79
Slave Diagnostics Message
Appendix B
Slave Diagnostics Bytes 5 to 6: Ident Number
Slave Diagnostics Bytes 5 and 6 contain the PROFIBUS Ident Number of the slave device. The Ident number
uniquely identifies the type of device. For the GRT1-PRT PROFIBUS DPV1 slave the Ident number is 098F
(Hex).
B-2
Extended Diagnostics
Module Diagnostics
The Module Diagnostics will indicate whether or not SmartSlice I/O Units have communication or configuration
errors related to the Unit.
Module Diagnostics bytes
Bit
Name
Description
00
COM Status
When set, this bit indicates that there is Diagnostics information pending related
to the COM status.
01 -
64
Module Diagnostics
When set, this bit indicates that there is Diagnostics information pending related
to the corresponding SmartSlice slot.
Header byte = 4A (Hex)
7
6
5
4
3
2
0
1
15
14
13
12
11
10
8
9
23
22
21
20
19
18
16
17
31
30
29
28
27
26
24
25
39
38
37
36
35
34
32
33
47
46
45
44
43
42
40
41
55
54
53
52
51
50
48
49
63
62
61
60
59
58
56
57
64
Fixed to 0
SmartSlice Slot 1 ~ 7, COM Status (0)
SmartSlice Slots 8 ~ 15
SmartSlice Slots 16 ~ 23
SmartSlice Slots 24 ~ 31
SmartSlice Slots 32 ~ 39
SmartSlice Slots 40 ~ 47
SmartSlice Slots 48 ~ 55
SmartSlice Slots 56 ~ 63
SmartSlice Slot 64
7
6
5
4
3
2
1
0
Byte 7
Byte 15
Byte 14
Byte 13
Byte 12
Byte 11
Byte 10
Byte 9
Byte 8
Byte 16
Содержание GRT1 - 27-11-2006
Страница 1: ...OPERATION MANUAL PROFIBUS Communication Unit SmartSlice GRT1 Series GRT1 PRT Cat No W04E EN 03 ...
Страница 2: ...SmartSlice GRT1 Series GRT1 PRT PROFIBUS Communication Unit Operation Manual Revised November 27 2006 ...
Страница 3: ...ii ...
Страница 9: ...viii ...
Страница 13: ......
Страница 49: ......
Страница 95: ......
Страница 105: ...86 Explicit Messages Appendix C ...
Страница 109: ......
Страница 111: ......