Fan
Forced Air Circulation
OMRON
product
OMRON
product
Room Cooling
Cool the entire room where the control panel is located.
Room Cooling
Cooler
Control panel
Low Temperatures
The Box PC may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least 5°C inside the panel, by implementing measures such as instal-
ling a low-capacity space heater in the panel.
Alternatively, leave the Box PC power ON to keep the Box PC warm.
5-3-4
Humidity
Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to short-
circuiting.
When there is a possibility of this occurring, take measures against condensation, such as leaving the
Box PC power ON at night or installing a heater in the control panel to keep it warmer.
Moisture
absorber
Power ON
Control panel
Heater
Examples of Measures against Condensation
OMRON
product
5 Installation
5 - 18
NY-series Industrial Box PC Without Operating System User's Manual (W586)
Содержание NYB17-*100 SERIES
Страница 8: ...CONTENTS 6 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 30: ...Revision History 28 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 32: ...Sections in this Manual 30 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 40: ...1 Overview 1 8 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 68: ...3 Software 3 4 NY series Industrial Box PC Without Operating System User s Manual W586...
Страница 189: ...I Index I 1 NY series Industrial Box PC Without Operating System User s Manual W586 I...
Страница 192: ......
Страница 193: ......