90
6
. Detailed settings for communications
6.3 CompoWay/F (continued)
Example of read variable area communications
This example shows how to read the two measurement values with one command when the measurement is of
voltage 1 at 103.7V and voltage 2 at 103.6V
Command
Response
This product converts measured values to hexadecimal without decimal points for response.
H
’
0000040D would be 1037 (in decimal).
“(H’02)
00
00
0
01
01
C0
0000
00
0002
(H’03)
(H’42)”
STX
Commu
nication
address
Sub-
address
SID
MRC
SRC
Variable
Type
Start
reading
address
Bit
Positio
n
Number of
elements
ETX
BCC
"(H’02)
00
00
00
01
01
0000
0000040D
0000040C
(H’03)
(H’02)”
STX
Commu
nication
address
Sub-
address
Exit
code
MRC
SRC
Respon
se
code
Voltage 1
Voltage 2
ETX
BCC