Reference
&
Section 6-2
If the actual character string is longer than the specified character string length,
the specified number of characters is written and the remainder are discarded.
A timeout error message is displayed if the actual character string is shorter than
the specified character string length.
Writing Numerals
A numeral (4 digits or 8 digits) can be written to a numeral table in the NT600S
using the following commands.
4-digit Write Numeral Memory Table
Format
1B
[ESC]
43
C
d
1
d
2
d
3
n
1
n
2
n
3
n
4
d
1
d
2
d
3
: Numeral memory table address of write destination (3-digit hexadeci-
mal)
000 to 1FF
H
(o to 511)
n
1
n
2
n
3
n
4
:
Number data (4-digit BCD or 4-digit hexadecimal)
Description
Writes 4-digit number data (decimal or hexadecimal) to the specified numeral
table.
If a 4-digit number data is written while an 8-digit numeral is displayed, the lower
4 digits are updated.
8-digit Write Numeral Memory Table
Format
1B
[ESC]
44
D
d
1
d
2
n
1
n
2
n
3
n
4
d
3
n
6
n
7
n
8
n
5
d
1
d
2
d
3
: Numeral memory table address of write destination (3-digit hexadeci-
mal)
000 to 1FF
H
(0 to 511)
n
1
n
2
n
3
n
4
n
5
n
6
n
7
n
8
:
Number data (8-digit BCD or 8-digit hexadecimal)
Description
Writes the 8-digit number data (decimal or hexadecimal) to the specified numer-
al memory table
To write a negative numeral (decimal), specify “F” for “n
1
” (in this case, a 7-digit
numeral is written.)
Содержание NT-series
Страница 1: ...NT series Programmable Terminal Operation Manual Cat No V022 E3 1 ...
Страница 2: ... ...
Страница 4: ... ...
Страница 9: ... PRECAUTIONS ...
Страница 14: ... ...
Страница 36: ... ...
Страница 166: ... ...
Страница 254: ... 0 4 4 5 4 5 6 5 4 4 5 5 7 5 5 6 5 ...
Страница 267: ... ...
Страница 281: ... 2 C500 LK201 and C200H LK201 V1 only ...
Страница 311: ... ...
Страница 317: ... ...