4
24-hour/Weekly Time Switch
H2F
Connections
Synchronous Motor Model
(SPST-NO Output)
H2F-D
(SPDT Output)
H2F-DC
H2F-DF
H2F-DFC
Quartz Motor Model
(SPST-NO Output)
H2F-DM/H2F-WM
(SPDT Output)
H2F-DMC/WMC
H2F-DMF/H2F-WMF
H2F-DMFC/WMFC
2
Note 1: Connect an independent power source to the load.
2: Do not exceed the following torque when tightening the screws.
Specified torque: 0.8 N·m
Maximum torque: 0.98 N·m
3: When connecting leads to the terminal block, use the same wire size for all leads. If different wire sizes are used,
the thinner leads may come off during operation.
4: Recommended lead wires: AWG18 to AWG24 (cross-section: 0.205 to 0.823 mm
2
), solid or twisted wire
5: When using crimp terminals, connect a maximum of two crimp terminals to any one terminal.