47
Wiring DeviceNet Communications Cables
Section 3-3
Recommended Power
Supplies
Use a SELV power supply with overcurrent protection.
A SELV power supply has redundant or increased insulation between the I/O,
an output voltage of 30 Vr.m.s and a 42.4-V peak or maximum of 60 VDC.
Recommended power supply: S82K-10024 (OMRON) or S8J-10024D
(OMRON)
Recommended Wire
Strip Length
Strip between 7 and 10 mm of insulation at the ends of the wires (stranded or
solid wire).
Pin Terminal Length
Use pin terminals with a pin (conductor) length of 8 to 10 mm.
3-3
Wiring DeviceNet Communications Cables
This section explains how to prepare the DeviceNet communications cables
that connect to the DeviceNet Communications Unit and how to attach com-
munications connectors.
For details on supplying the DeviceNet communications power and grounding
the DeviceNet Network, refer to the
DeviceNet Operation Manual (W267)
.
3-3-1
Connecting Communications Cables
Use the following procedure to prepare the communications cables and con-
nect them to the connectors.
The same methods are used to connect the cables to connectors with and
without set screws.
1,2,3...
1.
Remove about 30 to 80 mm of the cable covering, being careful not to dam-
age the mesh shield underneath. Do not remove more than necessary. Re-
moving excessive cable covering may cause a short-circuit.
3.5 mm
0.6 mm
Side view
Front view
Type
Gauge
Stranded wire
20 AWG to 16 AWG
(0.5 to 1.25 mm
2
)
Solid wire
Pin terminal
Strip 7 to 10 mm.
Pin length: 8 to 10 mm
About 30 to 80 mm
(Remove as little as possible.)
Содержание SMARTSLICE - 04-2008
Страница 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Страница 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 13: ...xiv ...
Страница 27: ...8 Basic Operating Procedure Section 1 5 ...
Страница 57: ...38 Unit Functions Section 2 3 ...
Страница 101: ...82 DeviceNet Explicit Messages Appendix A ...
Страница 113: ...94 Standard Models Appendix C ...
Страница 115: ...96 Power Consumption Tables Appendix D ...
Страница 117: ...98 I O Current Consumption Appendix E ...
Страница 119: ...100 Glossary ...