73
Reading the Error History with the DeviceNet Configurator
Section 6-3
Communications Unit
Error History
Slice Bus Error
History
Error
code
(Hex)
Contents
Details
Saved in error
history when
power goes OFF?
Corrective action
1st byte
2nd byte
0002
WDT error
0x00
0x00
Yes
Replace the Unit if the error
occurs frequently.
0370
Verification error (Slave miss-
ing)
00
00
No
Connect the missing Unit and
restart.
0372
Verification error (unregistered
Slave joined network)
0x80:
Slice I/O
Node address
(Hex)
No
Remove the unregistered
Unit and restart.
021A
Setting table logic error
Cause:
There was a checksum error in
on of the following tables or a
set value was out-of-range.
• Network parameters
• Registration table
• Slave parameters
• Backup restore data
0x00
0x0A: Registra-
tion table
0x0B: Slave
parameters
0x0C: Network
parameters
0x0F: Backup
restore data
Yes
Download the settings again.
0602
Memory access error
Cause:
• A hardware error occurred in
the Unit’s internal non-vola-
tile memory.
• E2P hardware error
• Backup communications fail-
ure
• FROM save failure
• EEPROM save failure
• FROM hardware error
• ADR failure (communications
failure)
0x01:
Read
error
0x02:
Write
error
0x07: Error his-
tory
0x09: Identity
information
0x0A: Registra-
tion table
0x0C: Network
parameters
0x0F: Backup
restore data
(E2P/FROM)
Yes (No for error
history only)
Replace the Unit if the error
occurs frequently.
Error
code
(Hex)
Contents
Details
Saved in error
history when
power goes OFF?
Corrective action
1st byte
2nd byte
0300
Backup data reception error
0x80:
Slice I/O
Node address
(Hex)
No
Verify that the Unit is con-
nected properly. Check
whether there is excessive
noise in the surroundings.
0374
Transmission error
Cause:
A transmission error occurred.
0x80:
Slice I/O
Node address
(Hex)
No
Verify that the Unit is con-
nected properly. Check
whether there is excessive
noise in the surroundings.
0375
Communications stopped due
to a transmission error.
Cause:
The Unit is set to stop commu-
nications for communications
errors and a transmission error
occurred. (Error code 0374 will
not occur in this case.)
0x80:
Slice I/O
Node address
(Hex)
Yes
Verify that the Unit is con-
nected properly. Check
whether there is excessive
noise in the surroundings.
Содержание SMARTSLICE - 04-2008
Страница 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Страница 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xiv ...
Страница 27: ...8 Basic Operating Procedure Section 1 5 ...
Страница 57: ...38 Unit Functions Section 2 3 ...
Страница 101: ...82 DeviceNet Explicit Messages Appendix A ...
Страница 113: ...94 Standard Models Appendix C ...
Страница 115: ...96 Power Consumption Tables Appendix D ...
Страница 117: ...98 I O Current Consumption Appendix E ...
Страница 119: ...100 Glossary ...