K8AK-AW

6

Example Relay Sequence for Overcurrent/Undercurrent Monitoring Mode

<Explanation of operation>

• RY2 (magnet contactor) will be energized in approx. 100 ms when PB1 (startup button) is pressed.
• Use a timer for the K8AK undercurrent alarm (AL2) as a switch from contact “b” to contact “a” will not occur for approx. 250 ms even if the magnet 

contactor (RY2) is turned on.

<Timer setting conditions (reference)>

• TA

: Timer (H3YN-2 + socket, Omron)

• Operating mode : Interval mode
• Setting time

: 2 s

Before pressing the startup button (after approx. 1.25 seconds have passed following turning on the power supply of K8AK)

Immediately after pressing the startup button (within approx. 250 ms)

Two seconds after pressing the startup button

Note: 1.

K8AK output contacts will operate (contact “a”) within the setting range for current input values (normal status).

2.

The overcurrent alarm (AL1) and undercurrent alarm (AL2) will operate as follows before the magnet contactor (RY2) is turned on (state 
without current input).

• Overcurrent alarm (AL1): Contact “b” for the approx. 1 second interval immediately after the K8AK control power supply is turned on. After that, a switch 

to contact “a” will be made as an overcurrent state is no longer present. At that time, there will be a response delay time from 
contact “b” to contact “a” of approx. 250 ms.

• Undercurrent alarm (AL2): Contact “b” for the approx. 1 second interval immediately after the K8AK control power supply is turned on. After that, because 

a state without current input will continue, an undercurrent will be detected and the status of contact “b” will continue as is.

A1

Magnet contactor for load switching OFF

K8AK

Stop button

T

A

RY1

RY1

RY1

RY2

AL1

AL2

11

14

21

24

PB2

PB1

AL1: K8AK overcurrent contacts
AL2: K8AK undercurrent contacts

Startup button

A2

T

A

Load

RY2

A1

K8AK

A2

A2

A1

K8AK

T

A

RY1

RY1

RY1

RY2

AL1

AL2

11

14

21

24

AL1: K8AK overcurrent contacts
AL2: K8AK undercurrent contacts

T

A

Stop button

PB2

PB1

Startup button

Magnet contactor for load switching ON

Load

RY2

A1

K8AK

A2

A1

K8AK

T

A

RY1

RY1

RY1

RY2

AL1

AL2

11

14

21

AL1: K8AK overcurrent contacts
AL2: K8AK undercurrent contacts

T

A

Startup button

A2

Stop button

PB2

PB1

24

Magnet contactor for load switching ON

Load

RY2

A1

K8AK

A2

Содержание K8AK-AS1 24VAC/DC

Страница 1: ...ent Transformer CT Direct input is not possible Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do not exceed the overload capacity of the K8AK AW...

Страница 2: ...mA AC DC 50 to 500 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 0 to 100 mA AC DC I2 COM Approx 1 Direct input 0 to 500 mA AC DC I3 COM Approx 0 2 Direct input K...

Страница 3: ...puts ALM Red Input impedance Refer to Input Range on previous page Output relays Two SPDT relay outputs normally closed operation Output relay ratings Rated load Resistive load 5 A at 250 VAC 5 A at 3...

Страница 4: ...minals Between input terminals and output terminals Dielectric strength 2 000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power su...

Страница 5: ...h the OMRON K8AC CT200L Current Transformer CT Wiring Example Directly Inputting a Current Using a CT Always turn on the control power supply for the K8AK at least 2 seconds before turning on the powe...

Страница 6: ...AL1 Contact b for the approx 1 second interval immediately after the K8AK control power supply is turned on After that a switch to contact a will be made as an overcurrent state is no longer present A...

Страница 7: ...K8AK power supply voltage Power ON Undercurrent AL2 contacts 21 24 Undercurrent set value AL2 30 of AL1 current set value Overcurrent AL1 contacts 11 14 Lit AL2 alarm indicator AL1 alarm indicator Ove...

Страница 8: ...ng time 0 1 to 30 s t Operating time 0 1 to 30 s t t Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Flashing Flashing Power ON lock...

Страница 9: ...ched the same level Use this as a guide to set the current The maximum setting range will differ depending on the model and the input terminal Example K8AK AW3 Using Input Terminals I3 COM The maximum...

Страница 10: ...de to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the set value Use startup lock time to prevent unwanted operation e g as a result of inrus...

Страница 11: ...figure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for...

Страница 12: ...cified torque of 0 49 to 0 59 N m Use of the product beyond its life may result in contact welding or burning Make sure to consider the actual operating conditions and use the product within its rated...

Страница 13: ...ifficult to see 15 Do not use the product if it is accidentally dropped The internal components may be damaged 16 Be sure you understand the contents of this catalog and handle the product according t...

Страница 14: ...MEMO 14...

Страница 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Страница 16: ...0169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com...

Отзывы: