Wiring/Installation
E
Series Connection
Up to three sets of F3SJ-Bs can be series-connected. Series connection allows them to be used as a safety
light curtain, requiring only one set to be wired to a controller and preventing mutual interference.
If any one set of series-connected F3SJ-B is blocked, both of the safety outputs turn OFF. The indication LED
for each F3SJ-B turns ON separately.
• Number of connections: Up to three sets
• Total number of beams: Up to 192 beams
• Connection cable length between two F3SJ-Bs in series connection: 7 m max.
Ex.: Configuring an U-shaped detection zone
The terms used in this document to describe each F3SJ-B in a series connection are shown below.
Easy Type cannot be series-connected.
Easy Type
Basic Type (basic system)
Basic Type (muting system)
Secondary
sensor 2 (3CH)
Secondary
sensor 1 (2CH)
Primary
sensor (1CH)
Содержание F3SJ-B0185P25
Страница 1: ...F3SJ E P25 F3SJ B P25 Series Safety Light Curtain User s Manual Cat No SCHG 732D...
Страница 12: ...x Introduction F3SJ E B User s Manual...
Страница 16: ...xiv Introduction F3SJ E B User s Manual...
Страница 52: ...36 Chapter 2 Description of Functions F3SJ E B User s Manual System Configuration and Functions...
Страница 104: ...88 Chapter 3 Wiring F3SJ E B User s Manual Wiring Installation...
Страница 124: ...108 Chapter 4 Wiring Examples F3SJ E B User s Manual Input Output Circuit and Applications...
Страница 130: ...114 Chapter 5 Maintenance Checklists F3SJ E B User s Manual Checklists...