314
IR
SR
HR
TR
AR
LR
TC
DM
#
00000 to 23615
23700 to 25515
HR 0000 to 9915
TR 0 to 7
AR 0000 to 2715
LR 0000 to 6315
TC 000 to 511
C1000H: DM 0000 to DM 4095
C2000H: DM 0000 to DM 6655
0000 to 9999
or 0000 to FFFF
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
Data Areas
Name Mnemonic
Page
Operand Data
Areas
Function
Symbol
STEP START
SNXT(09)
SNXT(09) B
Used with a control bit (B) to indicate the
end of the step, reset the step, and start
the next step which has been defined
with the same control bit.
B:
IR
HR
AR
LR
199
SHIFT REGISTER
SFT(10)
I
P
R
SFT(10)
St
E
Creates a bit shift register for data from the
starting word (St) through to the ending
word (E). I: input bit; P: shift pulse; R: reset
input. St must be less than or equal to E.
St and E must be in the same data area.
E
St
15
15
00
IN
00
St/E:
IR
HR
AR
LR
127
KEEP
KEEP(11)
S
KEEP(11)
B
R
Defines a bit (B) as a latch, controlled by
the set (S) and reset (R) inputs.
B:
IR
HR
AR
LR
112
REVERSIBLE
COUNTER
CNTR (12)
II
DI
R
N
SV
CNTR(12)
Increases or decreases the PV by one
whenever the increment input (II) or
decrement input (DI) signals,
respectively, go from OFF to ON. SV: 0 to
9999; R: reset input. Each TC bit can be
used for one timer/counter only. The TC
bit is entered as a constant.
N:
TC
SV:
IR
SR HR
AR
LR
DM
#
125
DIFFERENTIATE UP
DIFU(13)
DIFFERENTIATE
DOWN
DIFD(14)
DIFU(13)
DIFD(14)
B
B
DIFU(13) turns ON the designated bit (B)
for one cycle on reception of the leading
(rising) edge of the input signal; DIFD(14)
turns ON the bit for one cycle on
reception of the trailing (falling) edge.
B:
IR
HR
AR
LR
110
HIGH-SPEED TIMER
TIMH(15)
TIMH(15) N
SV
A high-speed, ON-delay (decrementing)
timer. SV: 00.02 to 99.99 s. Each TC bit
can be assigned to only one timer or
counter. The TC bit is entered as a
constant.
N:
TC
SV
:
IR
SR
HR
AR
LR
HR
#
121
WORD SHIFT
(@)WSFT(16)
WSFT(16)
E
St
The data in the words from the starting
word (St) through to the ending word (E),
is shifted left in word units, writing all
zeros into the starting word. St must be
less than or equal to E, and St and E
must be in the same data area.
St/E:
IR
HR
AR
LR
DM
134
COMPARE
(@)CMP(20)
CMP(20)
Cp1
Cp2
Compares the data in two 4-digit
hexadecimal words (Cp1 and Cp2) and
outputs result to the GR, EQ, or LE
Flags.
Cp1/Cp2:
IR
SR
HR
AR
LR
TC
DM
#
142
Special Instructions
Appendix B
Содержание SYSMAC C1000H
Страница 1: ...Cat No W140 E1 04 Programmable Controllers SYSMAC C1000H C2000H...
Страница 2: ...C1000H C2000H Programmable Controllers Operation Manual Revised May 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 395: ...Cat No W140 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 396: ...Cat No W140 E1 04 SYSMAC C1000H C2000H Programmable Controllers OPERATION MANUAL...