25
F3SJ-B
User’s Manual
Ch
apt
e
r
3
Series
Con
n
ect
ion
Wiring/Installation
E
Connection Procedure
1.
Remove the caps from the primary sensor. Loosen the screw (M3 cross-shaped) to remove the cap.
2.
Use the F39-JBR2W series connection cable for extension to connect them.
3.
When changing the connection distance between the F3SJ-Bs, connect a F39-JD
B double-ended
connector cable (sold separately).
- When attaching a cable or cap, securely fasten the screws (M3 cross-shaped (2 for each), recommended torque:
0.54 N•m).
Failure to do so may cause the cable/cap to come loose, leading to deterioration of the protective functions.
- Attaching/detaching of a cap or a series-connection cable may cause misalignment of rubber grommet in a
connector assembly.
Press the grommet to the bottom of the connector and attach the connector F3SJ-B again.
1.
1.
1.
1.
2.
2.
2.
2.
3.
3.
3.
3.
Cap
Cap
F39-JBR2W
F39-JD
□
B
F39-JBR2W
F39-JD
□
B
Receiver’s
power supply
cable end
Emitter’s
power supply
cable end
Emitter’s
power supply
cable end
Receiver’s
power supply
cable end
<Secondary sensor>
<Primary sensor>
Содержание Sti F3SJ-B P25-01TS Series
Страница 1: ...F3SJ B P25 01TS Series Safety Light Curtain User s Manual Cat No SCHG 734C ...
Страница 12: ...x Introduction F3SJ B User s Manual ...
Страница 82: ...68 Chapter 3 Wiring F3SJ B User s Manual Wiring Installation ...
Страница 92: ...78 Chapter 4 Wiring Examples F3SJ B User s Manual Input Output Circuit and Applications ...
Страница 98: ...84 Chapter 5 Maintenance Checklists F3SJ B User s Manual Checklists ...