2-35
Induction Noise: Electromagnetic induction generates noise on the signal line, causing the controller
to malfunction.
Radio Noise:
Electromagnetic waves from the Inverter and cables cause the broadcasting radio
receiver to make noise.
D
Cable Length between Inverter and Motor
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase,
causing the Inverter output current to increase as well. This may affect peripheral devices. To prevent
this, adjust the carrier frequency (set in C06-01 to C06-03 or n050) as shown in the table below. (For
details, refer to the parameter settings.)
Model
Cable length
20 m max.
40 m max.
More than 40 m
Carrier frequency
15 kHz max.
10 kHz max.
5 kHz max.
3G3FV
(Set value: C06-01)
(15.0)
(10.0)
(5.0)
(Set value: C06-02)
(15.0)
(10.0)
(5.0)
(Set value: C06-02)
(0)
(0)
(0)
3G3HV
(Set value: n050)
(6)
(4)
(2)