Use the following material for the wires to be connected to the 
S8VS to prevent smoking or ignition caused by abnormal loads.

Recommended Wire Type

15-W and 30-W Models

60-W, 90-W, 120-W, 180-W, 240-W, and 480-W Models

Strip I/O wires for 11 mm when using a screwless terminal block.

*

The rated current for output terminals is 10 A per terminal. Be sure 

to use multiple terminals simultaneously for current that exceeds 

the terminal rating. When applying a current of 10 A or more, use at 

least two terminals each for the positive and negative wires.

Installation Environment

Do not use the Power Supply in locations subject to shocks or 
vibrations. In particular, install the Power Supply as far away as 
possible from contactors or other devices that are a vibration 
source.

Install the Power Supply well away from any sources of strong, 
high-frequency noise and surge.

Operating Life

The life of a Power Supply is determined by the life of the 
electrolytic capacitors used inside. Here, Arrhenius Law applies, 
i.e., the life will be cut in half for each rise of 10

°

C or the life will be 

doubled for each drop of 10

°

C. The life of the Power Supply can 

thus be increased by reducing its internal temperature.

Ambient Operating and Storage Environments 

Store the Power Supply at a temperature of 

25 to 65

°

C and a 

humidity of 25% to 90%.

Do not use the Power Supply in areas outside the derating curve 
otherwise, internal parts may occasionally deteriorate or be 
damaged.

Use the Power Supply at a humidity of 25% to 85%.

Do not use the Power Supply in locations subject to direct sunlight.

Do not use locations where liquids, foreign matter, or corrosive 
gases may enter the interior of Products.

S8VS-

@@@

24A

@@

 Models only

Satisfy the following conditions when storing the Power Supply for 
long periods of time to maintain its remaining service life function.
When storing for more than three months, store within an ambient 
temperature range of 

25 to +30

°

C and the humidity range of 25% to 

70%.

Periodic Check for Models with Indication 

Monitor Except 60-W Models

It may take from several years to more than 10 years under general 
operating conditions for the power supply to output the maintenance 
forecast monitor alarm (S8VS-

@@@

24A

@@

). The total run time 

monitor (S8VS-

@@@

24B

@@

/S8VS-

@@@

24BE

@

) may be a similar 

number of years as the maintenance forecast monitor according to 
some settings. During operation over an extended period of time, 
periodically check if the maintenance forecast monitor output (Yrs) or 
total run time monitor output (kh) is correctly functioning by the 
following procedure.

1.

Select the operation mode.

2.

Check that the output (Yrs/kh) is turned ON (with continuity).

3.

In the operation mode, press and hold the Down Key 

D

 (10) and 

the Mode Key 

M

 (8) simultaneously for at least three seconds.

The main display (6) changes to “

a02

.”

An inactive output (Yrs/kh) (no continuity) in the “

a02

” indication 

indicates the correct function.

4.

Release keys to return to the regular state.

Note:

DC output stays ON during the periodical check.

Overcurrent Protection

Internal parts may possibly deteriorate or be damaged if a 
short-circuited or overcurrent state continues during operation. 

Internal parts may possibly deteriorate or be damaged if the Power 
Supply is used for applications with frequent inrush current or 
overloading at the load end. Do not use the Power Supply for such 
applications.

The DC ON indicator (green) flashes if the overload protection 
function operates.

Model

Stranded wire

Solid wire

S8VS-03005

AWG18 to 14

(0.9 to 2.0 mm

2

)

AWG18 to 16

(0.9 to 1.1 mm

2

)

Other models

AWG20 to 14

(0.5 to 2.0 mm

2

)

AWG20 to 16

(0.5 to 1.1 mm

2

)

Model

Recommended wire size

Input 

terminals

Output 

terminals

Alarm output 

terminals

S8VS-06024

@

AWG14 to 20 

(Cross section: 

0.517 to 

2.081 mm

2

)

AWG14 to 20 

(Cross section: 

0.517 to 

2.081 mm

2

)

---

S8VS-

09024

@@@@

AWG18 to 28 

(Cross 

section: 0.081 

to 0.823 mm

2

)

(Wires to be 

stripped: 

9 to 10 mm)

S8VS-

12024

@@@

AWG14 to 18 

(Cross section: 

