Section 2-4
CVM1/CV series backplate mounted type: CV500-LK201
[Setting the front switches]
Set the operating conditions with the PC System Setting functions when a
CVM1/CV series host link unit is connected to the NT600S. The PC system set-
tings can be made directly from the peripheral tool (LSS etc.) or the PC system
setting information created with a peripheral tool can be transferred to the CPU.
The following describes the switch settings so as to enable the PC system set-
tings. For the details of the PC system settings, refer to the “SYSMAC CVM1/CV
Series Support Software Operation Manual (Details)” (W196-E1-
).
PC system setting (DIP SW1)
Set SW1 to “OFF”.
Communication is performed in accordance with the
values set in the PC CPU special I/O unit system
settings. The initial values in the system settings
are as follows:
Unit # (SW3 and SW4)
Set these switches to “0”.
I/O port selection (selector switch)
Set this to “RS-232C”.
CTS selection (DIP SW2 and SW3)
Set SW2 or SW3 to “ON”. (Set this always to “0V”.)
To use communication port 1, set SW2. To use commu-
nication port 2, set SW3.
Communications
port 1
Communications
port 2
I/O port
selector
switch
RS-232C
↔
RS-422A
(RS-232C/
RS-422A)
(RS-232C)
Baud rate
: 9600 bps
Parity
: Even
Xon/Xoff control : Not performed
Communication mode
: Full duplex
Stop bit
: 2 bits
Data length
: 7 bits
Содержание NT-series
Страница 1: ...NT series Programmable Terminal Operation Manual Cat No V022 E3 1 ...
Страница 2: ... ...
Страница 4: ... ...
Страница 9: ... PRECAUTIONS ...
Страница 14: ... ...
Страница 36: ... ...
Страница 166: ... ...
Страница 254: ... 0 4 4 5 4 5 6 5 4 4 5 5 7 5 5 6 5 ...
Страница 267: ... ...
Страница 281: ... 2 C500 LK201 and C200H LK201 V1 only ...
Страница 311: ... ...
Страница 317: ... ...