2.3 Details of Services
H8GN
2-9
(4) Response code
At normal completion
Response code
Name
Description
0000
Normal completion
No errors were found.
At occurrence of error
Response code
Error name
Cause
1002
Command too short
The command is too short.
1101
Area type error
Wrong variable type
1103
Start address outĆofĆ
range error
Write start address is out of range.
1104
End address outĆofĆ
range error
The write end address (write start
a number of elements)
exceeds the final address of the variĆ
able area.
1003
Number of elements/
data mismatch
The number of data does not match
the number of elements.
1100
Parameter error
•
Bit position is other than 00".
•
Write data is out of setting range.
3003
ReadĆonly data
Variable type C0" was written to.
2203
Operation error
•
The
communications
writing"
parameter is set to OFF" (disĆ
abled).
•
Writing was carried out on the
parameters from setup areas 0 to 1.
•
Writing was carried out on a proĆ
tected parameter other than in the
protect level.
•
CPU or EEPROM error