208
00000
LD
00001
00001
SNXT(09)
LR
0000
00002
SNXT(09)
LR
0002
00003
STEP(08)
LR
0000
Process A
00100
LD
00002
00101
SNXT(09)
LR
0001
00102
STEP(08)
LR
0001
Process B
00100
LD
01101
00101
OUT
LR
0003
00101
AND
00004
00101
SNXT(09)
LR
0004
00102
STEP(08)
LR
0002
Process C
00200
LD
00003
00201
SNXT(09)
LR
0003
00202
STEP(08)
LR
0003
Process D
00300
STEP(08)
LR
0004
Process E
00400
LD
00005
00401
SNXT(09)
LR
0005
00402
STEP(08)
---
Address
Instruction
Operands
Address
Instruction
Operands
5-23
Special Instructions
The instructions in this section are used for various operations, including pro-
gramming user error codes and messages, counting ON bits, setting the
watchdog timer, and refreshing I/O during program execution.
5-23-1
FAILURE ALARM – FAL(06) and
SEVERE FAILURE ALARM – FALS(07)
N
: FAL number
# (00 to 99)
Ladder Symbols
Definer Data Areas
@FAL(06) N
FAL(06) N
N
: FAL number
# (01 to 99)
FALS(07) N
FAL(06) and FALS(07) are provided so that the programmer can output error
numbers for use in operation, maintenance, and debugging. When executed
with an ON execution condition, either of these instruction will output a FAL
number to bits 00 to 07 of SR 253. The FAL number that is output can be
between 01 and 99 and is input as the definer for FAL(06) or FALS(07).
FAL(06) with a definer of 00 is used to reset this area (see below).
25307
25300
X10
1
X10
0
FAL Area
Description
Special Instructions
Section 5-23
Содержание SYSMAC C1000H
Страница 1: ...Cat No W140 E1 04 Programmable Controllers SYSMAC C1000H C2000H...
Страница 2: ...C1000H C2000H Programmable Controllers Operation Manual Revised May 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 395: ...Cat No W140 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 396: ...Cat No W140 E1 04 SYSMAC C1000H C2000H Programmable Controllers OPERATION MANUAL...