Safety Precautions

!

CAUTION

Minor electric shock, fire, or Product failure may 

occasionally occur. Do not disassemble, modify, or 

repair the Product or touch the interior of the 

Product.

Minor burns may occasionally occur. Do not touch 

the Product while power is being supplied or 

immediately after power is turned OFF.

Fire may occasionally occur. Tighten terminal screws 

to the specified torque (15- and 30-W models: 0.8 to 

1.0 N·m/60-, 90-,120-, 180-, 240-, and 480-W models: 

1.08 N·m).

Minor injury due to electric shock may occasionally 

occur. Do not touch the terminals while power is 

being supplied. Always close the terminal cover after 

wiring.

Minor electric shock, fire, or Product failure may 

occasionally occur. Do not allow any pieces of metal 

or conductors or any clippings or cuttings resulting 

from installation work to enter the Product.

Mounting

Take adequate measures to ensure proper heat dissipation to 

increase the long-term reliability of the Product. Be sure to allow 

convection in the atmosphere around devices when mounting. Do 

not use in locations where the ambient temperature exceeds the 

range of the derating curve.

When cutting out holes for mounting, make sure that cuttings do 

not enter the interior of the Products.

15-W and 30-W Models

Improper mounting will interfere with heat dissipation and may 

occasionally result in deterioration or damage of internal parts. Use 

the Product within the derating curve for the mounting direction that 

is used.

Use a mounting bracket when the Product is mounted facing 

horizontally.

Heat dissipation will be adversely affected. When the Product is 

mounted facing horizontally, always place the side with the label 

facing upward. 

Operate the Power Supply within a range that is 5

°

C less than the 

values in the derating curve in 

Engineering Data

 on page 18 if the 

Power Supply is used with an installation spacing of 10 mm min. 

(20 mm max.) on the left and right.

60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models

Improper mounting will interfere with heat dissipation and may 

occasionally result in deterioration or damage of internal parts. Use 

the standard mounting method only.

The internal parts may occasionally deteriorate and be broken due 

to adverse heat radiation. Do not loosen the screw on the side face 

of the main body.

Wiring

Connect the ground completely. A protective earthing terminal 

stipulated in safety standards is used. Electric shock or malfunction 

may occur if the ground is not connected completely.

Minor fire may possibly occur. Ensure that input and output 

terminals are wired correctly.

Do not apply more than 100-N force to the terminal block when 

tightening it.

Be sure to remove the sheet covering the Product for machining 

before power-ON so that it does not interfere with heat dissipation. 

When wiring a screwless terminal block, do not insert more than 

one wire into a single terminal.

When using a screwless terminal block, connect or disconnect the 

I/O wire to each terminal while inserting an appropriate tool, such 

as a flat-blade screwdriver, into the tool insertion hole. Make sure 

that the wire is securely connected to the terminal after wiring. Do 

not insert wires into the tool insertion holes.

If a wire is not inserted far enough or if it is loose, electric shock, 

fire, or equipment failure may occur. Strip the wires according to 

specifications. Insert an appropriate tool, such as a flat-blade 

screwdriver, into the tool insertion hole, insert the wire until the 

stripped portion is no longer visible, and then remove the tool. 

Make sure that the wires are securely connected to the terminal 

block after wiring. Never insert wires into the tool insertion holes.

The method of use Alarm output terminal

The method of use Alarm output terminal is push the button then 

insert  or pull out the wire.

Please make sure that the wire is already fixed on the terminal.

Precautions for Safe Use

*1

*1

*2

*1. Convection of air
*2. 20 mm min.

Tool insertion hole

3.7 mm

Wire hole

flat-blade screwdriver

button

wire

Содержание S8VS

Страница 1: ...autions for All Power Supplies and Safety Precautions on page 32 Recommended Noise Filter Noise filter S8V NF For more information refer to S8V NF Noise Filter Data Sheet Cat No T212 E1 1 2 3 4 5 6 S8...

Страница 2: ...240 VAC 20 A Peak current 30 A 200 VAC S8VS 48024 S8VS 48024 F Power ratings Input voltage Output voltage VDC Output current Alarm output 2 UL Class 2 Output standards Model number screw terminal bloc...

Страница 3: ...500 ms typical 560 ms typical 560 ms typical With 200 VAC input 340 ms typical 360 ms typical 400 ms typical 360 ms typical 380 ms typical 400 ms typical Output hold time at rated I O 2 With 100 VAC i...

Страница 4: ...ms typical With 200 VAC input 400 ms typical 290 ms typical Output hold time at rated I O 2 With 100 VAC input 34 ms typical 33 ms typical With 200 VAC input 158 ms typical 154 ms typical Additional...

Страница 5: ...l With 200 VAC input 132 ms typical 136 ms typical Additional functions Overload protection 2 105 to 160 of rated load current 101 to 110 of rated load current for the S8VS 09024 S inverted L voltage...

Страница 6: ...ut 30 VDC max 50 mA max 9 No No Yes transistor output 30 VDC max 50 mA max 9 No Total run time monitor indication 5 No Yes selectable No Yes selectable Total run time monitor output 5 No Yes transisto...

Страница 7: ...ut 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9 Undervoltage alarm indication 5 No Yes selectable No Yes selectable Undervoltage alarm output terminals No Yes transistor outp...

Страница 8: ...ircuit Noise filter Inrush current protection Rectifier Smoothing circuit Overcurrent detection circuit S8VS 015 15 W Voltage detection circuit Photocoupler Rectifier smoothing circuit AC L INPUT AC N...

Страница 9: ...thmetic operation circuit Display circuit Switch Overvoltage detection circuit Inrush current protection circuit Rectifier S8VS 06024A 60 W S8VS 06024B 60 W S8VS 06024 60 W AC L INPUT AC N V V DC OUTP...

Страница 10: ...rent protection circuit Drive control circuit Arithmetic operation circuit Alarm DC Low Voltage detection circuit Overcurrent circuit Overvoltage detection circuit Current detection circuit S8VS 09024...

Страница 11: ...rrent circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Arithmetic operation circuit Rectifier smoothing circuit V V DC OUTPUT Alarm DC Low S8VS 12024A 120 W...

Страница 12: ...detection circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit V V DC OUTPUT Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low S8VS 18024A 18...

Страница 13: ...control circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low V V V V DC OUTPUT S8VS 24024A...

Страница 14: ...circuit Current detection circuit V V V V DC OUTPUT V V S8VS 48024A S8VS 48024B Display circuit Switch Arithmetic operation circuit S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 90 120 180 and...

Страница 15: ...ety standards Always ground this terminal No Name Function 1 Input terminals L N Connect the input lines to these terminals 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2...

Страница 16: ...als 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2 3 DC Output terminals V V Connect the load lines to these terminals 4 Output indicator DC ON Green Lights while a direct...

Страница 17: ...ent Apk Lights up during indication of peak hold current Yrs Lights up during indication of maintenance forecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Ligh...

Страница 18: ...acket is used Note 1 Internal parts may occasionally deteriorate or be damaged Do not use the Power Supply in areas outside the derating curve i e the area shown by shading A in the above graph 2 If t...

Страница 19: ...uent inrush current or overloading at the load end Do not use the Power Supply for such applications Peak Output Current S8VS 48024 only The boost current is a temporary current that exceeds the rated...

Страница 20: ...S 06024A S8VS 06024B Further an output undervoltage output terminal DC LOW to an external device is given from the transistor to notify of the error excluding S8VS 06024A S8VS 06024B S8VS 24BE Output...

Страница 21: ...ng 15 max Five M4 Square Washer Screw Rail Stopper 35 4 74 95 1 40 1 S8VS 06024 60 W S8VS 06024A 60 W S8VS 06024B 60 W 1 7 10 110 3 11 max 116 2 Five M4 Square Washer Screw 4 5 Sliding 15 max Screw Le...

Страница 22: ...VS 24024BE 240 W S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 150 1 7 70 10 1 Rail Stopper Rail Stopper Screw Lessly Terminal The 2 5 mm pace 122 2 127 2 1 Nine M4 Square Washer Screw 4 5 Slid...

Страница 23: ...15 max 115 1 10 S8VS 18024 F 180 W S8VS 18024A F 180 W S8VS 18024B F 180 W S8VS 18024BE F 180 W 1 50 10 100 1 10 117 6 7 max 119 3 Rail Stopper Rail Stopper 97 3 35 4 4 5 Sliding 15 max 115 1 S8VS 24...

Страница 24: ...over Order Separately Note Terminal block cover attaches to the body Please order from the loss time 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the...

Страница 25: ...unting Bracket For 60 90 120 W models S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W...

Страница 26: ...no key operation for 30 seconds or more Model indication Setting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and dis...

Страница 27: ...r at the same time When undervoltage alarm is indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication No...

Страница 28: ...method Setting after restoration Noise detected in voltage or current No change Automatic reset No change h t Overheated Maintenance forecast output terminal Yrs turns OFF Automatic reset No change e0...

Страница 29: ...g time are indicated alternately If the setting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes l...

Страница 30: ...rchase even if indication and output of maintenance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indica...

Страница 31: ...larm set value reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode The S8VS 09024BE S8VS 12024BE S8VS 18024BE and S8VS 24024BE...

Страница 32: ...max on the left and right 60 W 90 W 120 W 180 W 240 W and 480 W Models Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts U...

Страница 33: ...n Monitor Except 60 W Models It may take from several years to more than 10 years under general operating conditions for the power supply to output the maintenance forecast monitor alarm S8VS 24A The...

Страница 34: ...circuited a reverse voltage will be generated inside the Power Supply If this occurs the Power Supply may possibly deteriorate or be damaged Always connect a diode as shown in the figure Select a dio...

Страница 35: ...t voltage x rated output current In Case There Is No Output Voltage The possible cause for no output voltage may be that the overcurrent or overvoltage protection has operated The internal protection...

Страница 36: ...MEMO 36...

Страница 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 38: ...Estates IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www i...

Отзывы: