52
3.
Basic use
3.4 How to read the setting values (continued)
Circuit
MENU
No.
Setting Item
Main display
Display of options and input values
Sub display
Unit
Default
Value
Remarks
Comm
on
CMMN
00
Protocol
MODBS / COMPF
PRTCL
MODBS
01
Communication speed
1.2K / 2.4K /4.8K
9.6K / 19.2K / 38.4K(bps)
BPS
9.6K
02
Data length
7 / 8
LNGTH
8
Modbus: 8 (fixed)
CompoWay/F: Select between 7 or 8
03
Stop bit
1 / 2
STOP
1
04
Parity
NONE / ODD / EVEN
PRTY
EVEN
05
Transmission wait time
00 to 99
WAIT
20
06
VT ratio
1.00 to 999.99
VT-R
1.00
Set the ratio between the primary voltage and
the secondary voltage when voltage using VT
is input
07
Conversion rate
0.000 to 99.999
RATE
10.000
Set the conversion factor by which active
energy is multiplied for each circuit
08
Conversion display units
3 places: XXX
Each place: 0 to 9, A to Z, /, -, _
CHAR
CO2
Set the units for the conversion value using
any 3 characters
09
Pulse output units
1 / 10 / 100 / 1K / 5K
10K / 50K /100K (Wh)
WH/P
100
0A
Automatic LCD off
OFF / 1.0 / 5.0 / 10.0 (minutes)
DISP
5.0
OFF means alight constantly
0B
Warning ON/OFF
ON / OFF
ALARM
ON
Set the output for the warning for voltage
miss-wiring
(Output even when pulse output warning is
OFF)
0C
Tariff ON/OFF
ON / OFF
TARIF
ON
0D
Change password
0000 to 9999
PASSW
0001
Change the password used when making
settings.
Others
ETC
90
Software version display
V.1.0.0
KM-N2
---
The main display shows an example when the
version is 1.0.0.
91
All active energy reset
-----
0WH
-----
Clear the active energy for all circuits.
92
Initialize
-----
RESET
-----
Restore the factory defaults.
All settings and all measured values are
initialized.