background image

 

  

Section 1-2

2-2-2

Principal Functions of NT600S

Functions Related to the Data Display

Character display

Characters of various sizes can be displayed. Characters can flash or be highlighted.

Figure display

Straight lines, circles, and other graphic figures can be displayed.

Memory data display

Contents of the character-string memory table and the numeral memory table can be dis-
played. The memory table contents can be changed from the PC/Host.

Bar graph display

Bar graphs corresponding to the contents of the numeral table can be displayed.

Lamp display

Lamps which turn on or flash as controlled by the PC/Host can be displayed.

Functions Related to the Data Input

Input by the touch switch

Data can be input by simply touching the screen.

Numeric setting function

The touch keys can be assigned with numeric
values so that the numeric values can be input
at the operation site and sent to the PC.

Other Functions

Buzzer

A built-in buzzer can be used.

Communications with a PC/Host

The NT600S can be connected to a PC/Host to enable data to be received
and touch switch information to be sent by using the host link function, NT

link function, C200H direct communication function, or RS-232C.

System function

The system setting and maintenance can be executed by using the Sys-

tem Menu on the screen.

Screen data creation

The screen data can be created by using support tools on the computer

and stored in the unit.

Содержание NT-series

Страница 1: ...NT series Programmable Terminal Operation Manual Cat No V022 E3 1 ...

Страница 2: ... ...

Страница 3: ...tion in this sense The abbreviation PC means Programmable Controller and is not used as an abbreviation for anything else The abbreviation Host means a controller such as an FA computer which controls a PT programmable terminal Visual Aids The following headings appear in the left column of the manual to help you locate different types of informa tion Note Indicates information of particular inter...

Страница 4: ... ...

Страница 5: ... PRECAUTIONS xi SECTION 2 Functions of the NT600S 2 SECTION 3 Hardware Settings and Connections 23 0 0 1 2 3 0 1 2 3 4 5 SECTION 4 System Menu Operation 65 4 6 6 6 5 7 6 4 8 9 6 4 5 5 6 SECTION 5 NT600S Functions 113 6 5 ...

Страница 6: ... C Handling the RS 232C RS 422 Converter Unit 262 D NT600S Installation Environment 264 E Method for Making the Cable for Connection to the PC Host 266 F Connecting to an RS 232C RS 422 Converter Unit 1 1 278 G Function Restrictions Depending on the Support Tool 280 H Making the Cable for Connection to the Support Tool 281 I NT600S Internal Processing 283 J Model List 286 K Option List 291 L PC Me...

Страница 7: ...ifications required to set up a PT system including hardware switch settings and installation Section 3 provides steps required for initial PT operation Section 4 describes functions used to create screens and control display attributes on the PT Included is automatic transfer of data from the host computer via character string and numeral tables Section 5 describes functions used to input data on...

Страница 8: ...a programmable terminal body and host interface unit However note that a C200H interface unit is required for com munications using the C200H direct communication function This operation manual describes the functions and handling of both the programmable termi nal body and the host interface function Creating and Transferring Screen Data NT Series Support Tool Ver 2 Operation Manual V028 E1 The s...

Страница 9: ... PRECAUTIONS ...

Страница 10: ...n WARNING It is extremely important that Programmable Terminals and related devices be used for the specified purpose and under the specified conditions especially in applications that can directly or indirectly affect human life You must consult with your OMRON representative before applying Programmable Terminals to the above mentioned applications WARNING Do not use input functions such as PT t...

Страница 11: ...ons On unpacking the NT600S check its external appearance and confirm that there is no damage Also confirm that there is no abnormal noise on shaking the unit lightly The product may malfunction if it is damaged If the DIP switch settings have been changed when the NT600S is powered reset the power to the NT600S The changes with the DIP switches become effective only after the power supply is rese...

Страница 12: ...fety before turning the power ON OFF or resetting Other wise the system may operate unpredictably Carefully check the operation of all screen data and host programs before using them If incorrect the system may operate unpredictably Otherwise the system may operate unpredictably Turn off the NT600S power supply when connecting or disconnecting con nectors Check that the current capacity of the equ...

Страница 13: ...ow the power is switched ON OFF the entire system may stop Follow the correct procedure when switching the power ON OFF Otherwise the system may operate unpredictably Always turn off the power at both the PC and PT before connecting the C200H interface cable Otherwise the system may operate unpredictably Switch off the power to the NT600S and PC before disconnecting connecting the cable Set so tha...

Страница 14: ... ...

Страница 15: ...ions of the NT600S 2 1 Role and Operation of NT600S 2 2 1 1 Operations of NT600S 3 2 2 Functions of NT600S 4 2 2 1 Features 4 2 2 2 Principal Functions of NT600S 6 2 2 3 Comparison between NT600S and NT600M 7 2 2 4 Differences Between Existing Models and NT600S ST121 ST211 EV3 8 2 2 5 Displays 9 2 3 System Configuration 10 2 4 Direct Connection Function 13 2 4 1 What is the NT Link 1 N 14 2 4 2 C2...

Страница 16: ... and equipment Monitoring operating status etc Production Control 1994 1 25 Today s target NT20M NT600M 54 5 441 units Product Current Production achieved 305 units 560 units 275 units 63 0 Messages The NT600S warns of system or equipment failures and prompts the appropriate remedial action Assembly line B is defective Alarm Positioning pin Panel Switch Functions Setting touch switches on the NT60...

Страница 17: ...e C200H direct communica tion function or RS 232C OMRON s PC Host link NT link C200H direct communication RS 232C PC Host Sends Data to a PC Data input through a touch panel can be sent to a PC ON OFF information numeric data etc Touch panel PC Screen Data The screen data to be displayed on the NT600S can be created by a computer by using support tools Connect the NT600S to a PC AT with an RS 232C...

Страница 18: ...ited to the FA Environment Easy to read screen even in direct sunlight Two types of panel are available the STN LCD panel with backlight and the am ber EL display panel Its backlight unit and battery can be replaced at the operation site Waterproofed to a standard equivalent to IP65 and NEMA 4 Wide angle of visibility 50 to left and 40 to right 640 dots 400 dots POWER RUN 1 1 and 1 N Communication...

Страница 19: ...used if the C200H interface unit NT LB122 which must be purchased separately is mounted to the NT600S Touch Switch Operation The System Menu can be displayed by using the touch switches located in four corners of the screen Compatibility with NT600M Existing screen data user programs and support tools are compatible ...

Страница 20: ...PC Host can be displayed Functions Related to the Data Input Input by the touch switch Data can be input by simply touching the screen Numeric setting function The touch keys can be assigned with numeric values so that the numeric values can be input at the operation site and sent to the PC Other Functions Buzzer A built in buzzer can be used Communications with a PC Host The NT600S can be connect...

Страница 21: ...21 None ST211 Front side Expanded I O unit Expanded not possible Possible with DN type Waterproof performance NEMA4 Conforms to IP52F Visibility in direct sunlight Good ST121 None ST211 Barely visible Power supply 24 VDC more than 15 W ST121 B 24 VDC more than 25 W ST211 B 100 200 VAC Allowable momentary power interruption time Not guaranteed 5 msec System ROM Built in 512 KB not replaceable Syste...

Страница 22: ...e following additional functions in comparison with Ver 4 Thumbwheel type setting possible with the numeral setting function Upper and lower limit check can be set with the numeral setting function The type of operation alternate set reset can be selected for touch switch in put notification Indirect specification possible for numeral display and character string display functions ...

Страница 23: ...al memory tables Numbers stored in the numeral memory table are displayed The display numbers can be changed by changing the data stored in the numeral table Hexadecimal values can also be displayed Lamps Lamps indicate the operating status They are controlled by the PC Host and can be lit reversed or made flash alternates normal with reversed displays Touch Switches Touch switches can be set anyw...

Страница 24: ... use the NTM support tool Ver 4 2 However some restric tions apply when the NTM support tool is used Refer to 4 8 5 Setting the Sup port Tool Mode page 99 and Appendix G page 277 When using the Host Link NT Link 1 1 Function Use an RS 232C cable for connection to the PC Host OMRON s PC Controls NT600S as required while controlling machines and monitoring the production line With host link C series...

Страница 25: ...onitoring etc C200HX HG HE can be used RS 232C cable max length 2 m RS 232C RS 422 converter unit type NT AL001 RS 422A 485 cable 1 RS 232C RS 422 converter unit type NT AL001 RS 232C RS 422 converter unit type NT AL001 RS 422A 485 cable 1 RS 232C cable max length 2 m 1 Total cable length 500 2 For connection to an NT600S ST121 B V a separate power supply is required RS 232C cable max length 2 m N...

Страница 26: ...200HX HG HE NT600S In addition to applications such as monitoring production lines and displaying messages such as instructions transmitted to the workplace also notifies the ON OFF status of switches and numeral input to the PC Support tool Personal computer support tool Connected to the NT600S when necessary to transmit created screens to the NT600S and to set NT600S settings Personal computer I...

Страница 27: ...area in the PC and to write it to the memory table in the NT600S Also the data input on the NT600S can be written to the PC s memory area The NT600S screen status can be switched according to the PC s memory area and the NT600S s status data can be written to the PC s memory area NT600S PC DM area Internal relay area Auxiliary relay area Timer counter Features of the Direct Connection Function The...

Страница 28: ...cations for example the allocation of a lamp However since data is written to the DM area in word units it is not possible to use the other bits of words to which touch switches have been allocated for other applications in the case of this area Can be used even while the PC is in the run mode When using a host link the NT600S switches from the run mode to the monitor mode With NT link 1 N up to e...

Страница 29: ...s that the un used bits of words allocated to touch switches can be used for other applications for example lamp allocations The C200H direct communication function is compatible with the host link and NT link functions This means that NT600S screen data and PC programs handled with the host link and NT link functions can also be used with the C200H direct communication function as they are In a s...

Страница 30: ...touch switches Display instructions confirmation of display status setting of input prohibition etc System control Buzzer ON OFF ON OFF of backlight or EL display and other NT600S status Notifying from the NT600S to a PC Data in the NT600S is sent to a PC when a touch switch is pressed The following types of data are sent to a PC NT600S status Touch switch status Numeric values input by the numera...

Страница 31: ... on the screen the value on the screen will also change Monitoring of words can also be made easily Reading and writing are executed so that the contents of allocated words are always the same as those of the numeral memory tables Character string memory table Allocation destination Word Character string memory table 1 Allocated word number 3ch First word DM0100 NT600S PC a b c d e f Allocate char...

Страница 32: ...ch setting Memory table Copy setting PT status control bits NT600S PC Functions of the PT Status Notify Area NT600S to PC The PT status notify area is used to notify the changes of the NT600S status When a change is made in the NT600S status the change is written to this area in the PC By reading the data from the area the NT600S status can be checked Example of the PT status notify area applicati...

Страница 33: ... as well as to notify information Screen display data writing data inquiries etc Notification of the NT600S operation contents to the Host Terminal commands Terminal commands are used to use the NT600S as a display terminal of the Host When the NT600S is used as a display terminal it can display characters and fig ures in accordance with instructions given by the Host independently of the screens ...

Страница 34: ...operation panel page 27 Connect the power supply page 28 Connect to the PC Host link page 31 NT link 1 1 page 43 NT link 1 N page 47 C200H direct commu nication page 56 RS 232C page 63 Check the settings and communications Transfer the screen data page 79 Install support tools to the computer refer to Section 4 and the manuals for the support tools Create the screens Start operation Host Check and...

Страница 35: ...E Installation Guide W302 E1 SYSMAC C200HX HG HE Operation Manual W303 E1 SYSMAC C1000H C2000H Operation Manual W140 E1 SYSMAC CQM1 Operation Manual W226 E1 SYSMAC CQM1 CPM1 Programming Manual W228 E1 SYSMAC CV500 CV1000 CV2000 Operation Manual Ladder For a PC of the CVM1 series refer to the SYSMAC CV500 CV1000 CV2000 User s Manual W202 E1 Peripheral tools SYSMAC C series and CVM1 PCs SYSMAC Suppo...

Страница 36: ... ...

Страница 37: ...onnection to a PC by the Host Link 31 3 4 1 Compatible PCs 31 3 4 2 Connecting the NT600S 32 3 4 3 PC Switch Settings 34 3 5 Connection to a PC by the NT Link 1 1 43 3 5 1 Compatible PCs 43 3 5 2 Connecting the NT600S 44 3 5 3 PC Switch Settings 45 3 6 Connection to a PC by the NT Link 1 N 47 3 6 1 Compatible PCs 47 3 6 2 Connecting the NT600S Units 47 3 6 3 PC Switch Settings 55 3 7 Connecting to...

Страница 38: ...e product may malfunction if it is damaged 3 1 1 Description of Parts Front View RUN LED Lit when the unit is in RUN mode Flashes orange when the battery voltage is low POWER LED Lit when the power is supplied Display An STN LCD screen with a backlight or an EL screen The whole area of the screen is a touch panel which works as an input device POWER RUN Battery Normal Battery Abnormal RUN mode Lit...

Страница 39: ... 3 grounding to prevent malfunction due to noise and electric shock Reset switch SW1 Initializes the NT600S statuses Note that for the image data memory and the memory switch the status before the initialization is retained Host I F tool connector Connect the cable from a PC Host or support tool here Power input terminals Connect the power to the NT600S at these terminals 24VDC Host interface unit...

Страница 40: ... the System Menu will be automatically displayed However RUN Mode cannot be entered OFF The System Menu can be displayed SW2 4 SW Not used SW2 7 ON OFF This switch must be set to the OFF position SW2 8 Low battery voltage detection effective ineffective ON Low battery voltage is detected OFF Low battery voltage is not detected indicates factory setting In addition to the DIP switches set also the ...

Страница 41: ...ure that no metal scraps enter the unit Otherwise the product may malfunction The thickness of applicable operation panel is 1 6 mm to 4 8 mm All fittings must be tightened uniformly to a torque of 0 5 to 0 6 N m in order to ensure water and dust resistance The panel must not be soiled or warped and must be able to support an installation that will remain secure and strong 1 Open a hole shown belo...

Страница 42: ...00S must be started up be fore the host For details refer to Switching the Power ON OFF When Using C200H Direct page 62 When not using C200H direct communication there are no restrictions on the order in which power supplies are switched ON and OFF Noise prevention The NT600S has a noise preventive feature against the power supply line noise To further reduce noise connect a noise filter to the po...

Страница 43: ...se and to prevent electric shock carry out class 3 grounding grounding resistance of 100 or less using a spe cial purpose grounding cable wire of at least 2 mm2 Grounding wire length should be less than 20 m Note that if grounding wire is used in common with other equipment or if it is con nected to a beam of a building for example the NT600S might be adversely af fected by this grounding Other eq...

Страница 44: ...puter and the Host that are used to run the support tool at the same time Connect a computer only for transferring the screen data Communication conditions Communication conditions are set when a support tool is started It is impossible to connect a computer and a PC Host at the same time to the NT600S Connect a computer only to transfer the screen data To make a connector cable refer to Appendix ...

Страница 45: ...Built in Host Link Function CPU Units Connectable Using an Connectable to PC Series Host Link Unit CPU Unit CPU Units Connectable Using an Expansion Communication Board Connectable to C20H C28H C40H C60H C H C120 LK201 V1 C120 C200H C500 F C1000H C2000 H C200H LK201 C200H C200H LK201 V1 C200HS CPU21 E C200HS CPU23 E C200HS CPU31 E C200HS CPU33 E C200HS C200H LK201 V1 C200HE CPU42 E C200HE CPU32 E ...

Страница 46: ...ector cable refer to Appendix E Method for Making the Cable for Connection to the PC Host page 264 After connecting a communication cable always secure it with the screws Otherwise the cable may disconnect causing operation to fail The cable s tensile load is 30 N Do not subject it to loads greater than this Otherwise a discontinuity may occur causing operation to fail Connecting to a PC with a 25...

Страница 47: ...nnector type To connect to communication port 1 This is a 25 pin RS 232C connector Use a connector cable with a 25 pin con nector on one end and a 9 pin connector on the other end NT600S side To connect to communication port 2 This is a 9 pin RS 232C RS 422A connector Use a connector cable with a 9 pin connector on both ends Set the I O port selector switch to the RS 232C side upper side to use th...

Страница 48: ... RS 232C RS 422A converter unit page 275 of the appendix 3 4 3 PC Switch Settings When the NT600S and PC are connected to each other set the conditions at the PC host link unit or the CPU as given in the table below The following is a general description of switch settings Refer to the manual for respective units for the details of the switch settings Item Switch Setting I O port RS 232C Baud rate...

Страница 49: ... values or symbols in the setting value window agree with the following Unit SW1 SW2 Set these switches to 0 Instruction level parity and transfer code SW4 Set this switch to 2 Baud rate SW3 Set this switch to 5 to select 9600 bps Set this switch to 6 to select 19200 bps 5 2 Setting the rear switches 1 to 1 1 to N selection DIP switch Set 3 to ON CTS selection selector switch Set this always to 0V...

Страница 50: ...aud rate DIP SW2 1 to SW2 4 Set these switches to 1010 to select 9600 bps Set these switches to 0010 to select 19200 bps 1 to 1 1 to N selection DIP SW2 6 Set SW2 6 to 0 1 to N Instruction level DIP SW2 7 SW2 8 Set these switches to 1 Levels 1 2 and 3 are enabled CTS selection selector switch Set this always to 0V ON I Oport RS 422A RS 232C Synchronization Internal External Termination resistance ...

Страница 51: ...r switch Set this to Internal Baud rate DIP SW2 1 to SW2 4 Set these switches to 1010 to select 9600 bps Set these switches to 0010 to select 19200 bps 1 to 1 1 to N selection DIP SW2 6 Set SW2 6 to 0 1 to N Instruction level DIP SW2 7 SW2 8 Set these switches to 1 Levels 1 2 and 3 are enabled CTS selection selector switch Set this always to 0V ON 5V supply ON OFF Synchronization Internal External...

Страница 52: ...FF 0 Parity is fixed at Even Parity Transfer code is fixed at ASCII 7 data bits and 2 stop bits Baud rate DIP SW2 1 to SW2 4 Set these switches to 1010 to select 9600 bps Set these switches to 0010 to select 19200 bps 1 to 1 1 to N selection DIP SW2 6 Set SW2 6 to 0 1 to N Instruction level DIP SW2 7 SW2 8 Set these switches to 1 Levels 1 2 and 3 are enabled CTS selection DIP SW3 1 and SW3 2 Set S...

Страница 53: ...1 CV Series Support Software Operation Manual Details W196 E1 PC system setting DIP SW1 Set SW1 to OFF Communication is performed in accordance with the values set in the PC CPU special I O unit system settings The initial values in the system settings are as follows Unit SW3 and SW4 Set these switches to 0 I O port selection selector switch Set this to RS 232C CTS selection DIP SW2 and SW3 Set SW...

Страница 54: ...series CV500 CPU01 EV1 CV1000 CPU01 EV1 CV2000 CPU01 EV1 CVM1 CPU01 EV1 CVM1 CPU11 EV1 CVM1 CPU11 EV2 CVM1 CPU21 EV1 Only CVM1 CV series CPU units designated EV1 or higher can be con nected When connecting to a CVM1 CV series CPU set the switches as given be low Setting the front switches System setting DIP SW4 To effect the existing DIP switch settings set SW4 to ON To effect the existing PC syst...

Страница 55: ...the switch settings so as to enable the PC system set tings For the details of the operation with the PC system setting area refer to the SYSMAC CQM1 Reference Manual W228 E1 Switch settings C200HS C200HX HG HE CQM1 RS 232C port communication condition settings Set DIP switch 5 to OFF right side to enable the PC system settings CPU unit DIP switch settings Switch settings CPM1 Set the mode setting...

Страница 56: ...annel Writing Value Settings DM6550 0001 Host link mode Set the conditions with the contents of DM DM6551 0303 Data length 7 bits 2 stop bits even parity baud rate 9600 bps DM6551 0304 Data length 7 bits 2 stop bits even parity baud rate 19200 bps DM6553 0000 Unit No 0 When using CPM1 Channel Writing Value Settings DM6650 0001 Host link mode Set the conditions with the contents of DM DM6651 0303 D...

Страница 57: ...Check the model and series of the PC against the type of host link unit before mak ing the connections The compatible PCs are listed in the table below PC Series CPU Unit CPU Units Connectable Using an Expansion Communication Board Connectable to CQM1 CPU41 E CQM1 CPU42 E CQM1 CPU43 E CQM1 CPU44 E CQM1 C200HS CPU21 E C200HS CPU23 E C200HS CPU31 E C200HS CPU33 E C200HS C series C200HE CPU42 E C200H...

Страница 58: ...ect the NT600S to a PC with a 9 pin connector CPU unit SYSMAC C series PC CVM1 CV series PC Host I F connector RS 232C 9 pin type 9 pin connector RS 232C connector cable 9 pin connector NT600S The following are the recommended cables manufactured by OMRON Connector Specification Model Cable Length 9pin 9pin XW2Z 200T 2 m 9pin 9pin XW2Z 500T 5 m If a Cable Longer Than 5 m is Required If a cable lon...

Страница 59: ...h settings so as to enable the PC system set tings For the details of the operation with the PC system setting area refer to the SYSMAC CQM1 Reference Manual W228 E1 Switch setting C200HS C200HX HG HE CQM1 RS 232C port communication condition settings Set DIP switch 5 to OFF right side to enable the PC system settings CPU unit DIP switch settings PC system setting area settings C200HX HG HE CPM1 C...

Страница 60: ...V When connecting to a CVM1 CV series EV CPU set the switches as given below I O port selection selector switch Set this to RS 232C NT link setting DIP SW3 Set SW3 to ON I O port selector switch RS 232C RS 422A Set SW3 to ON right ...

Страница 61: ...nnectable Using an Expansion Communication Board Connectable to C200HE CPU42 E C200HE CPU32 E C200HE CPU42 E C200HE C series C200HG CPU43 E C200HG CPU63 E C200HG CPU33 E C200HG CPU43 E C200HG CPU53 E C200HG CPU63 E C200HG C200HX CPU44 E C200HX CPU64 E C200HX CPU34 E C200HX CPU44 E C200HX CPU54 E C200HX CPU64 E C200HX 3 6 2 Connecting the NT600S Units Referring to the illustrations below and using ...

Страница 62: ...ength 500 m 2 For connection to an NT600S ST121 B EV3 a separate power supply is required 5V 2 150mA 5V 2 150mA Maximum Number of NT600Ss Connectable to One Port The maximum number of NT600S units that can be connected to the RS 232C port built in the CPU and the A and B ports in the communication board is indi cated below C200HE Up to 4 NT600S units per port unit Nos 0 to 3 C200HG C200HX Up to 8 ...

Страница 63: ...ction Block Pin No Signal Name Abbreviation Input Output 8 Request to send CSA 7 Request to send CSB 6 Receive data RDA 5 Receive data RDB 4 Send data SDA 3 Send data SDB 2 Signal ground SG GND 1 Functional ground The CSA and CSB signals are for special applications Converter Unit Terminal Screws and Crimp Terminals The terminal screws are M3 screws Use M3 size crimp terminals Tighten the ter mina...

Страница 64: ...verter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 RS 422A cable RS 422A cable RS 422A cable RS 422A cable RS 232C cable max length 2 m RS 232C cable max length 2 m RS 232C cable max length 2 m RS 232C cable max length 2 m NT600S NT600S NT600S NT600S Total cable length 500 m RS 232C Cable Wiring NT600S ST211 B EV 2 3 4 5 6 9 Pin No A...

Страница 65: ...t the PC side 3 4 5 6 Pin No Abbrev SDB SDA RDB RDA RS 422A terminal block Shielding wire NT AL001 NT AL001 RS 422A terminal block Pin No Abbrev 1 3 4 5 6 SDB SDA RDB RDA 1 Functional ground Functional ground RS 422A connection at the PC side Abbrev SDA SDB RDA RDB RS 422A interface Shielding wire PC NT AL001 RS 422A terminal block Pin No Abbrev 1 3 4 5 6 SDB SDA RDB RDA Functional ground Connecto...

Страница 66: ...x length 2 m RS 232C cable max length 2 m RS 232C cable max length 2 m RS 232C cable max length 2 m NT600S NT600S NT600S NT600S Total cable length 500m RS 232C RS 422A converter unit type NT AL001 RS 232C Cable Wiring Same as for an RS 422A connection Refer to RS 422A connection page 50 RS 485 Cable Wiring NT AL001 to NT AL001 3 4 5 6 Pin No Abbrev SDB SDA RDB RDA RS 422A terminal block Shielding ...

Страница 67: ...verter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 Total cable length 500 m RS 422A cable RS 232C cable max 2 m RS 232C cable max 2 m RS 232C cable max 2 m RS 422A cable NT600S NT600S NT600S Termination RS 485 connection RS 232C at the PC side C200HX HG HE RS 232C cable max 2 m RS 232C RS 422A converter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 RS 232C RS ...

Страница 68: ... max 2 m RS 232C cable max 2 m RS 422A cable NT600S NT600S NT600S Communication board Termination Termination RS 485 connection RS 485 at the PC side C200HX HG HE RS 232C RS 422A converter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 RS 232C RS 422A converter unit type NT AL001 Total cable length 500 m RS 485 cable RS 232C cable max 2 m RS 232C cable max 2 m RS 232C cable max 2 ...

Страница 69: ...for setting the PC system area refer to the SYSMAC C200HX HG HE Installation Guide W302 E1 PC system setting area setting With C200HX HG HE the setting area differs according to the standard port of the CPU module used for the connection or the port of the expansion communication board Port Channel Writing Value Settings C200HX HG HE RS 232C port DM6645 Use NT link 1 N highest unit No C200HX HG HE...

Страница 70: ... C200H direct communica tion are listed below CPU Unit Model Name C20H C28H C40H C60H C H C200H CPU01 E C200H CPU03 E C200H CPU11 E C200H C200H CPU21 E C200H C200H CPU23 E C200H CPU31 E C200HS CPU01 E C200HS CPU03 E C200HS CPU21 E C200HS C200HS CPU23 E C200HS C200HS CPU31 E C200HS CPU33 E C200HE CPU11 E C200HE CPU32 E C200HE C200HE CPU42 E C200HG CPU33 E C200HG CPU43 E C200HG C200HG CPU53 E C200HG...

Страница 71: ...he PC is connected here When the C200H interface unit is mounted or removed from the NT600S the memory switches are initialized Mounting and Setting the C200H Interface Unit This section explains how to mount the C200H interface unit on the NT600S and how to set the DIP switches Mounting the Unit to the NT600S Mount the C200H interface unit by inserting it fully home so that there is no clear ance...

Страница 72: ...f C200H Make sure that the machine number to be allo cated is unique Switch cover The DIP switches are located under the switch cover on the front of the interface unit SW1 SW2 SW3 When using C200H HS or C200HX HG HE the words corresponding to the channel numbers indicated below are occupied for each unit number set Howev er since the NT600S uses the allocated bits and words for processing it does...

Страница 73: ...le length L C200H CN311 30cm NT20M CNP711 C200H CN711 70cm For connecting C200H HS HE HG HX NT20M CNP221 C200H CN221 2m HS HE HG HX NT20M CNP521 C200H CN521 5m NT20M CNP131 C200H CN131 10m C20H CN312 30cm For connecting C H NT20M CNP712 C20H CN712 70cm For connecting C H NT20M CNP222 C20H CN222 2m In the case of NT20M CNP models the connector at the C200H interface side is a compact one The combin...

Страница 74: ...ction to two I O extension units is not possible Connection to remote I O slave units is not possible The C200H interface unit only has one interface connector It is not possible to connect a C200H interface unit between a CPU unit and an I O extension unit It must be connected as the final element in the system CPU unit I O extension unit Max 1 unit Rear face of NT600S C200H I F unit I O extensio...

Страница 75: ... final element in the system CPU unit I O unit Max 2 units Rear face of NT600S C200H I F unit I O extension cable C20M CNP 2 C20H CN 2 I O connection cable C20H CN 2 I O unit I O connection cable C20H CN 2 When making a connection to a C H a noise filter must be installed 1 Insert the noise filter in the power supply line of the C H 2 Make the distance between the noise filter and the C H as short...

Страница 76: ... system reset disabling PC Host operation If the power to the NT600S is then switched ON Connecting to Host will be displayed on the NT600S screen for approximately one second and then normal operation will commence If the I O connecting cable is disconnected during system operation an I O bus error will occur at the PC Host side and operation will stop If this happens con nect the I O connecting ...

Страница 77: ...tion Conditions page 89 3 8 1 Host Computer Communication Settings Set the host communication conditions according to the following table Item Setting Baud rate Set to the same baud rate as the NT600S 2400 4800 9600 19200 Data bits 7 bits 8 bits Stop bits 1 bit 2 bits Parity Even Odd None Flow control RS CS control XON XOFF control None Set the same communication conditions at the NT600S and Host ...

Страница 78: ...nector of the host to connect the NT600S and the host In the example shown here the cable connects the 9 pin connector of the NT600S and 25 pin connector of the host If the host has a 9 pin RS 232C connector use an RS 232C cable with 9 pin connectors at both ends NT600S 25 pin connector Host Interface connector RS 232C 9 pin type 9 pin connector RS 232C cable Turn off the NT600S power supply when ...

Страница 79: ...P Switch Forced Initialization 74 4 5 Registering the Screen Data 79 4 6 Setting the Conditions of Communications with the PC Host by Using the Memory Switches 83 4 6 1 Selecting the Host Communication Method 85 4 6 2 Baud Rate Selection Host Link Only 86 4 6 3 Setting Unit Numbers NT Link 1 N Only 87 4 6 4 Setting the RS 232C Communication Conditions 89 4 6 5 Selecting the Automatic Reset Functio...

Страница 80: ...wer to the NT600S When no screen data has been registered the SYSTEM MENU will be displayed If the NT600S enters the RUN mode press ap propriate touch switches to display the System Menu Initialize Memory page 72 Select a System Menu and initialize the NT600S unit memory Transfer the Screen Data page 79 Connect a support tool to the NT600S and transfer the screen data from the support tool to the ...

Страница 81: ...he DIP switch settings page 26 4 2 1 Changing the System Settings etc Follow the procedure below to change the system settings or screen data con tents Procedure 1 Turn ON the power to the NT600S The NT600S will enter the RUN mode and the start up screen will be dis played The start up screen varies according to registered screen data 2 Press appropriate touch switches to display the System Menu a...

Страница 82: ...For the operations with the System Menu refer to the Operations with the System Menu page 70 RUN mode The NT600S runs in this state Controls from the PC Host are enabled and various indications and I O operations are made Transmit Mode Screen data and other data are transmitted between the NT600S and a support tool When system settings and screen data registration have been completed To change sys...

Страница 83: ...witches page 83 Display History page 110 I O CHECK MENU MEMORY INITIALIZATION MENU Quit Screen Data Memory page 72 Memory Tables page 75 Display History page 77 Memory Switches page 78 MEMORY SWITCH MENU 1 Key Press Sound page 93 Buzzer Sound page 94 Backlight OFF EL Screen OFF page 96 Comm Method page 85 Host Link Speed page 86 Automatic Reset page 90 Resume Function page 98 Communication I F CHE...

Страница 84: ...ENU Quit Transmit Mode Maintenance mode Press any two of these four corners at the same time RUN mode POWER RUN Note that the touch switches used to call the System Menu are not displayed on the screen If a touch switch displayed in a corner is pressed first the touch switch will function and the System Menu will not be displayed To successfully call the System Menu first press a corner where no t...

Страница 85: ...below Menu Item Function Quit The System Menu screen is cleared and the NT600S will return to the RUN mode Transmit Mode The Transmit Mode screen will be displayed to allow the trans mission of the screen data between the NT600S and the support tool For the transmission of the screen data refer to Section 3 5 Registering the Screen Data page 79 Maintenance Mode The Maintenance Mode menu will be di...

Страница 86: ...pted will be displayed For the error messages displayed on the screen refer to Section 7 2 Responding to Displayed Error Messages page 242 The following memory data can be initialized Image data memory Memory tables Display history Memory switch The image data memory can be initialized regardless of the setting for the resume function page 98 After initializing one type of data if it is necessary ...

Страница 87: ...les Display History MemorySwitches Initialize theScreen DataMemory Confirm Cancel Section 3 4 Initialization by using the System Menu Initialize the image data memory by following the procedure given below Select Maintenance Mode Select Memory Init Select Screen Data Memory Select Confirm The screen data memory is initialized During the initialization the Initializing message will be displayed ...

Страница 88: ...eration mode At this point nothing is displayed on the screen of the NT600S When the screen data memory initialization has been completed transfer the screen data from the support tool If the screen data cannot be initialized for any reason the message An Error Oc cur Initializing Memory is displayed 4 4 2 Initialization by Using the DIP Switch Forced Initialization Be sure to turn the power OFF b...

Страница 89: ...lize the numeral memory tables and character string memory tables in the NT600S When these tables are initialized the values are returned to those set by the support tool If a memory table is initialized in the Maintenance Mode it is initialized regardless of the setting for the resume function resume function page 98 If Effective is set for the Resume Function memory switch the initial values set...

Страница 90: ...intenance Mode it is initialized regard less of the setting for the resume function resume function page 98 Initialization of the Display History Data Memory Thedisplayhistory page110 is storedintheorderofoccurrence timeorder orthe order of frequency frequent order Since no more display history data can be stored if the memory becomes full the memory has to be initialized at regular inter vals The...

Страница 91: ...NT600S returns to the Memory Initialization Menu without initializing the memory Initialization of the Memory Switch It is possible to initialize the settings of the NT600S memory switch to the settings made before shipping Key Press Sound ON Buzzer Sound ON Screen Saver 10 min Comm Method Host Link Host Link Speed 9600 bps Automatic Reset OFF Resume Function OFF Data bit length 8 bits Stop bit le...

Страница 92: ...el Reference Section 3 4 Using the System Menu initialize the memory switch by following the procedure given below Select Maintenance Mode Select Memory Init Select Memory Switches Select Confirm The memory switch settings are initialized to the settings made before shipping While the memory switch is being initialized Initializing is displayed If Cancel is selected instead of Confirm the NT600S r...

Страница 93: ...hed on its display The screen data of one NT600S unit corresponds to the files created by using the support tool Select a file which contains the screen data to be transmitted when selecting the screen data to be transmitted to the NT600S so that the required screen data can be transmitted to the NT600S Screen data file Screen 1 Screen 2 Screen N Memory table Mark data System memory Direct connect...

Страница 94: ...600S it does not overwrite existing screen data it is written to a free area of the memory Consequently if data is transmitted frequently in screen units the free area of the memory will not be suffi cient and transfer will become impossible If this happens transmit the data in file units to bring the memory of the NT600s back to order Transmitting the Screen Data from the Support Tool To transmit...

Страница 95: ...S is made compatible with the existing NTM support tool For details on setting the Support Tool Mode refer to page 99 4 Enter the Transmit Mode by operating the menu of the NT600S as men tioned below Select Transmit Mode 5 Select a screen data to be transmitted to the NT600S in the File Selection screen of the support tool and press the Send key 6 The NT600S will display the following screen when ...

Страница 96: ...ns to be Observed During the Screen Data Transmission When any of the following or a system error occurs during the screen data trans mission the transmitted screen data will not be registered correctly to the NT600S If an error message is displayed in the System Menu and the Transmit Mode cannot be selected the screen data memory needs to be initialized The power to the NT600S is interrupted or t...

Страница 97: ...switches and called the memory switches Since the memory switches use the flash memory the stored data can be held even when the power supply is turned OFF If for any reason the set memory switch data is destroyed a message will be dis played on switching to the run mode If this happens press the Write touch switch to initialize the memory switches Setting Functions and the Memory Switch Menu The ...

Страница 98: ...et ON MEMORYSWITCHMENU 2 2 EXIT SAVE EXIT PREV PAGE PTUNITNo 7 Automatic Reset ON MEMORYSWITCHMENU 2 2 EXIT SAVE EXIT PREV PAGE Automatic Reset ON MEMORYSWITCHMENU 2 2 EXIT SAVE EXIT PREV PAGE 0 1 Section 3 6 MEMORY SWITCH MENU 2 Host Link method NT Link method 1 1 NT Link method 1 N C200H direct method ...

Страница 99: ...ting the RS 232C Communication Conditions page 89 Stop Bit Length Setting the RS 232C Communication Conditions page 89 Parity Bit Setting the RS 232C Communication Conditions page 89 Flow Control Setting the RS 232C Communication Conditions page 89 RS 232C Speed Setting the RS 232C Communication Conditions page 89 4 6 1 Selecting the Host Communication Method The NT600S can be connected to a PC Ho...

Страница 100: ...es to the next item in the sequence Host Link NT Link NT Link 1 N RS 232C When a C200H interface unit is connected the setting is fixed as C200H To set and quit the menu press the SAVE EXIT touch switch To quit without set ting press EXIT 4 6 2 Baud Rate Selection Host Link Only When using the host link the baud rate for the communication method must be set 9600 bps or 19200 bps can be selected Th...

Страница 101: ...ng option 9600 bps alternates with 19200 bps To set and quit the menu press the SAVE EXIT touch switch To quit without set ting press EXIT 4 6 3 Setting Unit Numbers NT Link 1 N Only When using NT600S with the NT link 1 N communication method set unit num bers When using NT link 1 N unit numbers are used to identify each of the multiple PTs connected to a single PC port Set a different unit number...

Страница 102: ...T NEXT PAGE Automatic Reset UNITNo ON 7 MEMORYSWITCHMENU 2 2 EXIT SAVE EXIT PREV PAGE 0 1 Section 3 6 Select Memory Switches Press the NEXT PAGE If NT link 1 N is not displayed as the communication method press Comm Method to dis play it Repeatedly pressing the UNIT No touch switch cycles through the numbers that can be set To set and quit the menu press the SAVE EXIT touch switch To quit without ...

Страница 103: ... to the host by the RS 232C method set the follow ing communication conditions Item Setting Factory Setting RS 232C Speed 2400 4800 9600 19200bps to be set to the same value as set for the Host 2400bps Data bit length 7 bits 8 bits 8 bits Stop bit length 1 bit 2 bits 1 bit Parity bit Even odd none None Flow control RS CS control XON XOFF control None None Select the required menu option from the S...

Страница 104: ... Parity Bit Changes among None Even and Odd Flow Control Changes among None RS CS and XON XOFF RS 232C Speed Changes among 2400 bps 4800 bps 9600 bps and 19200 bps To set and quit the menu press the SAVE EXIT touch switch To quit without set ting press EXIT 4 6 5 Selecting the Automatic Reset Function The Automatic Reset memory switch in MEMORY SWITCH MENU 2 selects whether or not operation is aut...

Страница 105: ...Select Memory Switches Select NEXT PAGE Each time the Automatic Re set touch switch is pressed the setting option changes from ON to OFF or from OFF to ON The menu display differs ac cording to the communication method see page 83 To set and quit the menu press the SAVE EXIT touch switch To quit without setting press EXIT OFF If a communication error has occurred corresponding error message is dis...

Страница 106: ...een registered at screen number 1 the Specified Screen Cannot Be Saved error message will be displayed For the screen number setting refer to Section 5 3 Screen Display page 124 Confirming the Communications between the NT600S and the PC Host If RS 232C communication is used confirm that communications are normally executed between the NT600S and the PC Host using the RS 232C communica tion check ...

Страница 107: ...tches which are con venient during the operation This section describes the memory switch settings related to the operation environment 4 8 1 Setting the Key Press Sound Whether or not the key press sound is given when the NT600S touch switch is pressed can be set with the memory switch The factory setting has been set to give the key press sound when the touch key is pressed Set the key press sou...

Страница 108: ...attribute with the support tool When creating the screen data by using the support tool set buzzer sounding as a screen attribute so that the buzzer will sound When a screen for which this attribute has been set is displayed the NT600S buzzer sounds If the control by the host and the display of the screen in which the buzzer attribute has been set are executed simultaneously the priority is given ...

Страница 109: ...als If both the continuous buzzer and the intermittent buzzer are instructed by the Host the continuous buzzer will sound Setting the Buzzer Use the memory switches to set whether or not the buzzer sounds when the buzz er sound has been instructed by the Host or with a screen attribute or when an error has occurred The factory setting has been made at ON so that the buzzer will sound when a comman...

Страница 110: ...e kept displayed for a long period What is meant by afterimage is that previously displayed screen con tents are not cleared and are left on the screen Turning ON the Backlight Redisplaying the Turned OFF Screen When a touch switch on the NT600S is pressed or when a screen is switched or redisplayed by the host after the backlight or EL screen has been switched OFF by the backlight OFF or EL scree...

Страница 111: ... effective and the same screen will therefore remain displayed indefinitely even if no op eration is performed When 10 min is set the backlight or the EL screen will be turned off when no operation has been performed for 10 minutes When 1 hour is set the backlight or the EL screen will be turned off when no operation has been performed for 1 hour Do not press touch switches carelessly while the ba...

Страница 112: ...tarting the operation next using the values stored to the memory table before the switching off of the power The memory table is always initialized disregarding of the ON or OFF setting of the resume function if the memory table is initialized using the Memory Init of the MAINTENANCE MENU For the procedure for initializing the memory table refer to Initialization of the Memory Tables page 75 The r...

Страница 113: ...nitial settings is written from the support tool the initial settings are updated but the memory tables themselves retain their original contents To initialize with new initial settings carry out memory table initialization page 75 4 8 5 Setting the Support Tool Mode By setting the Support Tool Mode to NT600M the NT600S can be used in the same way as the existing NT600M model and is made compatibl...

Страница 114: ...ting from the system menu make the following menu selections to set the Support Tool Mode Select Maintenance Mode Select Memory Switches Each time the Support Tool Mode touch switch is pressed the setting option changes from NT600S to NT600M or from NT600M to NT600S To set and quit the menu press the SAVE EXIT touch switch To quit without setting press EXIT When NT600M is set the NT600M compatible...

Страница 115: ...4 9 System Maintenance The NT600S has the self maintenance functions such as I O check and setting status check 4 9 1 I O Check The I O operations for the following items of the NT600S are checked by the I O check function LED Buzzer Touch Switch LCD EL Backlight Communication I F DIP Switch Checking the LED Check the LED by using the menu operation from the System Menu as mentioned below Select M...

Страница 116: ...tch The I O Check Menu will be redisplayed Checking the Buzzer Check the NT600S buzzer by using the menu operation from the System Menu as mentioned below Select Maintenance Mode Select I O Check Select Buzzer If the buzzer function is normal the continuous buzzer sound will be made To stop the buzzer press EXIT in the buzzer check screen Though memory switch setting for the buzzer has been made f...

Страница 117: ...dots x 49dots cm will be displayed EXIT switch to exit the touch switch check menu The touch switch is normal if it is highlighted while it is pressed Press a touch switch on the screen If the touch switch is highlighted while it is pressed the touch switch is normally functioning When the check is finished press the EXIT touch switch The I O check menu will be redisplayed If memory switch setting...

Страница 118: ...tion from the System Menu as mentioned below Select Maintenance Mode Select I O Check Select LCD or EL The LCD EL displays dots segments of the screen line by line beginning with the top left corner When all dots are normally displayed the I O Check Menu will be redisplayed To cancel the LCD EL indication check press any touch switch anywhere on the screen The I O Check Menu will be redisplayed Ch...

Страница 119: ...enu The EL type does not feature the backlight check function Checking the Communications with the Support Tool Host Execute a NT600S to support tool Host communication check by the menu op eration from the System Menu as mentioned below This check can be executed only for RS 232C communications In direct connection other than the C200H communications the same connector is used for the connection ...

Страница 120: ...ryInit MemorySwitches I OCHECK MENU Quit LED Buzzer Backlight T ouchSwitch LCDDisplay Communication I F DIP Switch COMMUNICATIONI FCHECK MENU Quit T ool Transmit RS 232CTransmit Section 3 9 Select Maintenance Mode Select I O Check Select Communication I F Select Tool Transmit or RS 232C Transmit Select Tool Transmit ...

Страница 121: ...switch Communication I F check menu will be redisplayed The NT600S uses one connector for connection to both the Support tool and the PC Host If it is connected to other equipment remove the connecting cable from the connector and connect the cable to the connector for the Support tool Host Then perform a communication check 4 9 2 Checking the NT600S DIP Switch Settings Display the NT600S DIP swit...

Страница 122: ...e Section 3 9 Select DIP Switch The NT600S DIP switch sta tuses are displayed To exit the DIP switch settings display press the EXIT touch switch If the DIP switch settings have been changed when the NT600S is powered reset the power to the NT600S The changes with the DIP switches become effective only after the power supply is reset 4 9 3 Checking the PT Setting Status Checking the PT setting Sta...

Страница 123: ... PTUNITNo 7 EXIT PTSETTINGSTATUS Communication Method C200H PTControl Area DM0010 PTNotification Area DM0020 Automatic Reset OFF ResumeFunction OFF UNITNo 9 EXIT PTSETTINGSTATUS Communication Method RS 232C Automatic Reset ON ResumeFunction ON DataBit Length 7bits StopBit Length 1bit Parity Bit Even FlowControl XON XOFF RS 232CSpeed 2400bps EXIT Section 3 9 Select PT Setting Status Host link NT li...

Страница 124: ...itialization command from the Host page 76 or by selecting the Screen Data Memory initialization menu in the Maintenance Mode page 72 If the memory becomes full of history data the history data for new occur rences cannot be recorded 3 Executing the display history recording If a screen for which the display history recording attribute has been set is dis played during operation the display histor...

Страница 125: ...he display history data memory either by sending the display history data memory initialization com mand from the Host page 76 or selecting Screen Data Memory initialization menu in the Maintenance Mode page 72 If the memory becomes full of history data the history data for new occurrences cannot be recorded Display the recorded display history using the following menu operation starting from the ...

Страница 126: ...lay history is displayed in the order the screens were dis played Up to 40 items of recorded data are displayed in one screen If the recorded data cannot be displayed in one screen it is possible to scroll the screen by pressing the NEXT or PREV touch switch If there is no display history recorded the following message is displayed Display History not Found Pressing the EXIT touch switch causes th...

Страница 127: ...lassification of Screens 124 5 3 2 Screen Attributes 126 5 4 Memory Tables 128 5 4 1 Character String Memory Table 128 5 4 2 Numeral Memory Table 129 5 5 Bar Graphs 131 5 5 1 Bar Graph Functions 131 5 6 Lamps 135 5 6 1 Lamp Functions 135 5 7 Touch Switches 138 5 7 1 Functions of Touch Switches 139 5 7 2 Standalone Function 141 5 7 3 System Key Functions 142 5 8 Numeral Setting 143 5 8 1 Function o...

Страница 128: ...en data and the screen data creation procedure For the details of the support tool and screen data creation refer to the NT series Support Tool Operation Manual V028 E1 01 5 1 1 Setting the Support Tool for Use with the NT600S To create the screen data for the NT600S make settings with the support tool for use with the NT600S Select Tool Settings ...

Страница 129: ...creen data used with one NT600S to one file Screen data can be created by one of the following three methods creating a new file editing an existing file reading and editing selected screens from an existing file Screen Data Creation Procedure The following gives the basic screen data creation procedure Required settings and reference pages are given for each step of the procedure Select Tool Sett...

Страница 130: ...tion Select a screen number to edit in the selected file in the Screen List screen To read the screen data from other file press the F5 Read function key When using host link NT link C200H direct communication set the direct connec tion information before selecting the screen number While in the Screen List screen press the F10 Next page key and then the F4 Direct key to display the Direct Connect...

Страница 131: ...he screen Numeral display Set numbers in the numeral memory table Numeral Memory Table page129 Character string display Set numbers in the character string memory table Character String Memory Table page 128 Lamp Host link NT link C200H direct Specify allocated bits RS 232C Specify lamp address Section 4 6 Lamps page 135 Touch switch Host link NT link C200H direct Specify allocated bits for contro...

Страница 132: ...f the screen number to be displayed when the NT600S is booted Only effective when using RS 232C Transmitting Screen Data to the NT600S Transmit the screen data created by using the support tool to the NT600S screen data memory Connect the NT600S to the support tool and set the NT600S to Transmit Mode Then press the F6 Transmit key in the File List screen to transmit the created screen data to the ...

Страница 133: ...eration procedure using Host NT link or C200H direct such as screen switching refer to Section 4 3 Screen Display page 124 For actual operations such as displaying the specified screen using RS 232C re fer to Section 6 2 Commands Sent by the Host page 207 Composition of the Screen The NT600S screen is composed of horizontal 640 dots x vertical 400 dots Each dot is set by the combination of the X h...

Страница 134: ...nd from a Host character attrib utes are displayed in accordance with the enlarged size which is obtained by executing the command and the display attribute Types and Attributes of Characters and Figures The following types of characters can be input by using the support tool and be displayed during operation Character Type Dots vertical x horizontal Character Set Maximum Number of Characters Disp...

Страница 135: ... scale specifying command from a Host Reverse and flashing display Reverse display The display brightness of the character and the background is reversed comparing with the normal display Flashing display Characters are displayed as they flash The normal display alternates with no display Reverse and flashing display The reverse display alternates with the normal display Types and Attributes of th...

Страница 136: ...2C communication by sending and receiving commands via anRS 232C interface the following functions of the NT600S can be utilized from various types of host Control and notifications of display elements Control and notification of NT600S statuses Memory table operations Display deletion of characters and graphics For details on the actual operations involved refer to Section 6 Using the RS 232C Int...

Страница 137: ...input by numeral setting For details on the actual method for detecting these operating statuses refer to Section 5 5 Notification of the Operating Status to the PC Determining the NT600S Operating Status page 197 and also Screen Number Response page 217 and Notifying Input to the Numeral Memory Table page 217 In order to ensure system safety be sure to periodically read the PT operating status bi...

Страница 138: ...be displayed Overlapping Screen Several normal screens can be overlapped and displayed as one screen A group of overlapped screens is called an overlapping screen Several normal screens are displayed in the order of screen numbers which have been designated to each screen and form an overlapping screen Up to eight screens can be overlapped to form one overlapping screen The base screen used for ma...

Страница 139: ...creens is called a parent screen and the registered continuous screens are called child screens The current screen number and the total number of continuous screens can be displayed in the top right corner of the screen This is called the page number dis play The page number is set when creating the screen data by using the support tool Refer to the NT series Support Tool Operation Manual V028 E1 ...

Страница 140: ...tribute This attribute will become effective to sound the buzzer in the NT600S when the screen to which this attribute has been set is displayed The buzzer sound can be set as follows No Buzzer does not sound when the screen is displayed Continuous sound Buzzer sounds continuously Intermittent sound Buzzer sounds intermittently at constant intervals The buzzer sound is set with the NT600S memory s...

Страница 141: ...to the host when a touch switch is pressed There are two types of bit input attribute in the screen attributes as indicated below Off Bit control when a touch switch is pressed is invalid The status of the touch switch is notified using its number Touch SW Bit control when a touch is pressed is valid The status of the touch switch is notified using bit information Backlight attributes NT600S ST121...

Страница 142: ...umber of the character string memory table using the numeric memory table instead of directly changing the contents of the character string memory table indirect designation For the procedure for changing the character string in the table refer to Changing Displayed Numerals or Character Strings Changing the Contents of Allocated Words page 170 172 or Write Character string Memory Table page 208 I...

Страница 143: ...lternates with the normal display 5 4 2 Numeral Memory Table The numeral memory table is an NT600S internal memory used to store the nu meral data Up to 512 numeral memory tables can be used and up to eight digits four bytes of numeral data including signs can be stored in one numeral memory table The numeral memory tables at up to 50 positions can be registered in one screen Displaying a Numeral ...

Страница 144: ...ts of the decimal fraction 0 to 7 digits Character sizes Half normal Enlarged display Double width double height x4 x9 x16 x64 The characters enlarged to the x4 scale or larg er are displayed with the outline automatically smoothed This function is called smoothing Sign display setting Decimal hexadecimal display setting Zero suppress setting Zero suppress setting The numeral data are displayed in...

Страница 145: ... to the contents of a numeral memory table Up to 50 bar graphs can be registered in one screen Reference table The numeral memory table used as the reference for the bar graph display can be set The support tool has the direct and indirect options for the reference method of the numeral memory table However the NT600S recognizes the direct method only The bar graph display cannot use hexadecimal n...

Страница 146: ...ich indicates the effective display range is displayed This frame is not displayed if Graph frame No has been set Setting the 100 value and display Set a value which corresponds to 100 for the 100 value The available value range is 0 to 99999999 max eight digits For the display whether or not the proportion percentage of the reference numeral memory table value to the 100 value is displayed in a n...

Страница 147: ...displayed in the range of 0 to 100 The end of the bar graph indicates 0 Values below 0 are indicated as 0 display 0 100 60 Differences in the bar graph display method according to the values The bar graph display method varies according to the value range 1 When the value is in the minus range The display varies as follows according to the sign display setting Sign display No Displayed as 0 Sign d...

Страница 148: ...played display 0 100 999 Graph width 8 dots When the frame is not displayed display 0 100 999 Graph width 8 dots 1 dot wide space Sign display Yes A value below 100 will be displayed in the minus direction as shown above 3 When the absolute value of the value is above 1000 The bar graph will be displayed the same as 2 above The value is displayed as follows according to the sign display setting Si...

Страница 149: ...it and flash which are registered when creating the screen data can be switched according to the ON OFF of the PC bit status Unlit Lit PC Host Lamp Attributes The following attributes can be set with the lamp Use the support tool to set the lamp attributes Shape Select from the square and circle shapes The display size can be freely se lected Square Circle Frame Select whether or not the boundary ...

Страница 150: ...e frame setting Frame is set Only the area in the frame will be lit flashing Frame is not set The area including the frame will be lit flashing Frame is set Unlit Flash Lit Area inside the frame flashes Area including the frame flashes Frame is not set Unlit Flash Lit Controlling lamps in a batch Multiple lamps can be lit or flashed in a batch by registering multiple lamp alloca tions to the same ...

Страница 151: ...e lighting of the lamp and the updating of the memory table Bear this in mind when creating the control program Example 1 Lamp lit after the memory table is updated Lamp OFF Character string memory table display area Memory table updated Lamp turned ON Lamp OFF Lamp ON The characters are displayed white on black Lamp OMRON PT PT Example 2 Memory table updated while lamp is lit Lamp OFF Character s...

Страница 152: ...nd Lamp and Touch Switch display Number Specifica tion on page 212 For details on how the statuses of touch switches are ascertained by the Host re fer to Notifying the Host that a Switch has been Pressed Determining Touch Switch Status on page 185 and Lamp and Touch Switch Display Status Enqui ry on page 212 Do not use input functions such as PT touch switches for applications where danger to hum...

Страница 153: ...iguration of the touch switches When switches A B and D are switched on at the same time switch C is also assumed to have been switched on due to the configuration of the touch switches A C B D Smallest touch switch frame 5 7 1 Functions of Touch Switches Touch switches are created using rectangular elements measuring 39 dots hori zontally by 49 dots vertically A touch switch can comprise more tha...

Страница 154: ...h OFF Switch ON Standard 3 D None If none is selected only the touch switch s guidedisplay message or nothing if there is none are displayed until a light or flash designation is sent from the PC Host or the touch switch is pressed Inverse display on input It is possible to set a touch switch so that its display will be inverted when it is pressed Lighting and flashing When using host link NT link...

Страница 155: ...when the screen data is created using the sup port tool If the touch switch is pressed during operation the screen whose number was designated will be displayed Simultaneously the PC will be notified of the screen number of the screen selected for display Screen 5 set for touch switch 1 Tonext screen Touch switch pressed once Screen 5 To set a screen number for a touch switch use Touch SW Bit spec...

Страница 156: ... and Numeric key of the support tool Allocation of System Key Functions The system key functions are allocated to touch switch numbers 227 to 230 and 255 as shown below When a touch switch with one of these numbers is displayed on the screen it has the same function as the corresponding system key System Key Key Symbol Touch Switch No System menu display MENU 227 228 229 Buzzer stop 230 ENT 255 Wh...

Страница 157: ...rocedure for numeral setting is as follows 1 Input the numerical value using touch switches numeric keys 2 The input numerical value is displayed in the numeral setting area on the screen 3 Confirm the input numerical value by pressing the ENT key it will bewritten to the numeral memory table and simultaneously notified to the PC Host Numerical values aredisplayed in the numeral setting area Input...

Страница 158: ...is used upper and lower limits can be set for input numerical values to prevent erroneous values that are outside the valid range be ing stored in the numeral memory table or notified to the PC The upper lower limit check is executed when the input numerical value has been confirmed if the value is outside the valid range the screen returns to its status before input To use the numerical value inp...

Страница 159: ...ssing the key the input value is written to the numeral memory table andsimultaneously notified to the PC 1 2 3 4 1 2 3 4 Host NT600S Thumbwheel Type Ver 5 Direct Connection Only When using an NT600S ST121 ST211 EV with Ver 5 direct connection numeri cal values are input directly at the numeral setting input field using touch switches that increment or decrement each of the digits in the display w...

Страница 160: ...f numeric key shown in the figure below system keys are used Tank A Tank B Tank C 1 2 3 4 5 6 7 8 9 0 CLR When using the NT600S with the numeral setting attribute set to system apart from the numeric keys provided by the system the touch switches allocated to system keys also have to be created system key function To en able input of hexadecimal values it is also necessary to create numeric keys A...

Страница 161: ...select Numeric key from the Touch SW Bit setting menu of the support tool then designate a touch switch number at Numeric key When a touch switch allocated as a numeric key is pressed the touch switch sta tus is not notified to the PC Consequently touch switches 227 to 255 cannot be used as ordinary touch switches Continuous screens and overlapping screens Numeral setting screens cannot be registe...

Страница 162: ... 4624 HOME Pressing the HOME key will shift the cursor to the area whose top left corner has the smallest XY coordinate sum the top left numeral setting input field in the example above Selection with the system keys When the and system keys on the touch panel are pressed the cursor moves between the numeral setting areas by following the order in which they were created using the support tool For...

Страница 163: ...int Changing the sign When there is a sign display pressing the sign key changes minus to plus or plus to minus Confirming input numerical values Always press the return key as the final step when inputting a numerical value When the return key is pressed the displayed numerical value is written to the numeral memory table and at the same time notified to the host Initial operation of input keys T...

Страница 164: ... by using the incrementing decrementing keys pro vided for each digit Numerical value specification When an incrementing decrementing key is touched the numeral at the corresponding digit is incremented or decremented by one Whenever a plus or minus key is touched the changed value is notified to the host There is no need to press the return key as is the case when using the numeric key type of nu...

Страница 165: ...alues so that n n m m or create another touch switch and write values to the host when digits are carried up or down Restrictions and Additional Settings for Thumb Wheel Type Numeral Settings There are the following restrictions and additional items to set when creating thumb wheel type numeral settings Number of input digits for positive values when there is a sign display When a sign display is ...

Страница 166: ... ...

Страница 167: ...Changing the Contents of Allocated Words Indirect Specification 172 6 2 4 Copying the Memory Table 175 6 2 5 Upgrading Bar Graphs Changing the Contents of Allocated Words 179 6 3 Lamps Touch Switches and Numeral Setting 180 6 3 1 Allocation Bits and Display of Lamps 180 6 3 2 Turning ON lit and OFF unlit the Lamps Changing the Contents of Allocated Bits 181 6 3 3 Allocated Bits and Display of Touc...

Страница 168: ...x L PC Memory Map page 291 The allocations must be made without exceeding respective area range OMRON PCs C Series PCs CVM1 CV Series PCs Symbol Allocated Allocated Word Allocated Allocated Word Symbol Area Name Allocated Bit Numeral Character String Area Name Allocated Bit Numeral Character String DM Data Memory Data Memory CH Internal Special Relay Internal Special Relay TIM Timer Timer CNT Coun...

Страница 169: ...e Display Elements by Using Allocated Bits and Words The NT600S will operate as follows in the display element control operation NT600S operation 1 The NT600S checks the allocation bits and words of the display elements and makes an inquiry to the PC 2 The PC answers the NT600S about the bit and word data 3 The NT600S changes the display status according to the bits and words ob tained from the PC...

Страница 170: ... of a memory table internally in the NT600S Set the copy type to match the type of memory table to be copied 0 Character string memory table 1 Numeral table PT status control bits refer to page 192 Turn this bit ON and OFF to control the buzzer and backlight of the NT600S Item Controlled 1 ON 0 OFF Screen display Note 1 ON OFF Processing priority registration Note 2 ON OFF Continuous buzzer ON OFF...

Страница 171: ...ap between the PT status control area and PT status notify area Otherwise the system may operate unpredictably When NT link 1 N is set the PT status control area must be set for each con nected PT Notifying the Display Elements by Using Allocated Bits and Words The NT600S will operate as follows in the display element notification operation NT600S operation The NT600S will write any changes in the...

Страница 172: ...er to page 162 The screen number displayed on the NT600S is written to this word Simultaneously the PT status screen switch strobe flag is set to ON 1 After this is notified to the PC this flag reverts to OFF 0 Checking the status of this flag will provide a simple method of checking if the NT600S display has switched Content upgrade memory table refer to page 189 The number of the numeral table i...

Страница 173: ... PT operation status 1 ON RUN 0 OFF STOP Screen switching strobe Numeral setting strobe flag Battery 1 ON LOW 0 OFF NORMAL The PT status control area PC to PT can be allocated to the following PC areas Symbol C Series PCs Allocated CVM1 CV Series PCs Allocated DM Data Memory Data Memory CH Internal Special Relay Internal Special Relay TIM Timer Timer CNT Counter Counter HR Holding Relay AR Auxilia...

Страница 174: ... Screen number 0000 screen clear no display 0001 to 01000 Since the special auxiliary relays of the CVM1 CV series PCs are allocated to the system they cannot be used for purposes other than the system use The range of respective area varies with the type of PC Refer to Appendix L PC Memory Map page 291 Procedure 1 Use the support tool to allocate the PT status control area PC to PT to the PC memo...

Страница 175: ...continuous and overlapping screens refer to the Classification of screens page 124 Example of Display Screen Switching This example operates the PC switch bit to switch the NT600S display screen Support tool settings Make the following settings with the support tool PT status control area Word 0100 PT status notify area Word 0110 Screen number to be created Screen 2 and 3 PC ladder program Create ...

Страница 176: ...hen the screen switch strobe flag has turned ON the number of the currently displayed screen on the NT600S is displayed NT600S PC Currently displayed screen PT status notify area Currently displayed screen Screen number Content upgrade memory table PT status Screen switch strobe flag Currently displayed screen and PT status words in the PT status notify area Use a 4 digit BCD binary coded decimal ...

Страница 177: ... Classification of screens page 124 Example of Reading the Number of Currently Display Screen This example gives a PC program that reads the screen number each time the screen is switched In this example the number of the previous screen is also stored Support tool settings Make the following settings with the support tool PT status notify area Word 0110 PC ladder program MOV 21 DM0100 DM0101 1121...

Страница 178: ... they are displayed Can be updated by the PC Display area where the character string memory table No 2 is allocated NT600S PC During the operation the display contents are automatically updated so that the contents of the character string memory table being displayed are the same as that of the PC word Displaying and Referencing Character String Memory Table Contents Since the character string mem...

Страница 179: ...ral memory table 20 Allocated word character string table 51 Indirect specification This specification method is a little complex but it allows the display to be changed more easily according to the circumstances In the example above if 1 were add ed to the contents of memory table 20 to give 52 the contents of memory table 52 would be displayed instead The memory tables used for display can also ...

Страница 180: ...system use 2 If the number of registration words x 2 word setting window set with the support tool is larger than the number of character digits character string display setting window the character string may be broken halfway The range of respective area varies with the type of PC Refer to Appendix L PC Memory Map page 291 Writing Numerals to the Numeral Memory Table Since numeral memory tables ...

Страница 181: ... Special relay TIM Timer Timer CNT Counter Counter HR Holding Relay AR Auxiliary Relay Auxiliary Relay LR Link Relay OK 1 word only NG Since the special auxiliary relays of the CVM1 CV series PCs are allocated to the system they cannot be used for purposes other than the system use The range of respective area varies with the type of PC Refer to Appendix L PC Memory Map page 291 6 2 1 Allocation W...

Страница 182: ...the CVM1 CV series PCs are allocated to the system they cannot be used for purposes other than the system use The range of respective area varies with the type of PC Refer to Appendix L PC Memory Map page 291 Contents of the numeral memory tables Numerals are stored in the allocated words as shown below Stored as a single word 15 to 12 11 to 8 7 to 4 3 to 0 Bit Digit 4 Digit 3 Digit 2 Digit 1 Exam...

Страница 183: ... Start 1 Decimal without sign 123456 Decimal with sign 123456 Hexadecimal F0123456 3 4 5 6 F 0 1 2 When the data contain characters A to F Start Start 1 Decimal without sign 123B56 Decimal with sign 123B56 Hexadecimal F0123B56 3 B 5 6 F 0 1 2 If the hexadecimal data A to F are stored when the decimal display has been set the alphabets are displayed If the number of display digits has been set to b...

Страница 184: ... A 41H B 42H Start A 0 4 4 4 1 4 2 4 3 E B 9 F E B ABC D EBA0H Start 3 EB9FH Start 2 C 43H Start 1 D 44H Characters with 8 bit codes 00 to 1FH are displayed on the screen as a one byte space 20H 00H is converted to 20H 6 2 2 Changing Displayed Numerals or Character Strings Changing the Contents of Allocated Words Direct Specification The following describes the procedure to change displayed numera...

Страница 185: ...ortant points when writing a character string If the character font for character strings displayed on the NT600S screen is set as half height and a normal character string is written after displaying a 2 byte code mark part of the mark will remain displayed as shown below In this case first write a 2 byte code FF20 to FF5F for which nothing is regis tered then write a normal size character string...

Страница 186: ...ases by 1 3 When bit 00001 turns ON the contents of DM0002 are incremented by 1 The value displayed on the NT600S in numeral memory table entry 2 increases by 1 6 2 3 Changing Displayed Numerals or Character Strings Changing the Contents of Allocated Words Indirect Specification When displaying numerals or character strings it is possible to change them indi rectly by specifying a numeral memory t...

Страница 187: ...specify the numeral memory table In the case of a numerical value use the numeral display function of the sup port tool to specify the numeral memory table 3 Use the table edit function of the support tool to write the actually displayed data to the memory table for display If displaying a numerical value use a nu meral memory table and if displaying a character string use a character string memor...

Страница 188: ...cification 51 Initial value of numeral memory table number 51 100 Line1 NT600S Display of character string specification of numeral memory table number 51 in indirect specification Character string memory table settings Contents Number of Character Digits 100 NT20S 6 digits 101 NT600S 6 digits 102 NT610G 6 digits 103 NT610C 6 digits no word allocation PC program Create the following PC ladder prog...

Страница 189: ... the PT status control area NT600S PC Memory table copy source Copy destination for display PT status control area Screen switch setting PTstatus control setting Copy sourcenumber Copy destination number A A A Copy memory table setting Write a memory table number etc to the copy memory table setting area in the PT status control area in the PC memory Data will be copied between the memory tables i...

Страница 190: ... Memory Map page 291 Procedure 1 Use the support tool to allocate the PT status control area PC to PT to the PC memory 2 Register the memory tables for the numerals and character strings to be dis played when creating the screen data by using the support tool To display a character string use character display and specify the charac ter string memory table by using the support tool To display nume...

Страница 191: ... only when the contents of the area are changed To repeat copying of the same copy source and same copy destination write a value other than 0 or 1 for the copy type and then write a correct value again Copying a numeral memory table If the display method or the number of registered words include discrepancies a numeral memory table may not be copied and displayed correctly Application Example of ...

Страница 192: ...ble Copy source word MOV 21 0004 09000 MOV 21 0011 2 Copy type copy destination memory table Copy destination word Copy source memory table Copy source word Error flag Error flag 101 102 101 102 Program operation 1 When an error occurs bit 09000 turns ON the NT600S displays the mes sage Error 2 When the error is cleared bit 09000 turns OFF the NT600S display mes sage reverts to Normal ...

Страница 193: ...ord only NG Since the special auxiliary relays of the CVM1 CV series PCs are allocated to the system they cannot be used for purposes other than the system use The range of respective area varies with the type of PC Refer to Appendix L PC Memory Map page 291 The bar graph display cannot use hexadecimal numbers If hexadecimal num bers are set the bar graph will not be displayed By writing a negativ...

Страница 194: ...located to the following PC areas Symbol C Series PCs Allocated CVM1 CV Series PCs Allocated DM Data memory Data memory CH Internal Special Relay Internal Special Relay TIM Timer Timer CNT Counter Counter HR Holding Relay AR Auxiliary Relay Auxiliary Relay LR Link Relay OK NG To set the data memory DM specify the word number and then the bit number 00 to 15 Since the special auxiliary relays of th...

Страница 195: ...creating the screen data by using the support tool 3 Create a PC program to turn ON OFF the lamp control bit Use the support tool to set the lamp display attributes whether the lamp is lit or flashing when the lamp control bit is turned ON Application Example to Make the Lamp Light or Flash This example gives a procedure to control the bits to move a robot arm and turning the lamps ON and OFF Supp...

Страница 196: ...p 4 UNCLAMP Lamp 5 C CLOCK CLOCK DOWN UP CLAMP UNCLAMP PC ladder program No PC ladder program is required to control the NT600S Only a program to con trol the robot arm movements is required Program operation When the ladder program to control the robot arm is executed the lamps on the NT600S screen turn ON and OFF in synchronization with the robot arm move ment For example lamp 0 lights when the ...

Страница 197: ...bit so that it can be managed Designate the area and bit number To use touch switches for notification to the PC the following settings must be made using the support tool touch switch bit setting notify bit Types of notification operation When using Ver 5 of the direct connection function the notification operation when the touch switch is pressed can be selected from the following four types wit...

Страница 198: ... pressed the touch switch itself disappears so the status OFF is notified In the case of 1 this means that the other bits in the word will also be turned OFF When using the host link or NT link with the DM area do not allocate momen tary touch switches and other types of touch switch to the same word since the notification operations are different In the case of 3 and 4 the notification operation ...

Страница 199: ... the support tool to allocate the touch switch control bits to the PC memory 2 When creating the screen data using the support tool register the touch switch for a screen 3 Create the PC program to switch the control bit of the touch switch ON and OFF Set whether a touch switch will be continuously lit or blink when its bit has been turned ON by setting the support tool touch switch display attrib...

Страница 200: ... Internal Special Relay TIM Timer Timer CNT Counter Counter HR Holding Relay AR Auxiliary Relay Auxiliary Relay LR Link Relay OK NG When making a data memory DM specification specify the bit number 00 to 15 following the word number It is not possible to allocate a momentary switch to the same word as an alter nate set reset switch Since all the CVM1 CV series special auxiliary relays are allocate...

Страница 201: ...tents of the word before display which means that the other bits are not rewritten However if the word contents are changed at the PC side they will be rewritten based on the contents before display If the screen is switched while a momentary key is being pressed the touch switch itself disappears so the status OFF is notified In the case of 1 this means that the other bits in the word will also b...

Страница 202: ...een touch switch 10 touch switch 11 Line1 Touch switch 11 RUN Touch switch 10 STOP PC program Create the following ladder program 11212 06001 05001 06000 05000 06001 06000 05001 05000 1 scan ON Touch switch 10 notify bit Stop flag touch switch 11 control bit Touch switch 10 notify bit Run flag touch switch 10 control bit Touch switch 11 notify bit Touch switch 11 notify bit ...

Страница 203: ...graded numeral memory table number the content upgrade memory table in the PT status notify area is used When numerical data is input at the NT600S this is automatically notified to the PT status notify area PT PC allocated in the PC memory as follows Notification of upgrade PT status numeral setting strobe flag turned ON 1 Upgraded numeral table number Stored in the content upgrade memory table W...

Страница 204: ...reas listed in the following table Symbol C Series PCs Allocated CVM1 CV Series PCs Allocated DM Data memory Data memory CH Internal Special Relay Internal Special Relay TIM Timer Timer CNT Counter Counter HR Holding Relay AR Auxiliary Relay Auxiliary Relay LR Link Relay OK NG Since all the CVM1 CV series special auxiliary relays are allocated to the system they cannot be used for applications not...

Страница 205: ...umeral memory table entry number 4 4 digit input 1 2 3 4 5 6 7 8 9 0 CLR PC program Create the following PC ladder program MOV 21 111 DM0105 11211 1 Notification word for content upgrade memory table Word that stores the numeral memory table number Numeral setting strobe flag Program operation 1 When the numeral setting strobe flag bit 11211 comes ON 1 the contents of CH 0111 the word where the co...

Страница 206: ... Screen display Note 1 ON OFF Processing priority registration Note 2 ON OFF Continuous buzzer ON OFF Intermittent buzzer ON OFF Backlight mode Note 3 ON Flash Note 1 When Screen display ON the back light EL display is ON and when Screen display OFF the backlight EL display is OFF Note 2 Priority registration is only valid when NT link 1 N is set Note 3 These functions cannot be used for NT600S ST...

Страница 207: ...ast will have priority By word monitoring with C200HX HG HE the unit number of the PT for which priority registration has been set can be confirmed For details on the monitoring operation at the PC side refer to the manual for the PC used Connection to RS 232C port of C200HX HG HE Channel Bit CIO265CH standard port CIO284CH t A 0 Unit No 0 Communication in progress flag ONwhen connected CIO284CH p...

Страница 208: ...controlled using the screen attributes The screen attributes are set with the support tool Buzzer attribute The setting for this attribute determines whether the buzzer is sounded or not and the type of buzzer sound if it is sounded Backlight mode bit 8 NT600S ST121 only If bit 8 is turned ON when the screen is displayed bit 15 ON the screen is made to flash using the backlight When bit 8 is turne...

Страница 209: ...pendix L PC Memory Map page 291 for more details Procedure 1 Use the support tool to allocate the PT status control area PC PT to the PC memory 2 Create a PC program to write control data to the PT status control bits of the PT status control area Control timing of PT status control bits The PT status control area PC PT is not read when the NT600S starts up It is only read and control is only exec...

Страница 210: ...ogram operation 1 The PT status control bits are set as shown below when bit 09002 turns OFF This command block is not executed when bit 09003 is ON Screen display bit 15 1 ON Continuous buzzer bit 13 1 ON The NT600S continuous buzzer sounds 2 The PT status control bits are set as shown below when bit 09003 turns OFF Screen display bit 15 1 ON Intermittent buzzer bit 12 1 ON The NT600S intermitten...

Страница 211: ...PT operating status 1 ON operating 0 OFF stopped 15 14 13 12 11 10 9 8 Bit The NT600S statuses that the PC can determine are listed below Low voltage of battery installed in NT600S battery option NT600S operating stopped status Screen switches Data input PT operating status bit 15 When the NT600S is in the RUN mode this bit is set to ON 1 In other modes and while the system menu is displayed it is...

Страница 212: ... used see Notification of Numbers to the PC page 189 6 5 2 Reading the NT600S Operating Statuses This section explains how to determine the status of the NT600S and ascertain its operating status To ascertain the operating status of the NT600S PT status is used The NT600S automatically notifies information such as the operating status to the PT status word of the PT status notify area PT PC alloca...

Страница 213: ...en to the PC when the NT600S status is changed during operation Example of Using the PT Status Notify Bit An operation example in which the NT600S status is checked by operating the PT status notify bit is explained below Setting by the support tool Perform the following setting with the support tool PT status notify area allocated word CH0110 PT error storage area allocated word DM0001 PC program...

Страница 214: ...rned OFF 0 and battery con tact 11213 is turned OFF 0 2 NT600S stop normal battery voltage is transmitted to DM0001 3 If PT operating status contact 11215 is turned ON 1 and battery contact 11213 is turned ON 1 3 NT600S running low battery voltage is trans mitted to DM0001 4 If PT operating status contact 11215 is turned ON 1 and battery contact 11213 is turned OFF 0 4 NT600S running normal batter...

Страница 215: ... 4 Table of Commands 206 7 2 Commands Sent by the Host 208 7 2 1 Displaying the Screen 208 7 2 2 Memory Tables 209 7 2 3 Lamps and Touch Switches 212 7 2 4 Controlling the NT600S Status 215 7 3 Commands Sent by the NT600S 218 7 3 1 Screen Display 218 7 3 2 Memory Table 218 7 3 3 Lamps and Touch Switches 219 7 4 Terminal Commands 222 7 4 1 Clearing the Screen 222 7 4 2 Displaying a Character String...

Страница 216: ...rogram RS 232C circuit NT600S operation OPEN command PRINT command LINE INPUT command CLOSE command Open circuit Send instruction Close circuit Send instruction Receive instruction Send instruction Open status After a circuit has been opened it can be used until it is closed again OPEN Opens the RS 232C circuit The Host communication conditions are also set Refer to 4 6 4 Setting the RS 232C Commu...

Страница 217: ...command Enquiry from Host to NT600S Host program NT600S operation Enquiry operating command Enquiry Receive command Receive command Send response command Response operating command Notification of Operation at NT600S to the Host Host program NT600S operation Receive notification Notification operating command Send notification command Operation by Terminal Commands The following describes control ...

Страница 218: ...nsmissions exceeds 5 se conds When commands are sent too frequently a buffer overflow error may occur if the NT600S cannot keep up with the command processing Control of the NT600S status by the operating commands is restricted by the NT600S memory switch settings as listed below Operating command Restriction from memory switch setting Buzzer control command ESC T Effective when buzzer turned on T...

Страница 219: ...i tion of the touch switch When this method is used if more than one touch switch is pressed at the same time the information of all the pressed touch switches 0 to 63 is reported to the Host Touch switch number method bit input not permitted setting If the touch switch status is changed the touch switch number set when the touch switch is created is sent as a 3 digit hexadecimal number If the tou...

Страница 220: ... ESC R Lamp and Touch Switch Display Status Enquiry 213 Touch Switch and Function Key Input ESC U Touch Switch Disable 214 Function Key Input ESC V Touch Switch Enable 214 System Control ESC P Screen Display Control 215 ESC T Buzzer Control 215 ESC W System Menu Display Permission 216 ESC Z PT Status Enquiry 216 ESC Initialize Display History 216 ESC _ Display Mode Control 217 Notification ESC Y S...

Страница 221: ...Character Display Attributes ESC Normal Display 223 Attributes ESC Set Inverse Display 224 ESC End Inverse Display 224 ESC Set Flashing Display 224 ESC End Flashing Display 225 Character String Display ESC Set Cursor Position 225 Display ESC 4 Specify Displayed Characters 226 Graphic Display ESC 7 Draw Polyline 226 ESC 8 Draw Circle 227 ...

Страница 222: ...reen is displayed If a screen number is specified by the Host using the following command the dis play screen is switched to the corresponding screen screen number 1 to 1000 Screen number 0 is a white screen no display Continuous screens and overlapping screens To display continuous screens or overlapping screens it is necessary to speci fy a parent screen If a child screen is specified only the s...

Страница 223: ...s refer to 5 4 Memory Tables page 128 Writing Character Strings A character string can be written to a character string memory table in the NT600S using the following command Write Character string Memory Table Format 1B ESC 42 B n1 n2 d1 d2 c1 c2 c3 cn n1n2 Character string length as a number of normal characters 2 digit hexadecimal 01 to 28H 1 to 40 d1d2 Character string memory table address of ...

Страница 224: ...stination 3 digit hexadeci mal 000 to 1FFH o to 511 n1n2n3n4 Number data 4 digit BCD or 4 digit hexadecimal Description Writes 4 digit number data decimal or hexadecimal to the specified numeral table If a 4 digit number data is written while an 8 digit numeral is displayed the lower 4 digits are updated 8 digit Write Numeral Memory Table Format 1B ESC 44 D d1 d2 n1 n2 n3 n4 d3 n6 n7 n8 n5 d1d2d3 ...

Страница 225: ...ble of the same type character string memory table to character string memory table or nu meral table to numeral memory table Operation 1 Register the memory table which contains the numerals or character string to be displayed for the screen when creating the screen data using the sup port tool In the case of a character string use the character string display mode of the support tool to specify ...

Страница 226: ...05 The commands are described below Lamp and Touch Switch Display Bit Specification Format 1B ESC 4B K m01 m02 m12 m21 m22 m31 m11 m41 m42 m32 m131 m132 CR 0D m0 m13 Specification of lamps and touch switches 2 digit hexadecimal The relationship between the lamp and touch switch number and an expression of m0 to m13 in bits is given in the following table mx1 mx2 7 6 5 4 3 2 1 0 m0 07 06 05 04 03 0...

Страница 227: ...y 1 31H Lit 2 32H Flashing inverse 3 33H All not lit n1n2n3 Lamp or touch switch address 3 digit hexadecimal 000 to 0FFH 0 to 255 Description Changes the lamp or touch switch lighting status Specify the display status as 3 all not lit to turn off all the lamps and touch switches In this case specify the lamp or touch switch number to any number in the permitted range The display attributes set wit...

Страница 228: ...sable Format 1B ESC m1 55 U m1 Switch whose input is to be disabled 0 30H Touch switches 2 32H Touch switches Description Disables touch switch and function key input and notification to the Host Use the Touch Switch Enable Command refer to 7 2 3 Touch Switch Enable to use a disabled touch switch again Disabled touch switches are also enabled when the NT600S power is turned off Touch Switch Enable...

Страница 229: ...ny point on the NT600S s screen is pressed The specified screen is displayed when the Display Specified Screen Command refer to 7 2 1 Display Specified Screen is transferred Turning the Buzzer ON OFF By using the following command it is possible to control the ON OFF status of the buzzer built into the NT600S from the Host Two buzzer modes are provided continuous beep and short intermittent beep B...

Страница 230: ...ck the voltage status of the built in NT600S battery use the following com mand The battery is optional PT Status Enquiry Format 1B ESC 5A Z Description Determines if the built in PT battery voltage is low The PT returns the PT Battery Status Response Command see 7 3 PT Battery Status Response to report the battery status Whether or not report is made is determined by the ON OFF setting of DIW SW2...

Страница 231: ...ing the following command Display Mode Control Format 1B ESC 5F _ m1 m1 Specifies the display mode 0 30H Normal display white background 1 31H Inverse display black background Description Controls the display mode of the LCD liquid crystal display screen This command is only valid for the following PTs NT600S ST121 V NT600S ST121B V ...

Страница 232: ...ommand refer to 7 2 1 Request Screen Number sent from the Host The new screen number is report to the Host with this command after the dis played screen is switch with the Stand alone functions screen switch function If the screen is switched by pressing a touch switch the screen number of the newly displayed screen is sent to the Host by executing this command 7 3 2 Memory Table Notifying Input t...

Страница 233: ...Notifying the Display Status The lit flashing status of the lamps and touch switches which are set on the screen currently displayed on the NT600S is sent to the Host by executing the following command Lamp and Touch Switch Display Status Response Format 1B ESC n1 n2 m1 53 S n3 m1 Display status m1 Display status 0 30H Not lit normal display 1 31H Lit 2 32H Flashing inverse n1n2n3 Lamp or touch sw...

Страница 234: ...tch The relationship between the touch switch number and an expression of s0 to s7 in bits is given in the following table sx1 sx2 7 6 5 4 3 2 1 0 s0 07 06 05 04 03 02 01 00 s1 15 14 13 12 11 10 09 08 s2 23 22 21 20 19 18 17 16 s3 31 30 29 28 27 26 25 24 s4 39 38 37 36 35 34 33 32 s5 47 46 45 44 43 42 41 40 s6 55 54 53 52 51 50 49 48 s7 63 62 61 60 59 58 57 56 sx1 Higher 4 bits of sx x 0 to 7 sx2 ...

Страница 235: ...which is set as a ten key switch 231 to 254 is pressed it is not reported to the Host When a touch switch which is set as a system key 227 to 230 255 is pressed it is not reported to the Host Notifying Low Battery Voltage The status of the battery in the NT600S is sent to the Host by executing the follow ing command PT Battery Status Response Format 1B ESC m2 m1 5B 0D CR m1m2 Battery voltage statu...

Страница 236: ...en Format 1B ESC 26 Description Clears all text and graphics on the NT600S screen After the display of number text lamps or touch switches is upgraded only the upgraded parts are re displayed 7 4 2 Displaying a Character String Specifying the Character Size The size normal or 1 2 size of characters to be displayed can be specified by the following command Character Specify Size Format 1B ESC m1 29...

Страница 237: ...e height x 2 2 32H Enlarge width x 2 3 33H 2 x 2 enlargement 4 34H 3 x 3 times enlargement 5 35H 4 x 4 times enlargement 6 36H 8 x 8 times enlargement 9 39H 8 x 8 times enlargement Description All text and marks sent after this command are displayed in the specified size The character string is specified with the Specify Displayed Characters Com mand refer to 7 4 2 Specify Displayed Characters The...

Страница 238: ...lashing Display to produce a flashing inverse display Canceling the Inverse Display Use the following command to cancel the inverse display mode End Inverse Display Format 1B ESC 23 Description Clears the inverse display attribute so that all characters and marks sent subse quently are not highlighted Other attributes remain unchanged The inverse display attribute is set with the Set Inverse Displ...

Страница 239: ... marks sent subse quently are not flashing Other attributes remain unchanged The flashing display attribute is set with the Set Flashing Display Command The setting with this command remains valid until the screen display is switched or another display attribute setting is made The default display attributes are set to a normal display when a screen is initially displayed Specifying the Display Po...

Страница 240: ...according to the enlargement and display at tributes set with commands The character string continues on the next line if it cannot fit into a single line Set the position where the character string is displayed with the Set CursorPosi tion Command refer to 7 4 2 Set Cursor Position 7 4 3 Displaying Figures Displaying the Line Use the following command to display a polyline Draw Polyline Format 1B...

Страница 241: ...8 8 x1 x2 x3 y1 y2 y3 r1 r2 r3 x1x2x3 X coordinate of circle center 3 digit BCD y1y2y3 Y coordinate of circle center 3 digit BCD X coordinate Y coordinate 000 to 639 000 to 399 r1r2r3 circle radius in dots 3 digit BCD 000 to 199 Description Draws a circle of the specified radius around the circle center point ...

Страница 242: ...column confirm execution Up Down Left Right keys select item Enter key confirm Esc stop 1 This sample program is written in N88BASIC 86 NEC for a PC 9801 com puter Modify this program for use with any other computer language or com puter such as an IBM PC AT or compatible 2 The interval between parameter input and command transmission is a hold interval for interrupt processing of the received com...

Страница 243: ... 67 6 3 Section 6 6 7 6 EXAMPLE PROGRAM 0 1 1 1 1 2 34 56 7 8 2 2 4 9 0 1 1 1 1 0 A 2 4B 4 2 C52 DC24 1 0 1 E 5 D C 4 24D 5D 2 F 0 G H A G 0 A 4 C A ...

Страница 244: ... 67 6 3 Section 6 6 A CI C A 0 A A 8 D 34 9 2D D 3 5 2 4 5C2 A JK JK 0 JK L M JK A JK G 0 JK JK 0 0 JK0 0 JK A 0 0 A D 4 2 4 4D 0 N 0 K 1 1 0 1 LO1N 0 0 L 0 1 1N 1 1N 0 L 11 L 00 L 0 JK L ...

Страница 245: ... C 3 DC24 6D D C 4 24D 5D 2 0 3 D 3 DC24 E A 4B 4 2 C52 DC24 A E A 0 1 1N A A D24 7 C I JK1 1 1 C I 1NA 1 1 A A D24 7 34942 C I JK1 1 1 C 6 2 I6 E 1NA 1 1 A 0 1 5C2 3 4 6 B 6C 1NA A A D24 7 0 34942 C I JK1 1 1 C 6 2 I6 E 1NA 1 1 A A 1 1 A A A A 0 1 5C2 3 4 6 B 6C 1N ...

Страница 246: ... D24 7 2DC 8 42 8 I42 JK1 1 1 3 2DC 8 42 8 C I 1N A 1 1 A N1 1N 0 P A D24 7 6 5 3 2DC 8 42 8 2 2C JK1 1 A 1 5H2DC 8 42 8 C I 1NA 1 1 A A A 1 1 1 1 1 A 1 1 4 56 7 2 2C 1N A 0 A 1 4B 3 2 D 1 A A 0 4 56 7 5 4 4 3 1 C I 1 1 1 E QC4 7 G 42 8 2 0 1 8 2 D 7 2 I6 C I 1 1G 42 8 2 2 4 9 K1 0 ...

Страница 247: ... 1 1 R 1 1 G 42 0 34942 C I 1 C 6 2 I6 E 1 0 0 1G 42 2D 0 34942 C I 1 E E E EJ E EK E 0 EJ 1 1 11 1 1 E E E JK1 1 1 1 0 1 1 0 D57 D 7 2 I6 1 8 2 2 4 9H C I 1 JK1 1 JK1 1 1 D57 DC D 7 2 I6 C I 1 R 1 D57 3 24 24D D 7 2 I6 C I 1 R R 1 1 R 1 1 0 L 4 56 7 6 5 3 2DC 8 42 8 I42 0 P0 1 5C2 E B 5C2 C 4 5C2 S C2 1 L ...

Страница 248: ...1 1 1 M 4 56 7 6 5 3 2DC 8 42 8 C I 1 4 56 7 5 4 4 24D 1 0 1 1 1 1 1 B 6 84 9 6 5 D 67 1 1 66 1 M 1 1 JK1 1 JK1 1 JK1 1 JK1 1 M 1 5H2DC 8 42 8 C I 1 1 1 0 QC4 6 5 3 2DC 8 42 8 2 2C 1 5H2DC 8 42 8 C I 1 1 1 4 I6 4 5C2 1 1 A I6 4 5C2 0 1 1 4 56 7 1 D 2 D66 3 42 1 1 4 56 71 ...

Страница 249: ... 1 2D5 ICUU 1 0 1 D 24 CDC ICUU 1 0 1 2 422 2 ICUU 1 0 0 1 1 0 JK1 1 JK1 1 JK1 1 0 00 0 G 7 2 C 34 56 7 1 D 2 D66 3 42 1 1 1 1 1 G 1 1 JK1 1 JK1 1 G 0 6 5 4 7 I72 8 2 1 8 2 5 4 7 4U 1 1 V S0 1 1 V 0S0 1 1 1 JK1 1 JK1 1 0 5 4 7 8 2 6 9 2 1 5 4 7 8 2 6 9 21 1 1 1 1 1 G 1 1 1 1 1 1 1 0 ...

Страница 250: ... 6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 D 6 34 56 7 0 2 4 B 34 56 7 3 4 B 34 56 7 2 6 84 9 34 56 7 3 6 84 9 34 56 7 2 C D 5D 424D 0 1 1 K J 1 1 K J 1 1 1 1 0 5 4 7 4 56 7 3 8 2 1G 42 8 2 2 4 9 KW1 1 1 D6764 11 0 0 0 0 0 1 1 J K ...

Страница 251: ... 67 6 3 Section 6 6 0 1 1 J K 0 1 1 1 1 0 P N1 1N N J 1 1 0 0 4 6 0 0 0 1 1 0 K J 0 0 0 0 0 1 1 0 K J 0 0 0 00 0 1OOOOOEEEEE1 K J 0 1 1 1 1 1 1 2 6 24D DC24 0 A A A A J A K A 0 L L 11 L JK L ...

Страница 252: ... 1 1 1 1 1 4 56 7 5 4 4 3 1 1 1 1 QC 2 C I 1 1 1 1G 42 8 2 2 4 9 D 7 2 I6 1 1 1 1 34942 42 C 6 2 I6 1 1 1 0 10 34942 42 C 6 2 I6 1 1 1 1 D57 D 7 2 I6 1 1 H1 1 5 3 2DC 8 42 8 34 56 7 I42 5 4 4 24D 1 1 L1 1 5 3 2DC 8 42 8 34 56 7 33 5 4 4 24D 1 1 M1 1 5 3 2DC 8 42 8 34 56 7 2 2C 9C4 71 1 1 1 DC 8 42 8 34 I6 1 1 1 ...

Страница 253: ... D61 1 1 1 7 2 C 34 56 71 1 G1 1 6 1 1 1 1 8 2 5 4 7 4U 1 1 1 1 5 4 7 8 2 6 9 21 1 1 1 D 6 34 56 71 1 X1 1 2 4 B 34 56 71 1 1 0 1 3 4 B 34 56 71 1 E1 1 2 6 84 9 34 56 71 1 1 1 3 6 84 9 34 56 71 1 R1 1 2 C D 5D 424D 1 1 1 1 5 4 7 34 56 7 3 8 2 1 1 1 1 5D6764 1 1 1 1 4 6 1 1 01 ...

Страница 254: ... 0 4 4 5 4 5 6 5 4 4 5 5 7 5 5 6 5 ...

Страница 255: ... and select the Transmit Mode Refer to 4 5 Registering the Screen Data page 79 Not connected to the support tool Check the installation of the connector cable Refer to 2 3 Connecting to the Support Tool page 30 PT type setting and direct connection setting at the support tool do not match the NT600S Using the Tool Settings of the support tool set the PT type and direct connection settings that mat...

Страница 256: ...e communication cable from the source of the noise and insert a noise filter in the power supply line Touch panel is broken Check the touch panel by performing the touch panel test in the I O check in the maintenance mode PC mode changes to monitor mode The NT600S changes the mode during host link communication This is normal with the NT600S specification When using a PC that can also be connected...

Страница 257: ... initial settings An error occurred in the unit There is an error at the C200H interface unit Contact your OMRON service center 8 2 2 Errors Occurring During Operation The table below shows the errors that can occur during operation of the NT600S and their remedies Message Cause Remedy Setting Error Bits or words allocated to the PC memory cannot be found in the screen data Check the memory area i...

Страница 258: ...when a communication error occurs When an error message is displayed press the confirm touch switch displayed on the screen The screen display will return to the RUN mode Display of communication errors As shown below communication errors are displayed in the center of the screen together with a classification indicating whether they are receive or send errors Screen when an error has occurred dur...

Страница 259: ...ne command a time lapse exceeding 5 seconds is detected Confirm the proper command length Check the cable connection NAK Received end code simultaneously displayed Noise caused data corruption during communication Use a noise resistant cable if communication occurs in an environment with high levels of noise Check the end code by referring to the PC user s manual Unit No Error The unit No does not...

Страница 260: ...due to deterioration of the display unit Backlight When the backlight in the display is getting dim and the screen cannot be read eas ily replace the backlight The backlight can be replaced at the rear of the NT600S while it is mounted in an operation panel Models that use a backlight NT600S ST121 EV NT600S ST121B EV Replaceable Backlight Model NT600S CFL01 Guide to Backlight Replacement Under nor...

Страница 261: ...an electric shock Operation 1 Turn off the power to the NT600S and remove the lid of the CFL case located at the upper right part of the rear of the NT600S remove the screw with a Phil ips head screwdriver then open the CFL case lid CFL case lid Screw securing CFL case lid 2 Disconnect the backlight connector from the NT600S ...

Страница 262: ...p The backlight is fitted in the correct position if the handle is upright If the handle is tilted it indicates that the backlight is not fitted correctly Repeat the step above until the backlight is fitted correctly 5 Connect the backlight connector to the NT600S Plug in the connector after making sure the polarity is correct Take care to en sure that the connector cord will not be damaged while ...

Страница 263: ... battery in the following cases The battery must be replaced within 5 days When 5 years have passed since the installation of a new battery When the RUN LED is lit Battery replacing method Replace the battery by following the procedure given below To protect the contents of the memory the battery must be replaced in less than 5 minutes Operation 1 Keep the power ON for at least 1 minute and then t...

Страница 264: ...e battery may be replaced while the power is ON In this case there are no re strictions on battery replacement time Never short the and terminals of the battery Do not recharge take apart de form or discharge it into open flame Attempting any of these will lead to hazards such as fire leakage of electrolyte rupture etc When replacing a battery ensure that the battery terminal does not touch the bo...

Страница 265: ...tuck to the display remove them dur ing cleaning Never use volatile solvents such as benzene or thinners or chemical dusters These could cause degeneration of the coatings of the NT600S display and body Inspection Method In normal environments inspect the NT600S at intervals of between 6 months and a year In environments that are extremely hot and humid or very dusty environ ments shorten the insp...

Страница 266: ...f external connecting cables Faults such as incipient disconnections Visual inspection Components with limited lives Brightness of the backlight Must be sufficiently bright Backlight life Brightness is halved after about 20 000 hours in use Visual inspection Brightness of EL display unit Must be sufficiently bright EL display unit life Brightness is reduced by 30 after about 30 000 hours in use Vi...

Страница 267: ... ...

Страница 268: ...In air 8 kV contact 6 kV indirect 7 kV Electromagnetic field strength 10 V m IEC801 3 Fast transient burst noise Power supply line 2 kV IEC801 4 I O line 0 25 kV Damped oscillatory wave Power supply line 1 kV IEC255 4 Vibration resistance 10 to 22 Hz with 1 5 mm double amplitude for a total of 30 min in X Y and Z directions 22 to 500 Hz with 1 5 G 14 7 m s2 acceleration in X Y and Z directions Sho...

Страница 269: ...View angle Left direction 80 Right direction 80 Life expectancy 30 000 hours minimum till brightness becomes 30 weaker Backlight white cold cathode tube Life expectancy Average 20 000 hours the time taken for the brightness to decline to half its original value at normal temperature and humidity Automatic turn off Can be set to turn off in 10 minutes or 1 hour or to remain on Indicators POWER indi...

Страница 270: ...play history recording backlight Number of registered screens 1000 max Screen registration method Transfer screen data created using the support tool to the NT600S Screen saving method screen data memory Saved to flash memory recording format unique to NT600S Number of numeral memory tables that can be used Number used for numeral display number used for graphics number used for numeral settings 5...

Страница 271: ...test for memory switches etc Status setting confirmation for communications and other conditions Simple communications confirmation Backup by battery Connecting an optional battery makes the display history recording and resume functions available Data retaining time 5 years at 25 C If battery voltage becomes low the RUN LED on the front panel lights in orange and the communication flag BAT LOW to...

Страница 272: ... SUB connector female Number of units connected 1 to 1 Transmission distance Max 15 m For an NT Link 1 N Item Specification Communications standard EIA RS 232C Connector 9 pin D SUB connector female Number of units connected 1 1 to 8 Transmission distance RS 232C cable Max 2 m RS 422A 485 cable Total length 500 m When NT AL001 used For RS 232C Item Specification Communication standard EIA RS 232C ...

Страница 273: ... Appendix B APPENDIX B Dimensions Body NT600S ST121 B V NT600S ST211 B V POWER RUN 275 10 81 263 10 34 192 7 55 180 7 08 6 0 24 71 2 79 Unit mm inch ...

Страница 274: ... Appendix B Installation Unit mm inch 180 7 09 287 11 3 15 5 0 61 34 1 34 min 38 1 5 max Installation fitting Installation panel 204 8 03 Cable Installation Unit mm inch 45 1 77 RS232C cable ...

Страница 275: ...and describes the methods for installing and removing it Refer to this information when designing the control panel Dimensions With RS 422A terminal block cover closed 30 W x 114 H x 100 2 D mm With RS 422A terminal block cover open 30 W x 114 H x 119 5 D mm Installation and Removal The RS 232C RS 422A converter unit NT AL001 is installed on a DIN rail or in an operation panel The RS 422A terminal...

Страница 276: ... sideways a b Removal from the DIN Rail Remove the end plates at right and left then insert a flat tipped screwdriver into the rail stopper on the bottom of the unit and pry the unit away Installation in an Operation Panel Make two screw holes in an operation panel wall at least 2 mm thick and securethe converter to the wall with screws 100 3 94 110 4 33 30 1 18 21 0 83 2 M4 Unit mm In order to en...

Страница 277: ...ted and maintained without difficulty install it at a distance from high voltage equipment and power equipment Install the unit as far as possible from personal computers amateur radio equipment radios etc The radio waves generated by the unit may cause interference that will affect these types of equipment Do not install the NT600S at sites subject to the following conditions Otherwise the produc...

Страница 278: ...o equipment that generates a strong electric or magnetic field solenoids etc pro vide a gap of at least 40 mm 40 mm min Solenoid PT When using the RS 232C 5V output check the current capacity of the con nected equipment The maximum current value of the NT20S 5 V output is 150 mA Transportation and Storage of the PT Note on transportation Pack the PT in the packaging intended for it before transpor...

Страница 279: ...20 LK201 V1 25 pin manufactured by JAE Connector Cover XM2S 0911 C series CQM1 C200HS C200HX HG HE CVM1 CV series CPU unit CV500 LK201 9 pin manufactured by OMRON XM2S 2511 C500 LK203 C500 LK201 C200H LK201 25 pin manufactured by OMRON DB C2 J9 C500 LK201 V1 C120 LK201 V1 25 pin manufactured by JAE When connecting the NT600S to an OMRON PLC C H the connector and the connector hood must be prepared...

Страница 280: ...ot used Check the current capacity of the supplied equipment before using the No 6 pin 5 V output The 5 V output for NT600S is 5 V 5 150 mA max in the case of ST211 B EV and 5 V 5 100 mA max in the case of ST121 B EV Connecting an NT600S to a C Series Host Link C Series Host Link Unit 25 pin Connector Specifications Applicable Host Link Unit C200H LK201 V1 C500 LK201 V1 C500 LK203 C120 LK201 V1 El...

Страница 281: ... 2 C500 LK201 and C200H LK201 V1 only ...

Страница 282: ...rface RS 232C interface Pin number Abbrevi atioon 1 2 3 4 5 6 7 8 FG SD RD RS CS SG Shielding wire 25 pin connector NT600S PC host link unit ER 20 5V Connecting an NT600S to a C Series CPU C H C Series CPU Unit C H 9 pin Connector Specifications Applicable CPU C20H C28H C40H C60H Electrical characteristics Complies with EIA RS 232C Signal direction Signal input and output is relative to the PC Con...

Страница 283: ... unit CV500 LK201 Electrical characteristics Complies with EIA RS 232C Signal direction Signal input and output is relative to the PC Communication Port 1 25 pin Connector Connector Pin Signal Name Abbreviation Signal Direction Connector Pin No Signal Name Abbreviation Input Output Connector cover Frame ground FG 1 Frame ground FG 2 Send data SD TXD 3 Receive data RD RXD 4 Request to send RS RTS 5...

Страница 284: ...r and pin 1 at the host link unit end of the cable only Communication Port 1 25 pin Connector 1 2 3 4 5 6 7 8 9 Pin number Abbrevi atioon FG SD RD RS CS 5V SG RS 232C interface RS 232C interface Pin number Abbrevi atioon 1 2 3 4 5 6 7 8 FG SD RD RS CS SG Shielding wire 25 pin connector NT600S PC host link unit ER 20 Communication Port 2 9 pin Connector 1 2 3 4 5 6 7 8 9 Pin number Abbrevi atioon F...

Страница 285: ...ncorporated in CV CVM1 CPUs with the exception of EV cannot be used Electrical characteristics Complies with EIA RS 232C Signal direction Signal input and output is relative to the PC Connector Signal Name Abbreviation Signal Direction Connector Pin No Signal Name Abbreviation Input Output Connector cover Frame ground FG 2 Send data SD TXD 3 Receive data RD RXD 4 Request to send RS RTS 5 Clear to ...

Страница 286: ... lot number is 15Y5 or later Converter units of lot numbers previous to 15Y5 cannot be connected NT AL001 RS 232C Connector Specifications 9 pin Type Electrical characteristics Conform to EIA RS 232C Signal direction Signal input and output is relative to the NT AL001 Connector Signal Name Abbreviation Signal Direction Connector Pin No Signal Name Abbreviation Input Output Connector cover Groundin...

Страница 287: ...SG SDB SDA RDB RDA CSB CSA RS 232C interface RS 232C interface RS 422A interface RS 422A interface Pin No Abbrev RS 232C 9 pin NT AL001 Abbrev 9 pin Abbrev Terminal No Terminal block Shielding wire Host Signal Name Ground for safety Signal ground Receive data Receive data Send data Send data Request to send Request to send RS 422A Pin No For NT600S ST121 B V Shielding wire NT600S 1 2 3 4 5 6 7 8 9...

Страница 288: ...he FG Cable with Shielding Wire Connected to FG 1 Cut the cable to the required length 2 Remove the external vinyl insulation from the cable with a razor blade Take care not to damage the shielding underneath 3 Cut back the shielding wire with scissors 4 Use wire strippers to strip the insulation from each wire 5 Fold back the shielding wire 6 Wrap aluminum foil tape around the folded back shieldi...

Страница 289: ...e wire strippers to strip the insulation from each wire 5 Wrap vinyl tape over the cut off end of the shielding wire Vinyl tape 1 2 3 4 5 Units mm in 5 0 19 40 1 57 RS 232C Soldering 1 Slide heat shrink tube over each wire 2 Pre solder each wire and connector cable 3 Solder each wire to the connector terminal Heat shrink tube F 1 5mm dia l 10mm Soldering iron 4 Push the heat shrink tube over the s...

Страница 290: ...P 28AWG Multicore cable manufactured by Hitachi Cable Ltd On the other end of the cable use the type of connector and connector cover which matches the host computer connector type Connection For Host Only the shielded wire on the host side is connected to the connector hood The following diagram is for RS CS control If RS CS control is not executed RS and CS must be short circuited turned over fo...

Страница 291: ...422 converter unit type NT AL001 RS 422A cable max 500 m RS 232C RS 422 converter unit type NT AL001 RS 232C cable max 2 m NT600S Wiring Wiring of RS 232C cable 2 3 4 5 6 9 Pin No Abbrev SD RD RS CS 5V SG RS 232C interface Shielding wire PT or PC NT AL001 RS 232C interface 3 4 5 6 9 SD RD RS CS 5V SG Only connected at PC Connector cover 2 Abbrev Pin No Connector cover The pin numbers are the numbe...

Страница 292: ...Cable Wiring 3 4 5 6 Pin No Abbrev SDA SDB RDA RDB RS 422A terminal block Shielding wire NT AL001 NT AL001 RS 422A terminal block 3 4 5 6 FG SDA SDB RDA RDB 1 Abbrev Pin No 1 FG DIP Switch Settings at RS 232C RS 422 Converter Unit ...

Страница 293: ...e Support Tool Mode NT600S memory switch Restrictions NTM V4 NT600M OMRON Standard NT600M Thumbwheel numeral settings not possible no upper lower limits hexadecimal input not NT600M Ver 4 Standard NT600M limits hexadecimal input not possible indirect specification not possible touch switch input tifi ti fi d t NT V2 NT600S Ver 4 Standard High speed NT600S notification fixed as momentary data trans...

Страница 294: ...ed above are those applicable when the personal computer features a 25 pin DSub female connector If the personal computer features another type of connector prepare the appropriate parts by referring to its manual Wiring Connections The connector at the NT600S used for connecting the support tool is also used as the connector for connecting the PC Host For the pin configuration refer to NT600S Con...

Страница 295: ... connection cable use the following recommended parts Name Model Remarks Connector XM2D 0901 9 pin type made by OMRON personal computer side XM2A 0901 9 pin type made by OMRON PT side Connector cover XM2S 0911 9 pin type made by OMRON two Cable AWG28 5P IFVV SB Multi core shielded cable FUJIKURA Ltd CO MA VV SB 5P 28AWG Multi core shielded cable HITACHI cable Ltd ...

Страница 296: ...f registered elements Reading of elements that could not be registered Reading of the elements that could not be registered Reading the PT status control area Reading of elements that could not be registered Reading of elements that could not be registered Reading of the PT status control area PT PC PT PC PT PC PT PC PT PC PT PC PT PC PT PC When the values registered in the NT600S are used as the ...

Страница 297: ...120 words calculated in this way can be registered If the number of elements is larger than this internal processing is in creased in proportion to the excess number and this generates a delay in proces sing If the point where the registrable quantity is exceeded is in the middle of an ele ment that spans several words for example a character string memory table reg istration is quit without regis...

Страница 298: ...y NT600S processing Details of processing PT PC PT PC Writing to character string memory tables High Low Writing to the PT status notify area Changing the contents of words allocated to the PC when the value in a numeral memory table has changed Changing the contents of words allocated to the PC when the value in a numeral memory table has changed Writing to bits in order to inform the PC that a t...

Страница 299: ...tical fiber cable connector for C200H C series C200H C200H LK201 V1 Rack mounting Unit with RS 232C connector for C200H C200H C200HS C200HE C200H LK202 V1 Rack mounting Unit with RS 422C connector for C200H C200HE C200HG C200HX C500 LK101 P V1 3G2A5 LK201 EV1 Features an optical fiber cable connector C series C500 F C500 LK103 P Rack mounting Unit for C500 C500 F C1000 H C2000 H C500 LK201 V1 3G2A...

Страница 300: ...ctor for RS 232C connections selectable 9 pin C200HS C200HE CPU32 E C200HE CPU42 E Features a connector for RS 232C connections selectable 9 pin C series C200HE C200HG CPU33 E C200HG CPU43 E C200HG CPU53 E C200HG CPU63 E Features a connector for RS 232C connections selectable 9 pin C series C200HG C200HX CPU34 E C200HX CPU44 E C200HX CPU54 E C200HX CPU64 E Features a connector for RS 232C connecti...

Страница 301: ...HX CPU54 E C200HX CPU64 E Features a connector for RS 232C connections selectable 9 pin C series C200HX CV500 CPU01 EV1 CV1000 CPU01 EV1 CV2000 CPU01 EV1 Features a 9 pin connector for RS 232C connections CV500 CV1000 CV2000 CVM1 CPU01 EV1 CVM1 CPU11 EV1 CVM1 CPU21 EV1 Features a 9 pin connector for RS 232C connections CVM1 series For CPU units marked a communications port is required CPUs For Con...

Страница 302: ...U53 E C200HG CPU63 E C200HG C200HX CPU34 E C200HX CPU44 E C200HX CPU54 E C200HX CPU64 E C200HX Related Parts and Equipment for PT Name Model Remarks Support Tool NT ZA3AT EV2 3 5 inch FD for NT Series Options NT600S CFL01 Replaceable backlight NT600M KBA04 Reflection suppressing protective sheet NT600S KBA01 Chemical resistant cover 3G2A9 BAT08 Battery NT LB122 C200H I F Unit RS 232C RS 422 Conver...

Страница 303: ...1 C200H CN521 5 m C200HX HG HE C200H direct communication NT20M CNP131 C200H CN131 10 m C200H direct communication C20H CN312 30 cm NT20M CNP712 C20H CN712 70 cm C H NT20M CNP222 C20H CN222 2 m Connection cable Model Remarks AWG28 5P IFVV SB Multicore cable manufactured by Fujikura Ltd CO MA VV SB 5P 28AWG Multicore cable manufactured by Hitachi Cable Ltd Applicable connectors Name Model Remark Co...

Страница 304: ...st Replaceable Backlight NT600S CFL01 This is a backlight for replacement purposes Reflection Suppressing Protective Sheet NT600M KBA04 Stuck to the display to prevent it from being soiled The entire sheet is colorless and transparent ...

Страница 305: ...oya oil Toluene For information on protection against chemical agents not included in the table above please ask OMRON If it is a chemical agent to which silicone rubber is recognized to be resistant the cover can be used with confidence even if that chemical agent is not listed in the Protects Against column above This cover does not afford protection against all chemical agents Since the cover i...

Страница 306: ...g direct communication Battery 3G2A9 BAT08 This is a lithium battery used for memory backup The disposal of the batteries and backlight may be regulated by national or local authorities Dispose of them in accordance with the laws and regulations of the relevant coun try and local authority ...

Страница 307: ...0 H CQM1 0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0051 0000 to 6655 CPM1 0000 to 0019 0200 to 0255 0000 to 0019 0000 to 0015 0000 to 0015 0000 to 0127 0000 to 1023 6144 to 6655 Flow type C500F 0000 to 0063 0000 to 0031 0000 to 0031 0000 to 0127 0000 to 0511 Flow type C1000HF 0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0511 0000 to 4095 OMRON CV Series Memory Map ...

Страница 308: ...Character Codes Pin 2 of SW2 must be ON to enable English language messages to use the following codes Example Hex code is represented by 30 decimal code by 48 and character by 0 30 0 48 Code 20 and 32 in the table represents a space as indicated by SP ...

Страница 309: ...26 36 6 46 F 56 V 66 f 76 v 86 å 96 û 38 54 70 86 102 118 134 150 7 27 37 7 47 G 57 W 67 g 77 w 87 ç 97 ù 39 55 71 87 103 119 135 151 8 28 38 8 48 H 58 X 68 h 78 x 88 ê 98 ÿ 40 56 72 88 104 120 136 152 9 29 39 9 49 I 59 Y 69 i 79 y 89 ë 99 Ö 41 57 73 89 105 121 137 153 A 2A 3A 4A J 5A Z 6A j 7A z 8A è 9A Ü 42 58 74 90 106 122 138 154 B 2B 3B 4B K 5B 6B k 7B 8B ï 9B 43 59 75 91 107 123 139 155 C 2C...

Страница 310: ... τ F7 167 183 199 215 231 247 8 A8 B8 C8 D8 E8 Φ F8 168 184 200 216 232 248 9 A9 B9 C9 D9 E9 Θ F9 169 185 201 217 233 249 A AA BA CA DA EA Ω FA 170 186 202 218 234 250 B AB 1 2 BB CB DB EB δ FB 171 187 203 219 235 251 C AC 1 4 BC CC DC EC FC n 172 188 204 220 236 252 D AD BD CD DD ED FD 2 173 189 205 221 237 253 E AE BE CE DE EE ε FE 174 190 206 222 238 254 F AF BF CF DF EF FF 1 175 191 207 223 23...

Страница 311: ... ...

Страница 312: ...r specify size 222 Character string 17 Character string memory table 128 170 Characters 8 120 128 Checking the LCD display 104 Checking the LED 101 Checking the buzzer 102 Checking the communications 105 Checking the touch switches 102 Child screens 124 125 Classification of screens 124 Clear screen 222 Communication I F 106 Communication procedure 202 Comparison between NT600S and NT600M 7 Compat...

Страница 313: ... Equivalent to IP65 4 Error message during the start up 72 Error messages 244 F Factory setting 27 File units 79 Flash memory 83 Flash 135 140 Flashing display 121 129 Frame 135 G Graph frame 132 Grounding terminal 25 Grounding 29 Guide display 140 H Host I F tool connector 25 Host link method 31 Host link unit 33 34 Host link 13 85 I I O check 101 IP65 27 Image data memory 72 Initialization by us...

Страница 314: ...l display 223 Normal screen 124 Nothing is displayed 242 Notification and control of touch switches 205 Notification of numbers to the PC 189 Notify bit 183 Notifying the NT600S status 157 Notifying the PC 185 Notifying the display elements 157 Notifying the display screen 162 Number of registration words 164 166 Numeral memory table 16 129 169 Numeral setting attributes 126 144 Numeral setting st...

Страница 315: ...mory is initialized 73 74 Screen data 79 244 Screen display control 208 Screen display 194 Screen list 116 Screen number 0 119 242 Screen number 1 92 Screen number response 218 Screen number 119 Screen switch setting 160 Screen switch 142 Screen switching strobe 161 162 198 Screen switching timing 161 Screen 119 Selecting communication speed 86 Selecting the host communication method 85 Selecting ...

Страница 316: ...nu 68 System 127 T Table of commands 207 Terminal commands 19 207 222 3 D 140 Thumb wheel numeral settings 148 Tool settings 114 Tool transmit 106 Touch switch bit output 220 Touch switch disable 214 Touch switch enable 214 Touch switch number output 221 Touch switches used to call the system menu 70 Touch switches 9 17 70 139 Transmit mode 71 80 Transmit 68 79 Transmitting screen data 79 118 Turn...

Страница 317: ... ...

Страница 318: ...r notification to the PC using touch switches alternate set reset Additions relating to additional functions when performing numeral input upper lower limit check hexadecimal input Additions relating to additional communication method C200H direct communication E1 3 5 1997 Amendments relating to addition of the NT link 1 N method communication function Amendments relating to additions to safety no...