2-26
H
Conformance to EMC Directives
In order to conform to EMC Directives, the exclusive-use methods are required for noise filter applica-
tion, cable shielding, and Inverter installation. The following provides an outline of the methods.
The noise filter and the Inverter must be mounted on the same metal plate. The filter should be mounted
as close to the Inverter as practical. Keep the cable as short as possible (40 cm max.). The metal plate
should be securely grounded. The ground of the noise filter and Inverter must be bonded to the metal
plate using as large an area as possible (after peeling off the paint on the Inverter and the metal plate).
For the mains input cable, screened cable is recommended at least within the control panel. The screen
of the cable should be connected to a solid ground. For the motor cable, screened cable (20 m max.)
must be used and the screen of the motor cable is connected to the ground at both ends by a short
connection, using as large an area as possible.
Ground to the supply neutral, which will increase the effect of the noise filter.
The following table and figures provide the noise filter list for the EMC Directives and the installation and
wiring of the Inverter and noise filter.
Noise Filter List for EMC Directives
Inverter model
Noise filter (manufactured by Schaffner)
3G3FV/3G3HV
Model
Rated current (A)
Weight (kg)
Dimensions
(W
×
D
×
H) (mm)
A4004-CE
3G3FV-PFS4874-7-07
7
1.1
50
×
126
×
255
A4007-CE
A4015-CE
A4022-CE
3G3FV-PFS4874-18-07
18
1.7
55
×
142
×
305
A4037-CE
A4055-CE
3G3FV-PFS4874-30-07
30
2.0
60
×
150
×
335
A4075-CE
A4110-CE
3G3FV-PFS4874-42-07
42
3.0
70
×
185
×
329
A4150-CE
B4185-CE
3G3FV-PFS4874-55-07
55
3.3
80
×
185
×
329
B4220-CE
3G3FV-PFS4874-75-34
75
4.3
80
×
220
×
329
B4300-CE
B4370-CE
3G3FV-PFS4874-100-35
100
5.7
90
×
220
×
379
B4450-CE
3G3FV-PFS4874-130-35
130
8.0
110
×
240
×
439
B4550-CE
3G3FV-PFS4874-180-07
180
11
110
×
240
×
438
B4750-CE
3G3FV-PFS4874-300-99
300
15
300
×
564
×
160
B411K-CE
3G3FV-PFS4874-400-99
400
22
300
×
564
×
160
B416K-CE
AB004-CE
3G3HV-PFS4971-10-07
10
0.7
57.5
×
156
×
45.4
AB007-CE
3G3HV-PFS4971-20-07
20
1.0
85.5
×
119
×
57.6
AB015-CE
AB022-CE
3G3HV-PFS4971-40-07
40
3.0
90
×
246
×
65
AB037-CE
Installation
Chapter 2
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]