1
6
9
5
. .( $0&
Appendix E
Wiring Connections
The NT600S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together
or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see
in the figure).
Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.
1
2
3
4
5
6
7
8
9
Pin
number
Abbrevi-
atioon
FG
SD
RD
RS
CS
--
--
SG
RS-232C
interface
RS-232C
interface
Pin
number
Abbrevi-
atioon
1
2
3
4
5
6
7
8
--
FG
SD
RD
RS
CS
--
SG
--
--
Shielding
wire
25-pin connector
NT600S
PC (host link unit)
--
--
--
ER
--
--
--
20
+5V
Connecting an NT600S to a C-Series CPU (C
H)
C-Series CPU Unit (C
H) 9-pin Connector Specifications
Applicable CPU:
C20H/C28H/C40H/C60H
Electrical characteristics:
Complies with EIA RS-232C
Signal direction:
Signal input and output is relative to the PC.
Connector
Signal Name
Abbreviation
Signal Direction
Connector
Pin No.
Signal Name
Abbreviation
Input
Output
1
Frame ground
FG
--
--
2
Send data
SD (TXD)
3
Receive data
RD (RXD)
4
Request to send
RS (RTS)
5
Clear to send
CS (CTS)
7
Signal ground
SG (GND)
--
--
Содержание NT-series
Страница 1: ...NT series Programmable Terminal Operation Manual Cat No V022 E3 1 ...
Страница 2: ... ...
Страница 4: ... ...
Страница 9: ... PRECAUTIONS ...
Страница 14: ... ...
Страница 36: ... ...
Страница 166: ... ...
Страница 254: ... 0 4 4 5 4 5 6 5 4 4 5 5 7 5 5 6 5 ...
Страница 267: ... ...
Страница 281: ... 2 C500 LK201 and C200H LK201 V1 only ...
Страница 311: ... ...
Страница 317: ... ...