0.823 to 

2.081 mm

2

)

S8VS-

18024

@@@

AWG14 to 16 

(Cross section: 

1.309 to 

2.081 mm

2

)

S8VS-

24024

@@@

AWG14

(Cross section: 

2.081 mm

2

)

S8VS-48024

@

AWG 14 to 16

(Cross section: 

1,309 to 

2,081 mm

2

)

1

13

(COMMON)

12

(Yrs/kh)

11

(DC LOW)

2

4

5

8

9

7

6

10

3

60-, 90-, 120-, 
180-, 240-W 
Models

13

11

4

5

8

9

7

12

6

10

14

15

16

3

1

2

(Yrs/kh)

(DC LOW)

480-W Models

Содержание S8VS

Страница 1: ...autions for All Power Supplies and Safety Precautions on page 32 Recommended Noise Filter Noise filter S8V NF For more information refer to S8V NF Noise Filter Data Sheet Cat No T212 E1 1 2 3 4 5 6 S8...

Страница 2: ...240 VAC 20 A Peak current 30 A 200 VAC S8VS 48024 S8VS 48024 F Power ratings Input voltage Output voltage VDC Output current Alarm output 2 UL Class 2 Output standards Model number screw terminal bloc...

Страница 3: ...500 ms typical 560 ms typical 560 ms typical With 200 VAC input 340 ms typical 360 ms typical 400 ms typical 360 ms typical 380 ms typical 400 ms typical Output hold time at rated I O 2 With 100 VAC i...

Страница 4: ...ms typical With 200 VAC input 400 ms typical 290 ms typical Output hold time at rated I O 2 With 100 VAC input 34 ms typical 33 ms typical With 200 VAC input 158 ms typical 154 ms typical Additional...

Страница 5: ...l With 200 VAC input 132 ms typical 136 ms typical Additional functions Overload protection 2 105 to 160 of rated load current 101 to 110 of rated load current for the S8VS 09024 S inverted L voltage...

Страница 6: ...ut 30 VDC max 50 mA max 9 No No Yes transistor output 30 VDC max 50 mA max 9 No Total run time monitor indication 5 No Yes selectable No Yes selectable Total run time monitor output 5 No Yes transisto...

Страница 7: ...ut 30 VDC max 50 mA max 9 No Yes transistor output 30 VDC max 50 mA max 9 Undervoltage alarm indication 5 No Yes selectable No Yes selectable Undervoltage alarm output terminals No Yes transistor outp...

Страница 8: ...ircuit Noise filter Inrush current protection Rectifier Smoothing circuit Overcurrent detection circuit S8VS 015 15 W Voltage detection circuit Photocoupler Rectifier smoothing circuit AC L INPUT AC N...

Страница 9: ...thmetic operation circuit Display circuit Switch Overvoltage detection circuit Inrush current protection circuit Rectifier S8VS 06024A 60 W S8VS 06024B 60 W S8VS 06024 60 W AC L INPUT AC N V V DC OUTP...

Страница 10: ...rent protection circuit Drive control circuit Arithmetic operation circuit Alarm DC Low Voltage detection circuit Overcurrent circuit Overvoltage detection circuit Current detection circuit S8VS 09024...

Страница 11: ...rrent circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit Arithmetic operation circuit Rectifier smoothing circuit V V DC OUTPUT Alarm DC Low S8VS 12024A 120 W...

Страница 12: ...detection circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit V V DC OUTPUT Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low S8VS 18024A 18...

Страница 13: ...control circuit Voltage detection circuit Overvoltage detection circuit Rectifier smoothing circuit Rectifier smoothing circuit Arithmetic operation circuit Alarm DC Low V V V V DC OUTPUT S8VS 24024A...

Страница 14: ...circuit Current detection circuit V V V V DC OUTPUT V V S8VS 48024A S8VS 48024B Display circuit Switch Arithmetic operation circuit S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 90 120 180 and...

Страница 15: ...ety standards Always ground this terminal No Name Function 1 Input terminals L N Connect the input lines to these terminals 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2...

Страница 16: ...als 1 2 Protective Earth terminal PE Connect the ground line to this terminal 2 3 DC Output terminals V V Connect the load lines to these terminals 4 Output indicator DC ON Green Lights while a direct...

Страница 17: ...ent Apk Lights up during indication of peak hold current Yrs Lights up during indication of maintenance forecast monitor Blinks during setup of maintenance forecast monitor setting S8VS 48024A kh Ligh...

Страница 18: ...acket is used Note 1 Internal parts may occasionally deteriorate or be damaged Do not use the Power Supply in areas outside the derating curve i e the area shown by shading A in the above graph 2 If t...

Страница 19: ...uent inrush current or overloading at the load end Do not use the Power Supply for such applications Peak Output Current S8VS 48024 only The boost current is a temporary current that exceeds the rated...

Страница 20: ...S 06024A S8VS 06024B Further an output undervoltage output terminal DC LOW to an external device is given from the transistor to notify of the error excluding S8VS 06024A S8VS 06024B S8VS 24BE Output...

Страница 21: ...ng 15 max Five M4 Square Washer Screw Rail Stopper 35 4 74 95 1 40 1 S8VS 06024 60 W S8VS 06024A 60 W S8VS 06024B 60 W 1 7 10 110 3 11 max 116 2 Five M4 Square Washer Screw 4 5 Sliding 15 max Screw Le...

Страница 22: ...VS 24024BE 240 W S8VS 48024 480 W S8VS 48024A 480 W S8VS 48024B 480 W 150 1 7 70 10 1 Rail Stopper Rail Stopper Screw Lessly Terminal The 2 5 mm pace 122 2 127 2 1 Nine M4 Square Washer Screw 4 5 Slid...

Страница 23: ...15 max 115 1 10 S8VS 18024 F 180 W S8VS 18024A F 180 W S8VS 18024B F 180 W S8VS 18024BE F 180 W 1 50 10 100 1 10 117 6 7 max 119 3 Rail Stopper Rail Stopper 97 3 35 4 4 5 Sliding 15 max 115 1 S8VS 24...

Страница 24: ...over Order Separately Note Terminal block cover attaches to the body Please order from the loss time 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 Values in parentheses are for the...

Страница 25: ...unting Bracket For 60 90 120 W models S82Y VS10S Side mounting Bracket For 180 W models S82Y VS15S Side mounting Bracket For 240 W models S82Y VS20S Front mounting Bracket For 60 90 120 180 and 240 W...

Страница 26: ...no key operation for 30 seconds or more Model indication Setting mode Press and hold Up key U or Down Key D for three seconds or more Output voltage Voltage output by Power Supply is monitored and dis...

Страница 27: ...r at the same time When undervoltage alarm is indicated Press Key output load indication When the maintenance forecast monitor or overheat alarm is indicated Press Key undervoltage alarm indication No...

Страница 28: ...method Setting after restoration Noise detected in voltage or current No change Automatic reset No change h t Overheated Maintenance forecast output terminal Yrs turns OFF Automatic reset No change e0...

Страница 29: ...g time are indicated alternately If the setting is less than 2 0 years the indication changes to a value 1 5 after the remaining time becomes less than two years and after the remaining time becomes l...

Страница 30: ...rchase even if indication and output of maintenance forecast monitor are not issued 2 The maintenance forecast is accelerated or decelerated according to operating conditions Periodically check indica...

Страница 31: ...larm set value reached OFF i e no continuity at the total run time output terminal kh The alarm set value can be changed in the setting mode The S8VS 09024BE S8VS 12024BE S8VS 18024BE and S8VS 24024BE...

Страница 32: ...max on the left and right 60 W 90 W 120 W 180 W 240 W and 480 W Models Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts U...

Страница 33: ...n Monitor Except 60 W Models It may take from several years to more than 10 years under general operating conditions for the power supply to output the maintenance forecast monitor alarm S8VS 24A The...

Страница 34: ...circuited a reverse voltage will be generated inside the Power Supply If this occurs the Power Supply may possibly deteriorate or be damaged Always connect a diode as shown in the figure Select a dio...

Страница 35: ...t voltage x rated output current In Case There Is No Output Voltage The possible cause for no output voltage may be that the overcurrent or overvoltage protection has operated The internal protection...

Страница 36: ...MEMO 36...

Страница 37: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 38: ...Estates IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www i...

Отзывы: