(12) To allow for the startup time of peripheral devices (sensors, etc.), the H8GN starts timing operaĆ
tion between 210 to 260 ms after power is turned ON. For this reason, in operations where timing
starts from power ON, the time display will actually start from 258 ms. If the set value is 258 ms
or less, the time until output turns ON will be a fixed value between 210 and 260. (Normal operaĆ
tion is possible for set value of 259 ms or more.) In applications where a set value of 258 ms or less
is required, use start timing with signal input.