151
value is then turned ON in a result word. If more than one digit is specified,
then one bit will be turned ON in each of consecutive words beginning with R.
(See examples, below.)
The following is an example of a one-digit decode operation from digit num-
ber 1 of S, i.e., here Di would be 0001.
Source word
First result word
C
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
Bit C (i.e., bit number 12) turned ON.
The first digit and the number of digits to be converted are designated in Di. If
more digits are designated than remain in S (counting from the designated
first digit), the remaining digits will be taken starting back at the beginning of
S. The final word required to store the converted result (R plus the number of
digits to be converted) must be in the same data area as R, e.g., if two digits
are converted, the last word address in a data area cannot be designated; if
three digits are converted, the last two words in a data area cannot be desig-
nated.
The digits of Di are set as shown below.
Specifies the first digit to be converted (0 to 3)
Number of digits to be converted (0 to 3)
0: 1 digit
1: 2 digits
2: 3 digits
3: 4 digits
Not used
Digit number:
3 2 1 0
Some example Di values and the digit-to-word conversions that they produce
are shown below.
0
1
2
3
R
R + 1
R
R + 1
R + 2
0
1
2
3
0
1
2
3
0
1
2
3
R
R + 1
R + 2
R + 3
R
R + 1
R + 2
R + 3
S
Di: 0031
Di: 0023
Di: 0030
Di: 0010
S
S
S
ER:
Undefined digit designator, or R plus number of digits exceeds a data
area.
Indirectly addressed DM word is non-existent. (Content of
*
DM word
is not BCD, or the DM area boundary has been exceeded.)
Digit Designator
Flags
Data Conversion
Section 5-16
Содержание SYSMAC C1000H
Страница 1: ...Cat No W140 E1 04 Programmable Controllers SYSMAC C1000H C2000H...
Страница 2: ...C1000H C2000H Programmable Controllers Operation Manual Revised May 2003...
Страница 3: ...iv...
Страница 5: ...vi...
Страница 395: ...Cat No W140 E1 04 Note Specifications subject to change without notice Printed in Japan Authorized Distributor...
Страница 396: ...Cat No W140 E1 04 SYSMAC C1000H C2000H Programmable Controllers OPERATION MANUAL...