Terminals, or I/O Terminals connected to the Master with the lowest
Registering Word
Multipliers for Masters
Preparation for Operation
Section 4-5