Solid-state timer

 

H3RN

B-103

Ti

m

e

rs

Precautions

Correct Use

When using the H3RN in any place where the ambient temperature
is more than 50

°

C, supply 90% to 110% of the rated voltages (at

12 VDC: 95% to 110%).

Do not leave the H3RN in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts may become dam-
aged. Therefore, the use of the H3RN with a relay as shown in the
following circuit diagram is recommended.

The H3RN must be disconnected from the socket when setting the
DIP switch, otherwise the user may touch a terminal imposed with a
high voltage and get an electric shock.

Do not connect the H3RN as shown in the following circuit diagram
on the right hand side, otherwise the H3RN’s internal contacts differ-
ent from each other in polarity may become short-circuited.

Use the following safety circuit when building a self-holding circuit
with the H3RN and an auxiliary relay, such as a G2R Relay, in combi-
nation.

In the case of the above circuit, the H3RN will be in pulse operation.
Therefore, if the circuit shown on page 99 is used, no auxiliary relay
will be required.

Do not use the SPDT contact in a circuit which may cause short-cir-
cuiting at three points (otherwise, short-circuiting of the power supply
may occur) because the SPDT contact of H3RN-1/-11 is composed
of an SPST-NC contact.

Do not set to the minimum setting in the flicker modes, otherwise the
contact may be damaged.

Do not use the H3RN in places where there is excessive dust, corro-
sive gas, or direct sunlight.

Make sure that there is a space of 3 mm or more between any H3RN
Models next to each other. (When using the P2RF-

@

-E Socket, a

space of 3 mm or more will be secured.) If a space of 3 mm or more
is not secured, the ambient temperature must be less than 50

°

C.

The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3RN.

Precautions for EN61812-1 
Conformance

The H3RN as a built-in timer conforms to EN61812-1 provided that
the following conditions are satisfied.

Handling

Do not touch the DIP switch while power is supplied to the H3RN.

Before dismounting the H3RN from the socket, make sure that no
voltage is imposed on any terminal of the H3RN.

Wiring

Basic insulation is ensured between the H3RN’s operating circuit and
control output.

Basic insulation:

Overvoltage category III, 
pollution degree 2 
(with a clearance of 3.0 mm and a creepage
distance of 3.0 mm at 240 VAC)

The clearance from the edge of the P2R-087P Socket to internal,
current-carrying metal parts is 1.3 mm. Position the H3RN to provide
the necessary clearance for the voltage used.
When using the P2RF-

@

-E or P2R-057P Socket, basic insulation is

ensured in the mounted condition for a voltage of 250 VAC max.

X

1

T

X

2

X

2

/b

T/a

X

1

/a

X

1

/a

X

: Auxiliary relay such as G2R Relay

Correct

Incorrect

G2R Relay

3

4

2

1

5

Short-circuit current

Power supply 
for load

Содержание H3RN

Страница 1: ...O 2 Time Range None Short time range 0 1 s to 10 min 1 Long time range 0 1 min to 10 hrs Ordering Information List of Models Accessories Order Separately Connecting Socket H3RN 1 2 Supply voltage Time limit contact Short time range model 0 1 s to 10 min Long time range model 0 1 min to 10 h 24 VAC 12 24 VDC SPDT H3RN 1 H3RN 11 DPST NO H3RN 2 H3RN 21 Note Specify both the model number and supply vo...

Страница 2: ... H3RN 21 Accuracy of operating time 1 FS max 1 s range 1 10 ms max Setting error 15 50 ms FS max Reset time Min power opening time 12 24 VDC 0 1 s max including halfway reset 24 VAC 0 5 s max including halfway reset Influence of voltage 2 FS max Influence of temperature 2 FS max Insulation resistance 100 MΩ min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between operating circuit a...

Страница 3: ... level 3 2 kV I O signal line level 4 Immunity Surge IEC51000 4 5 1 kV line to line level 3 2 kV line to ground level 3 Approved standards UL508 CSA C22 2 No 14 Conforms to EN61812 1 IEC60664 1 4 kV 2 Output category according to IEC60947 5 1 Item H3RN 1 H3RN 2 H3RN 11 H3RN 21 OUT PW Bottom View H3RN 1 H3RN 11 H3RN 2 H3RN 21 DIN Indication DIN Indication OUT PW Bottom View Timer circuit Timer circ...

Страница 4: ...t NC 4 2 Time limit contact NO 4 3 Run Power indicator PW Output indicator OUT Power 1 8 Time limit contact NO 4 3 5 6 Run Power indicator PW Output indicator OUT Flicker OFF start Power Output Power 1 5 Time limit contact NC 4 2 Time limit contact NO 4 3 Run Power indicator PW Output indicator OUT Power 1 8 Time limit contact NO 4 3 5 6 Run Power indicator PW Output indicator OUT Flicker ON start...

Страница 5: ...operating modes Nomenclature Model Time range Time setting range Setting Factory set H3RN 1 H3RN 2 1 s 0 1 to 1 s Yes 10 s 1 to 10 s No 1 min 0 1 to 1 min No 10 min 1 to 10 min No H3RN 11 H3RN 21 1 min 0 1 to 1 min Yes 10 min 1 to 10 min No 1 h 0 1 to 1 h No 10 h 1 to 10 h No Operating mode Setting Factory set ON delay Yes Interval No Flicker OFF start No Flicker ON start No Run Power Indicator Gr...

Страница 6: ...se sockets replace with 05 for SPDT or 08 for DPST NO The P2RF cannot be used because the hook is a different shape P2RF E Socket 79 5 see note 1 83 5 see note 2 80 9 see note 1 84 9 see note 2 P2R 7P Socket Note 1 The value shown indicates the dimension for the P2RF 05 E with the PFP N Mounting Rail The value is 71 5 mm when using the PFP N 2 2 The value shown in parentheses indicates the di mens...

Страница 7: ...ed of an SPST NC contact Do not set to the minimum setting in the flicker modes otherwise the contact may be damaged Do not use the H3RN in places where there is excessive dust corro sive gas or direct sunlight Make sure that there is a space of 3 mm or more between any H3RN Models next to each other When using the P2RF E Socket a space of 3 mm or more will be secured If a space of 3 mm or more is...

Страница 8: ...rest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No L090 E1 02 ...

Отзывы: