Operation Methods

Setting Ranges and Wiring Connections

Connections

Input

Connect the input between the I1-COM, I2-COM, or I3-COM terminals, according to the input 
current. Malfunctions may occur if the input is connected to unused terminals and the Unit will 
not operate correctly.
Terminal I1 is not used by the K8AK-AW3.
If using the OMRON K8AC-CT200L CT, connect to terminals k and l on the K8AC-CT200L. 
(Terminals kt and lt are not used.)

Power Supply

Connect the power supply to terminals A1 and A2.

Outputs

AL1 (SPDT relay) is output to terminals 11, 12, and 14.
AL2 (SPDT relay) is output to terminals 21, 22, and 24.

Note:

Use the recommended ferrules if using twisted wires.

DIP Switch Settings

The resetting method, relay drive method, and operating mode are set using the DIP switch 
located on the bottom of the Unit.
K8AK-AW

@

 does not use SW1.

Setting Method

Setting Current

The current knob (SV) is used to set the current.
The current can be set to 10% to 100% of the maximum setting range.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the 
same level.)
Use this as a guide to set the current.
The maximum setting range will differ depending on the model and the input terminal.
Example: K8AK-AW3 Using Input Terminals I3-COM
The maximum measuring current will be 200 A AC and the setting range will be 20 to 200 A.

Model

Setting range

Input type

Wiring 

connections

K8AK-AW1

2 to 20 mA AC/DC

Direct input

I1-COM

Note:

The DC input terminals have no polarity.

* The K8AK-AW3 is designed to be used in combination 

with the OMRON K8AC-CT200L Current Transformer 
(CT). (Direct input is not possible.)

10 to 100 mA AC/DC

Direct input

I2-COM

50 to 500 mA AC/DC

Direct input

I3-COM

K8AK-AW2

0.1 to 1 A AC/DC

Direct input or 
commercially 
available CT

I1-COM

0.5 to 5 A AC/DC

I2-COM

K8AK-AW3

10 to 100 A AC*

OMRON CT

I2-COM

20 to 200 A AC*

OMRON CT

I3-COM

<For K8AK-AW3>

Load

Current input

Signal output

AL1 relay 
signal 
output

Single-phase power

Power supply

voltage

K8AK-AW3

K8AC-
CT200L

C (COM)

A1

A2

I1

I2

I3

11

14

l

k

12

21

24

22

Signal output

AL2 relay 
signal 
output

DIP switch pins

SW3

ON

OFF

SW2
SW1

SW4

DIP Switch Functions

Note:

All pins are set to OFF at the factory.

Pin

OFF 

 

ON 

 

Resetting 
method

Manual reset

Not used.

---

---

Automatic reset

---

---

Operating 
mode

AL1

AL2

Overcurrent

Undercurrent

---

Overcurrent

Overcurrent

---

Undercurrent Undercurrent

---

Overcurrent

Undercurrent

---

1

OFF

ON

2

3

4

Содержание K8AK-AS1 24VAC/DC

Страница 1: ...ent Transformer CT Direct input is not possible Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do not exceed the overload capacity of the K8AK AW...

Страница 2: ...mA AC DC 50 to 500 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 0 to 100 mA AC DC I2 COM Approx 1 Direct input 0 to 500 mA AC DC I3 COM Approx 0 2 Direct input K...

Страница 3: ...puts ALM Red Input impedance Refer to Input Range on previous page Output relays Two SPDT relay outputs normally closed operation Output relay ratings Rated load Resistive load 5 A at 250 VAC 5 A at 3...

Страница 4: ...minals Between input terminals and output terminals Dielectric strength 2 000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power su...

Страница 5: ...h the OMRON K8AC CT200L Current Transformer CT Wiring Example Directly Inputting a Current Using a CT Always turn on the control power supply for the K8AK at least 2 seconds before turning on the powe...

Страница 6: ...AL1 Contact b for the approx 1 second interval immediately after the K8AK control power supply is turned on After that a switch to contact a will be made as an overcurrent state is no longer present A...

Страница 7: ...K8AK power supply voltage Power ON Undercurrent AL2 contacts 21 24 Undercurrent set value AL2 30 of AL1 current set value Overcurrent AL1 contacts 11 14 Lit AL2 alarm indicator AL1 alarm indicator Ove...

Страница 8: ...ng time 0 1 to 30 s t Operating time 0 1 to 30 s t t Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Flashing Flashing Power ON lock...

Страница 9: ...ched the same level Use this as a guide to set the current The maximum setting range will differ depending on the model and the input terminal Example K8AK AW3 Using Input Terminals I3 COM The maximum...

Страница 10: ...de to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the set value Use startup lock time to prevent unwanted operation e g as a result of inrus...

Страница 11: ...figure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for...

Страница 12: ...cified torque of 0 49 to 0 59 N m Use of the product beyond its life may result in contact welding or burning Make sure to consider the actual operating conditions and use the product within its rated...

Страница 13: ...ifficult to see 15 Do not use the product if it is accidentally dropped The internal components may be damaged 16 Be sure you understand the contents of this catalog and handle the product according t...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...0169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com...

Отзывы: