10

Solid State Relays

G3RV

Installation

Tools

G3RV-SL700 series: Flat-Blade screwdriver should be used for mounting and / or releasing cables.

G3RV-SL500 series: Flat-Blade screwdriver should be used for mounting stranded wires without ferrules and / or releasing cables.

Applicable Screwdriver

Flat-blade, Parallel-tip, 2.5 mm diameter (3.0 mm max.)

Examples:  FACOM AEF.2.5 × 75E

(AEF. 3 × 75E)

VESSEL No. 9900-(-)2.5 × 75

(No. 9900-(-)3 × 100)

WAGO 210-119
WIHA 260/2.5 × 40

(260/3 × 50)

*Chamfering the tip of the driver improves insertion when used as an exclusive tool.

Applicable Wires

Applicable Wire Sizes

G3RV-SL700 Series

Box clamp technology

G3RV-SL500 Series

Push-in technology

Tightening torque

G3RV-SL700 Series: 0.4Nm

2.5 dia. (3.0 mm max.)

Cannot be used.

 Flat-blade, Flared-tip

 Flat-blade, Parallel-tip

Wire type

Applicable wire size

Stripping length

Stranded without ferrules

0.5 - 1.5 mm

2

7 mm

Stranded with ferrules and plastic collar

0.5 - 1.5 mm

2

7 mm

Stranded with ferrules without plastic collar

0.5 - 1.5 mm

2

7 mm

Solid

0.5 - 1.5 mm

2

7 mm

Wire type

Applicable wire size

Stripping length

Stranded without ferrules

0.5 - 1.5 mm

2

12 mm

Stranded with ferrules and plastic collar

0.5 - 1.5 mm

2

12 mm

Stranded with ferrules without plastic collar

0.5 - 1.5 mm

2

12 mm

Solid

0.5 - 1.5 mm

2

12 mm

Содержание G3RV-SL500-A

Страница 1: ...t Zero cross function D DC Output MOS FET Ordering Information List of Models SSR and Socket Combinations 1 2 3 4 G3RV SL Classification Enclosure rating Input voltage Type of connection Contact form...

Страница 2: ...2 mA 21 6V 24 VAC DC 20 mA 21 mA 11 mA 21 6V 48 VAC DC 10 mA 11 mA 6 mA 43 2V 110 VAC 7 5 mA 8 2 mA 99V 230 VAC 7 3 mA 8 6 mA 207V Rated voltage Rated current Must operate voltage Must release voltage...

Страница 3: ...nce 300m s2 Ambient temperature Storage 30 to 100 C with no icing or condensation Operating 30 to 55 C with no icing or condensation Ambient humidity 45 to 85 RH Weight Approx 38 g Pollution degree 2...

Страница 4: ...titive Keep the inrush current to half the rated value if it occurs repetitively The values shown by the solid line are for non repetitive inrush currents Mounting Distance 10mm Mounting Distance 0mm...

Страница 5: ...cription Connection P2RVC 8 O F PLC Output Interface for 8x G2RV SL700 G3RV SL700 series PNP type Ribbon cable connector 10 Pole IEC603 1 Input Rated voltage 30 VAC VDC max Current capacity 0 5 A per...

Страница 6: ...ototriac Yes Green DC12V AC Yes 2A at 100 to 240VAC G3RV 202S DC12 G3RV SL700 500 A DC12 DC24V G3RV 202S DC24 G3RV SL700 500 A DC24 AC DC24V G3RV SL700 500 A AC DC24 AC DC48V G3RV SL700 500 A AC DC48...

Страница 7: ...box minimum order Red R Blue S Black B P2RVM 030 3 60 pcs box minimum order P2RVM 040 4 60 pcs box minimum order P2RVM 100 10 20 pcs box minimum order P2RVM 200 20 20 pcs box minimum order Max curren...

Страница 8: ...ption P2RV S 50 plates Provides isolation between adjacent relays to achieve 400 V isolation Five M2 5 6 6 2 max 99 2 7 1 88 9 26 1 47 2 70 9 83 106 7 max 92 7 max 35 Input circuit 24 V DC Terminal Ar...

Страница 9: ...ltage Terminal Arrangement Internal Connections Top View 12 V DC Terminal Arrangement Internal Connections Top View 6 2 max 99 2 88 9 7 1 24 6 46 69 8 82 9 106 7 max 97 4 max 35 G3RV D03SL G3RV 202S L...

Страница 10: ...sive tool Applicable Wires Applicable Wire Sizes G3RV SL700 Series Box clamp technology G3RV SL500 Series Push in technology Tightening torque G3RV SL700 Series 0 4Nm 2 5 dia 3 0 mm max Cannot be used...

Страница 11: ...osed conductor into the connection hole No other tools are required Note In case of wiring stranded wires without ferrules screwdriver should be inserted before inserting the wire Screwdriver should b...

Страница 12: ...sible to connect cables properly if the screwdriver is inserted incorrectly General Precautions Do not use the product if it has been dropped on the ground Dropping the product may adversely affect pe...

Страница 13: ...rent to be applied Abnormal heating of wire may cause burning Do not use any wires with damaged sheaths These may cause electric shock Confirm that wiring to G3RV Socket is not used in pipe or duct fo...

Страница 14: ...roduct for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS...