63
Troubleshooting using the LED Indicators
Section 4-2
Note
Backup/Restore Operation failed: TS LED Indicator will be Lit for 2 seconds.
SmartSlice I/O Unit
4-2-4
PROFIBUS Errors
If power supply to the Unit is correct and the Communication Unit and the
SmartSlice I/O Units are operating correctly, problems in the PROFIBUS Con-
nection can be determined using the BF LED indicator (Bus Fail) on the
PROFIBUS Communication Unit. The tables below lists the BF LED options.
Lit
Red
Backup operation failed (See Note).
Backup the data again.
Restore operation failed (See Note).
Reinstall the Unit in which the data was being
restored and turn the power ON again.
SmartSlice I/O Unit configuration error occurred. Check the following items.
• Are more than 64 I/O Units connected?
• Are more than 128 bytes of I/O data being
used?
• Has the I/O configuration changed since the I/O
configuration table was registered?
Green
The Slice bus is operating normally.
---
TS
Colour
Probable cause
Correction
Not Lit
--
Power is not being supplied to the Unit.
Refer to section
4-2-1 Power Supply Errors
.
Flashing
(1 Hz)
Red
Communication error occurred.
Check whether the connector is inserted prop-
erly.
Flashing
(2 Hz)
Green
Restore operation in progress
Wait until the restore operation is completed.
Backup operation in progress
Wait until the backup operation is completed.
Lit
Red
Unit hardware failure
Turn the power OFF and then ON again.
Replace the Unit if the error recurs.
Green
SmartSlice I/O Unit operating normally.
---
TS
Colour
Probable cause
Correction
BF
Probable cause
Correction
Not lit
No PROFIBUS Communication error encountered. The Unit is exchanging I/O data with the Master Unit.
Flashing
The PROFIBUS configuration is not correct. There is
however communication with Master Unit.
• Check the configuration and the parameter data of
the slave (See Note 1).
• Verify that the first selected I/O module is the “COM
status” Module (see Note 2).
• Verify that the selected configuration matches the
physical slice configuration attached to the PROFI-
BUS Communication Unit.
• Verify the Profibus allocation of the SmartSlice I/O
Unit is according the description. Check the Profi-
bus Diagnostics. Please refer to
Appendix B Slave
Diagnostics Message
.
Lit
The PROFIBUS configuration is not correct. There is
NO communication with master.
• Verify that the Unit has the same station address as
in the master's configuration.
• Verify that no station address is used twice.
• Verify that the Master Unit is ON-LINE.
Содержание GRT1 - 27-11-2006
Страница 1: ...OPERATION MANUAL PROFIBUS Communication Unit SmartSlice GRT1 Series GRT1 PRT Cat No W04E EN 03 ...
Страница 2: ...SmartSlice GRT1 Series GRT1 PRT PROFIBUS Communication Unit Operation Manual Revised November 27 2006 ...
Страница 3: ...ii ...
Страница 9: ...viii ...
Страница 13: ......
Страница 49: ......
Страница 95: ......
Страница 105: ...86 Explicit Messages Appendix C ...
Страница 109: ......
Страница 111: ......