2-13
2-2-2 Terminals
H
3G3FV Series
D
Terminal Block Configuration (400-V Class with 3.7-kW Output, CE Models)
Control
circuit
terminals
Main circuit
terminals
D
Main Circuit Terminals
Voltage class
400-V class
Model 3G3FV-
A4004 to A4150
B4185 to B4450
B4550 to B416K
Maximum
applied motor
capacity
0.4 to 15 kW
18.5 to 45 kW
55 to 160 kW
L1 (R)
Power supply input terminals, 3-phase, 380 to 460 VAC, 50/60 Hz
L2 (S)
L3 (T)
T1 (U)
Motor output terminals, 3-phase, 380 to 460 VAC (correspond to input voltage)
T2 (V)
T3 (W)
B1
Braking Resistor Unit
---
B2
connection terminals
1
+
DC reactor connection
DC power supply input
---
2
+
terminal ( 1- 2)
+
+
terminal ( 1- )
+
–
–
DC power supply input
terminal ( 1- )
+
–
Braking Unit connection
terminal ( 3- )
+
–
Braking Unit connection
3
+
---
terminal ( 3- )
(see note 3)
+
–
s (l
2
)
---
Cooling fan power supply
---
r (l
1
)
input terminal
See notes 1, 2
s200 (l
2
200)
---
s400 (l
2
400)
Ground the terminal at a resistance of less than 10
Ω
.
Installation
Chapter 2