99
6
. Detailed settings for communications
6.4 Address map (continued)
• Current 2 is the value measured by either CT2 or CT4.
• Current 3 is the measured value calculated from current 1 and current 2.
• Figures with units of Wh and kWh can be read to the cumulative value. You can use the most easy to read
according to the changes in the cumulative value.
• Negative numbers are shown as two's complement.
• Only the consecutive address items can be read in a batch.
address
Item
R/W
Modbus
CompoWay/F
Parameter name
Monitor value
0228
0114
Cumulative total reactive power (not resettable)
(kVarh)
H'00000000 to H'3B9AC9FF
(0 to 999999999)
Value that is 1 times each value
R
022A
0115
T1 Active energy (import) (not resettable) (kWh)
R
022C
0116
T2 Active energy (import) (not resettable) (kWh)
R
022E
0117
T3 Active energy (import) (not resettable) (kWh)
R
0230
0118
T4 Active energy (import) (not resettable) (kWh)
R
0240
0120
Active energy (import) (resettable) (Wh)
R
0242
0121
Active energy (export) (resettable) (Wh)
R
0244
0122
Reactive energy (import) (resettable) (Varh)
R
0246
0123
Reactive energy (export) (resettable) (Varh)
R
0248
0124
Cumulative total reactive power (resettable) (Varh)
R
024A
0125
T1 Active energy (import) (resettable) (Wh)
R
024C
0126
T2 Active energy (import) (resettable) (Wh)
R
024E
0127
T3 Active energy (import) (resettable) (Wh)
R
0250
0128
T4 Active energy (import) (resettable) (Wh)
R
0260
0130
Active energy (import) (resettable) (kWh)
R
0262
0131
Active energy (export) (resettable) (kWh)
R
0264
0132
Reactive energy (import) (resettable) (kVarh)
R
0266
0133
Reactive energy (export) (resettable) (kVarh)
R
0268
0134
Cumulative total reactive power (resettable) (kVarh)
R
026A
0135
T1 Active energy (import) (resettable) (kWh)
R
026C
0136
T2 Active energy (import) (resettable) (kWh)
R
026E
0137
T3 Active energy (import) (resettable) (kWh)
R
0270
0138
T4 Active energy (import) (resettable) (kWh)
R
0300
0180
Conversion value (e.g. JPY)
R
0302
0181
Conversion value (e.g. K.JPY)
R