manualshive.com logo in svg
background image

S8VS

5

*1.

Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in 

ignition or burning.

*2.

For a cold start at 25

°

C. Refer to 

Engineering Data

 on page 18 for details.

*3.

If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range (by more than +10% for 240-W models with indication monitor). 

When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 

*4.

To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.

*5.

Displayed on 7-segment LED. (character height: 8 mm)

*6.

Resolution of output voltage indication: 0.1 V, Precision of output voltage indication: 

±

2% (percentage of output voltage value, 

±

1 digit)

*7.

Resolution of output current indication: 0.1 A; Precision of output current indication: 

±

5% F.S. 

±

1 digit max. (specified by rated output voltage)

*8.

Resolution of peak-hold current indication: 0.1 A; Precision of peak-hold current indication: 

±

5% F.S. 

±

1 digit max. (specified by rated output voltage);

Signal width required for peak-hold current: 20 ms

*9.

A Type and B Type: Sinking, AP Type and BP Type: Sourcing, BE Type: No alarm output.

*10.

S8VS-06024A, S8VS-09024A/AP, S8VS-12024A/AP, S8VS-18024A/AP, and S8VS-24024A/AP only

*11.

The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC).

*12.

The value is when both rated output voltage and rated output current are satisfied.

Power ratings

90 W

Item

Type

Standard

Maintenance forecast monitor

Total run time monitor

Efficiency

With 100-VAC input 83% typical

83% typical

With 200-VAC input 84% typical

85% typical

Input

Voltage 

*

1

100 to 240 VAC (allowable range: 85 to 264 VAC or 80 to 370 VDC 

*

11)

Frequency 

*

1

50/60 Hz (47 to 450 Hz)

Current

With 100-VAC input 2.3 A max., 1.9 A typical

2.3 A max., 1.9 A typical

With 200-VAC input 1.4 A max., 1.0 A typical

1.4 A max., 1.2 A typical

Power factor 

*

12

---

Harmonic current regulation

Conforms to EN61000-3-2

Leakage current

With 100-VAC input 0.5 mA max.
With 200-VAC input 1.0 mA max.

Inrush current 

*

2

With 100-VAC input 17.5 A max., 14 A typical
With 200-VAC input 35 A max., 28 A typical

Output

Voltage adjustment range 

*

3

10% to 15% (with V. ADJ) (The voltage cannot be adjusted for the S8VS-09024

@@@

S-

@

.)

Ripple noise voltage (at rated I/O)

250 mV max.

150 mV max.

Input variation influence

0.5% max. (at 85- to 264-VAC input, 100% load)

Load variation influence (rated input voltage) 1.5% max. (with rated input, 0 to 100% load)
Temperature variation influence

0.05%/

°

C max.

Startup time 

(at rated I/O) 

*

2

With 100-VAC input 460 ms typical

660 ms typical

With 200-VAC input 300 ms typical

420 ms typical

Output hold time 

(at rated I/O) 

*

2

With 100-VAC input 28 ms typical

28 ms typical

With 200-VAC input 132 ms typical

136 ms typical

Additional

functions

Overload protection 

*

2

105% to 160% of rated load current (101% to 110% of rated load current for the S8VS-09024

@@@

S-

@

), inverted L voltage drop, intermittent, automatic reset

Overvoltage protection 

*

2, 

*

4

Yes

Output voltage indication 

*

5

No

Yes (selectable) 

*

6

Output current indication 

*

5

No

Yes (selectable) 

*

7

Peak-hold current indication 

*

5

No

Yes (selectable) 

*

8

Maintenance forecast monitor indication 

*

5

No

Yes (selectable)

No

Maintenance forecast monitor output

No

Yes (transistor output), 30 VDC max., 50 mA max. 

*

9 No

Total run time monitor indication 

*

5

No

Yes (selectable)

Total run time monitor output 

*

5

No

Yes (transistor output), 30 VDC max., 50 mA max. 

*

9

Undervoltage alarm indication 

*

5

No

Yes (selectable)

Undervoltage alarm output terminals

No

Yes (transistor output), 30 VDC max., 50 mA max. 

*

9

Parallel operation

No (However, backup operation is possible. An external diode is required.)

Series operation

Yes for up to 2 Power Supplies (with external diode)

Other

Operating ambient temperature

Refer to the derating curve in . (with no icing or condensation)

Storage temperature

25 to 65

°

C

Operating ambient humidity

25% to 85% (Storage humidity: 25% to 90%)

Dielectric strength

3.0 kVAC for 1 min. (between all inputs and outputs/ alarm outputs; detection current: 20 mA) 

2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)

1.0 kVAC for 1 min. (between all outputs/ alarm outputs and PE terminals; detection current for standard models: 30 mA, detection 

current for models with indication monitor: 20 mA)

500 VAC for 1 min. (between all outputs and alarm outputs; detection current: 20 mA) 

Insulation resistance

100 M

 min. (between all outputs/ alarm outputs and all inputs/ PE terminals) at 500 VDC

Vibration resistance

10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions

10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min each in X, Y, and Z directions

Shock resistance

150 m/s

2

, 3 times each in ±X, ±Y, and ±Z directions

Output indicator

Yes (color: green)

EMI

Conducted 

Emissions

Models with indication monitor: Conforms to EN55011 Group1 Class A and based on FCC Class A, Conforms to EN55011 Group1 

Class B 

*

11

Standard models: Conforms to EN61204-3 EN55011 Group 1 Class B and based on FCC Class A

Radiated 

Emissions

Models with indication monitor: Conforms to EN55011 Group1 Class A, Conforms to EN55011 Group1 Class B 

*

11

Standard models: Conforms to EN55011 Group1 Class B 

EMS

Conforms to EN61204-3 high severity levels

Approved standards 

*

11

Standard model: 

UL 508 (Listing)

(S8VS-09024S-

@

 only): UL 508 (Listing, Class2 Output: Per 1310)

UL 62368-1

CSA C22.2 No.107.1 (cUL)

(S8VS-09024S-

@

 only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)

CSA C22.2 No.62368-1 (cUR)

EN 50178, EN 62368-1

EAC mark, RCM mark

With indication monitor:  UL 508 (Listing)

(S8VS-09024

@@

S-

@

 only): UL 508 (Listing, Class2 Output: Per 1310)

CSA C22.2 No.107.1

(S8VS-09024

@@

S-

@

 only): CSA C22.2 No.107.1 (cUL) (Class2 Output: Per CSA C22.2 No.223)

EN 62477-1

EAC mark, RCM mark, KOSHA S Mark 

*

10

SEMI 

*

11

F47-0706 (With 200-VAC input)

Weight

490 g max.

Содержание S8VS

Страница 1: ...autions for All Power Supplies and Safety Precautions on page 32 Recommended Noise Filter Noise filter S8V NF For more information refer to S8V NF Noise Filter Data Sheet Cat No T212 E1 1 2 3 4 5 6 S8...

Страница 2: ...240 VAC 20 A Peak current 30 A 200 VAC S8VS 48024 S8VS 48024 F Power ratings Input voltage Output voltage VDC Output current Alarm output 2 UL Class 2 Output standards Model number screw terminal bloc...

Страница 3: ...500 ms typical 560 ms typical 560 ms typical With 200 VAC input 340 ms typical 360 ms typical 400 ms typical 360 ms typical 380 ms typical 400 ms typical Output hold time at rated I O 2 With 100 VAC i...

Страница 4: ...ms typical With 200 VAC input 400 ms typical 290 ms typical Output hold time at rated I O 2 With 100 VAC input 34 ms typical 33 ms typical With 200 VAC input 158 ms typical 154 ms typical Additional...

Страница 5: ...l With 200 VAC input 132 ms typical 136 ms typical Additional functions Overload protection 2 105 to 160 of rated load current 101 to 110 of rated load current for the S8VS 09024 S inverted L voltage...

Страница 6: ...ut 30 VDC max 50 mA max 9 No No Yes transistor output 30 VDC max 50 mA max 9 No Total run time monitor indication 5 No Yes selectable No Yes selectable Total run time monitor output 5 No Yes transisto...

Страница 7: ...ut 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9 Undervoltage alarm indication 5 No Yes selectable No Yes selectable Undervoltage alarm output terminals No Yes transistor outp...

Страница 8: ...ircuit Noise filter Inrush current protection Rectifier Smoothing circuit Overcurrent detection circuit S8VS 015 15 W Voltage detection circuit Photocoupler Rectifier smoothing circuit AC L INPUT AC N...

Страница 9: ...thmetic operation circuit Display circuit Switch Overvoltage detection circuit Inrush current protection circuit Rectifier S8VS 06024A 60 W S8VS 06024B 60 W S8VS 06024 60 W AC L INPUT AC N V V DC OUTP...

Страница 10: ...rent protection circuit Drive control circuit Arithmetic operation circuit Alarm DC Low Voltage detection circuit Overcurrent circuit Overvoltage detection circuit Current detection circuit S8VS 09024...

Страница 11: ...rrent circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Arithmetic operation circuit Rectifier smoothing circuit V V DC OUTPUT Alarm DC Low S8VS 12024A 120 W...

Страница 12: ...detection circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit V V DC OUTPUT Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low S8VS 18024A 18...

Страница 13: ...control circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low V V V V DC OUTPUT S8VS 24024A...

Страница 14: ...circuit Current detection circuit V V V V DC OUTPUT V V S8VS 48024A S8VS 48024B Display circuit Switch Arithmetic operation circuit S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 90 120 180 and...

Страница 15: ...ety standards Always ground this terminal No Name Function 1 Input terminals L N Connect the input lines to these terminals 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2...

Страница 16: ...als 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2 3 DC Output terminals V V Connect the load lines to these terminals 4 Output indicator DC ON Green Lights while a direct...

Страница 17: ...ent Apk Lights up during indication of peak hold current Yrs Lights up during indication of maintenance forecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Ligh...

Страница 18: ...acket is used Note 1 Internal parts may occasionally deteriorate or be damaged Do not use the Power Supply in areas outside the derating curve i e the area shown by shading A in the above graph 2 If t...

Страница 19: ...uent inrush current or overloading at the load end Do not use the Power Supply for such applications Peak Output Current S8VS 48024 only The boost current is a temporary current that exceeds the rated...

Страница 20: ...S 06024A S8VS 06024B Further an output undervoltage output terminal DC LOW to an external device is given from the transistor to notify of the error excluding S8VS 06024A S8VS 06024B S8VS 24BE Output...

Страница 21: ...ng 15 max Five M4 Square Washer Screw Rail Stopper 35 4 74 95 1 40 1 S8VS 06024 60 W S8VS 06024A 60 W S8VS 06024B 60 W 1 7 10 110 3 11 max 116 2 Five M4 Square Washer Screw 4 5 Sliding 15 max Screw Le...

Страница 22: ...VS 24024BE 240 W S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 150 1 7 70 10 1 Rail Stopper Rail Stopper Screw Lessly Terminal The 2 5 mm pace 122 2 127 2 1 Nine M4 Square Washer Screw 4 5 Slid...

Страница 23: ...15 max 115 1 10 S8VS 18024 F 180 W S8VS 18024A F 180 W S8VS 18024B F 180 W S8VS 18024BE F 180 W 1 50 10 100 1 10 117 6 7 max 119 3 Rail Stopper Rail Stopper 97 3 35 4 4 5 Sliding 15 max 115 1 S8VS 24...

Страница 24: ...over Order Separately Note Terminal block cover attaches to the body Please order from the loss time 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the...

Страница 25: ...unting Bracket For 60 90 120 W models S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W...

Страница 26: ...no key operation for 30 seconds or more Model indication Setting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and dis...

Страница 27: ...r at the same time When undervoltage alarm is indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication No...

Страница 28: ...method Setting after restoration Noise detected in voltage or current No change Automatic reset No change h t Overheated Maintenance forecast output terminal Yrs turns OFF Automatic reset No change e0...

Страница 29: ...g time are indicated alternately If the setting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes l...

Страница 30: ...rchase even if indication and output of maintenance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indica...

Страница 31: ...larm set value reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode The S8VS 09024BE S8VS 12024BE S8VS 18024BE and S8VS 24024BE...

Страница 32: ...max on the left and right 60 W 90 W 120 W 180 W 240 W and 480 W Models Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts U...

Страница 33: ...n Monitor Except 60 W Models It may take from several years to more than 10 years under general operating conditions for the power supply to output the maintenance forecast monitor alarm S8VS 24A The...

Страница 34: ...circuited a reverse voltage will be generated inside the Power Supply If this occurs the Power Supply may possibly deteriorate or be damaged Always connect a diode as shown in the figure Select a dio...

Страница 35: ...t voltage x rated output current In Case There Is No Output Voltage The possible cause for no output voltage may be that the overcurrent or overvoltage protection has operated The internal protection...

Страница 36: ...MEMO 36...

Страница 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 38: ...Estates IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www i...

Отзывы: