![Omron S8VS Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/omron/s8vs/s8vs_manual_743734031.webp)
S8VS
31
Models with Total Run Time Monitor
(S8VS-
@@@
24B
@@/
S8VS-
@@@
24B
E@
)
S8VS-06024B
The accumulated value of the operating time of the Power Supply is
displayed as the total run time.
0
(kh) will be displayed initially after
purchase and then the display will advance in
1
-kh steps as the
operating time accumulates. The S8VS-06024B, however, does not
have an alarm function (setting, display, or output).
S8VS-09024B
@@
/S8VS-09024BE
@
/
S8VS-12024B
@
/S8VS-12024B
E
/
S8VS-18024B
@
/S8VS-18024BE/
S8VS-24024B
@
/S8VS-24024BE/S8VS-48024B
The display will appear when the set value for the total run time has
been reached.
The accumulated value of the operating time of the Power Supply is
displayed as the total run time.
0
(kh) will be displayed initially after
purchase and then the display will advance in
1
-kh steps as the
operating time accumulates. When the total run time reaches the
alarm set value, the alarm (
a02
) and the total run time will be
displayed alternately and a transistor (total run time output terminal
(kh)) will output the status externally.
(Alarm set value reached = OFF, i.e., no continuity at the total run time
output terminal (kh))
The alarm set value can be changed in the setting mode.
The S8VS-09024BE
@
, S8VS-12024BE, S8VS-18024BE, and S8VS-
24024BE do not have an alarm output.
Example: Alarm Displays When a Total Run Time Set Value of
88 kh Is Reached
Note:
The total run time cannot be reset. To clear the alarm, change
the alarm set value to a value higher than the value displayed
for the total run time.
Time Chart
*
Setting is possible for the following models only:
S8VS-09024B
@@
, S8VS-09024BE
@
, S8VS-12024B
@
,
S8VS-12024BE, S8VS-18024B
@
, S8VS-18024BE,
S8VS-24024B
@
,
S8VS-24024BE,
S8VS-48024B
Note: 1.
The total run time does not include the time that the Power
Supply is OFF.
2.
The total run time measures the total time that power is
being supplied and is not related in any way to deterioration
in the electrolytic capacitor built into the Power Supply or to
the effects of the ambient temperature.
Operation mode
Total run time
Total run time
Total run time set value reached.
(See note.)
Output
voltage
Output
current
Peak hold
current
Note: The alarm (
a02
)
and the total run
time will be
displayed
alternately.
Total run time
50 kh
0 kh
AC input
Alarm output
Set value = 50 kh
(See note.)
Содержание S8VS
Страница 36: ...MEMO 36...