SELECTING A SCALE RANGE

Use the rotary DIP switch to select the temperature scale range.
The tables below show the switch setting number for each range.
The temperature indication range is the set temperature range
(full scale) 

±

10%, unless otherwise noted.

If the set temperature is shifted outside of changing the scale
range, the set temperature is displayed. It is then automatically

changed to the maximum or minimum value of the newly set
temperature scale range.

If the alarm value is shifted outside the temperature scale range
as a result of changing the scale range, it is automatically
changed to the maximum value of the newly set scale range.

Thermocouple Input Type

Thermocouple input models are factory-set to switch position 2
for a temperature range of 0

°

 to 400

°

, using a type K

thermocouple.

Switch setting

0

1

2

3

4

5

6

6

7

8

9

Temperature range

0 to 200

0 to 300

0 to 400

0 to 500

0 to 600

0 to 999

0 to 999

0 to 200

0 to 300

0 to 400

0 t0 500

Scale indication

°

C

°

C

°

C/

°

F

°

C/

°

F

°

C/

°

F

°

C/

°

F

°

F

°

C

°

C

°

C/

°

F

°

C/

°

F

Unit of measure

1

°

 C or F

Platinum RTD Type

Platinum RTD input models are factory-set to switch position 3
for a temperature range of 0.0

°

 to 99.9

°

.

Switch setting

0

1

2

3

4

5

6

7

8

Temperature range

–50 to 50

0.0 to 50.0

–20 to 80

0.0 to 99.9

0 to 200

0 to 300

0 to 400

0 to 600

0 to 800

Scale indication

°

C

°

C

°

C

°

C/

°

F

°

C/

°

F

°

C

°

C/

°

F

°

F

°

F

Unit of measure

1

°

 C or F

0.1

°

 C or F

1

°

 C or F

0.1

°

 C or F

1

°

 C or F

Note: 1. Do not set the selector switch to position 9.  This will cause error message “FFF” or “–––” to be displayed.

2. When changing scale ranges where the unit of measure changes 1

°

 to 0.1

°

 or vice versa, the set temperature also changes to

reflect the unit of measure. For example, with a set temperature of 100

°

, a change from a scale range with 1

°

 resolution to 0.1

°

makes the set temperature 10

°

; with a set temperature of 15

°

, a change in scale range resolution from 0.1

°

 to 1

°

 makes the set

temperature 150

°

.

Thermistor Input Type

Thermistor input models are factory-set to switch position 0 for a
temperature range of –50

°

 to 50C

°

.

Switch setting

0

1

2

3

4

5

6

7

8

9

Temp. range

–50 to 50

0 to 100

50 to
150

100 to
200

150 to
300

–50 to 100

0 to 200

100 to
300

200 to
400

300 to
600

Scale indication

°

C

°

F

Unit of measure

1

°

 C or F

Note: 1. The temperature indication range for a setting scale of –50

°

 to 50

°

C is –50

°

 to 60

°

C. It is the full scale 

±

10% with the other set-

ting scale ranges.

2. With a temperature range, such as 50

°

 to 150

°

C, exceeds the factory-set range, the indication unit is automatically adjusted to

the minimum value. The set temperature is displayed upon power application.

Содержание E5CS

Страница 1: ...D Pt 100 Ω DIN and JIS standards Interchangeable thermistor THE types Output Contact E5CS R1KJX F E5CS R1PX F E5CS R1GX F Voltage E5CS Q1KJX F E5CS Q1PX F E5CS Q1GX F Temperature Ranges Thermocouple Input Type Input type Type K Type J Temperature range 0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500 Scale indication C C C F C F C F C F F C C C F C...

Страница 2: ...dication accuracy 0 5 of full scale 1 digit max Display range 999 to 999 limited to input type Control Type ON OFF and PID with automatic tuning of proportional band switch selectable modes Proportional band 3 to 20 in PID mode automatically adjusted according to the rise time of the controlled system Reset time 4 minutes in PID mode Rate time 0 4 minutes in PID mode Proportional period 2 or 20 se...

Страница 3: ... to OFF changes can be made simply by pressing the Up and Down keys 5 Down key decreases the set temperature or alarm value when pressed Decreases the value quickly when held down 8 Display data identifier lights SP when the set temperature is displayed on the main display and AL when an alarm value is displayed 6 Return key changes the value displayed on the main display each time pressed 9 Red d...

Страница 4: ...al mechanism Alarm mode selector switch Protection switch Right side view Control mode selector switch Left side view Temperature range selector switch Select the desired temperature range by using the temperature range selector switch rotary DIP type The other rotary DIP switch is used to select one of eight alarm functions Be sure the set temperature and alarm values are within the new range Oth...

Страница 5: ...l output ON OFF Set temperature Switch 1 OFF Temperature controller performs ON OFF action ON 1 6 5 4 3 2 P X ON Control output ON OFF Set temperature Switch 3 ON Used for cooling operations in ON OFF action ON 1 6 5 4 3 2 P X ON PID Action Set switch 1 of the function selector DIP switch to ON to perform PID control action Follow the steps described below Determining Proportional Period Set switc...

Страница 6: ...e main display Then set the shift value by using the Up or Down key Switch 4 ON Input shift function enabled ON 1 6 5 4 3 2 P X ON Fine adjustment of the temperature indication and the resulting controlled temperature is possible without changing or affecting the set point The input shift value can be set within the range from 99 9 to 99 F or C For ranges that have resolution to 0 1 the input shif...

Страница 7: ... 0 1 2 3 4 5 6 7 8 Temperature range 50 to 50 0 0 to 50 0 20 to 80 0 0 to 99 9 0 to 200 0 to 300 0 to 400 0 to 600 0 to 800 Scale indication C C C C F C F C C F F F Unit of measure 1 C or F 0 1 C or F 1 C or F 0 1 C or F 1 C or F Note 1 Do not set the selector switch to position 9 This will cause error message FFF or to be displayed 2 When changing scale ranges where the unit of measure changes 1 ...

Страница 8: ...dby sequence 6 Upper limit alarm with standby sequence 7 Lower limit alarm with standby sequence 8 Absolute value alarm Alarm value setting range Y must be within the temperature scale range Standby Sequence Alarm functions with standby sequence suppress nuisance alarms when the controller is first powered up As shown in the temperature charts at right the alarm output is suppressed until the temp...

Страница 9: ...ing heating reverse operation OFF during cooling normal operation fff blinks 1 Failure has occurred in thermocouple or platinum RTD 2 Temperature has risen much beyond scale range OFF blinks 1 Failure has occurred in platinum RTD 2 Polarities positive and negative of thermocouple are reversed 3 Temperature has fallen much below scale range OFF e11 or e33 1 Memory failure E11 display 2 Analog to di...

Страница 10: ...splashes of water or oil and high temperatures Separate the temperature controller from equipment that generates strong high frequency electrical noise such as welding equipment Sensor Input Connections The lead wires connecting the platinum RTD to the temperature controller must be separated from the power lines an the load lines wherever possible to prevent them from being inducted by electrical...

Отзывы: